Page 25
CBX32MV SERIES
Target CFM Tables
CBX32MV-018/024
BLOWER PERFORMANCE 0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range
ADJUST
Jumper
Setting
Jumper Speed Positions
HEAT Speed
COOL Speed
1
2
3
4
1
2
3
4
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
715
337
855
405
1000
470
1130
535
465
220
690
325
900
425
1050
495
NORM
670
315
770
365
900
425
1035
490
425
200
620
290
825
390
950
450
−
580
275
700
330
800
375
930
440
385
180
560
265
735
345
850
400
CBX32MV-024/030
BLOWER PERFORMANCE 0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range
ADJUST
Jumper
Setting
Jumper Speed Positions
HEAT Speed
COOL Speed
1
2
3
4
1
2
3
4
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
800
380
935
440
1070
505
1210
570
660
310
880
415
1100
520
1320
625
NORM
725
340
850
400
975
460
1100
520
600
285
800
380
1000
470
1200
565
−
655
310
765
360
880
415
990
470
540
255
720
340
900
425
1080
510
CBX32MV-036
BLOWER PERFORMANCE 0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range
ADJUST
Jumper
Setting
Jumper Speed Positions
HEAT Speed
COOL Speed
1
2
3
4
1
2
3
4
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
1230
580
1335
630
1445
680
1545
730
1090
515
1225
580
1380
650
1545
730
NORM
1120
530
1215
575
1315
620
1400
660
975
460
1125
530
1275
600
1400
660
−
1010
475
1185
560
1200
565
1265
595
900
425
1000
470
1135
535
1265
595
CBX32MV-048 AND CBX32MV-060
BLOWER PERFORMANCE 0 through 0.80 in. w.g. (0 Through 200 Pa) External Static
Pressure Range
ADJUST
Jumper
Setting
Jumper Speed Positions
HEAT Speed
COOL Speed
1
2
3
4
1
2
3
4
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
1850
875
1960
925
2090
985
2150
1015
1625
765
1820
860
2055
970
2145
1010
NORM
1705
805
1800
850
1900
895
2005
945
1425
670
1625
765
1805
850
2005
945
−
1560
735
1625
765
1720
810
1770
835
1205
570
1375
650
1555
735
1725
815
CBX32MV-068
BLOWER PERFORMANCE 0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range
ADJUST
Jumper Setting
Jumper Speed Positions
HEAT Speed
COOL Speed
1
2
3
4
1
2
3
4
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
1875
885
1975
930
2090
985
2150
1015
1640
775
1840
870
2075
980
2150
1015
NORM
1760
830
1825
860
1920
905
2030
960
1465
690
1625
765
1800
850
2000
945
−
1550
730
1650
780
1725
815
1800
850
1250
590
1390
655
1560
735
1720
810
NOTES − The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III
t
Zone Control applications − minimum blower speed is 300 cfm (145 L/s)