Page 15
CBX32MV SERIES
SENSOR
(CENTER SIDE−T0 −SIDE)
9−PIN
CONNECTOR
SECURING
SCREWS
AIR
HANDLER
CONTROL
AIR HANDLER CONTROL
L−BRACKET MOUNTING PLATE
19 IN.
(483 MM)
5−1/2 IN.
(140 MM)
9−PIN CONNECTOR
ELECTRIC HEAT RELAY
PART NO. 49W91
22V DIRECT CURRENT COIL
30 AMP CONTACT RATING
FASTEN THE PROBE
BRACKET TO THE
PLENUM WITH TWO
SELF−TAPPING SHEET
METAL SCREWS.
CONNECT WIRES TO DISCHARGE AIR SENSOR
TERMINAL ON AIR HANDLER CONTROL.
PLENUM
CBX32MV AIR HANDLER CONTROL
PART NO. 50W28
DISCHARGE SENSOR
(DAT)
TEMP RESISTANCE
ºF
(OHMS)
30
34,566
40
26,106
50
19,904
60
15,313
70
11,884
80
9,298
90
7,332
100
5,826
DETAIL A
NOTE EVENHEAT MODE CANNOT BE ENABLED WITH
HARMONY III DUE TO EACH CONTROL REQUIRING ITS OWN
DISCHARGE AIR SENSOR.
THE AIR HANDLER CONTROL (AHC) HAS
TWO SCREW TERMINALS MARKED
DISCHARGE AIR SENSOR. THE SENSOR
IS REQUIRED FOR EVENHEAT
OPERATION, IS FIELD−MOUNTED AND
MUST BE ORDERED SEPARATELY
(CATALOG # 88K38).
DETAIL B
TEMPERATURE RESISTANCE
CHART
NOTE − Due to varying duct designs
and airflow conditions, relocation of the
discharge sensor may be required to
insure accurate sensing.
Figure 15. Component Connections