
8
All lines must be individually insulated.
1. The seal on the mode selection box refrigerant piping
connections should remain in place until the last
possible moment. This will prevent dust or water from
getting into the refrigerant piping before it is connected.
2. Remove the black plastic caps from the mode selection
box connections and discard.
3. Slide
the
fl
are nuts onto the ends of the
fi
eld-provided
refrigerant piping
before
using a suitable
fl
aring tool to
fl
are the end of the copper pipe.
4. Apply recommended R-410A refrigerant lubricant to the
outside of the
fl
ared refrigerant lines (Figure 5-A).
5. Align the threaded connections with the
fl
ared refrigerant
lines. Tighten the
fl
are nuts lightly at
fi
rst to obtain a
smooth match (Figure 5-B).
Size
(Btuh)
Liquid Line
in.
Vapor Line
in.
7000
12000
15000
1/4
1/2
18000
24000
30000
36000
48000
3/8
5/8
Table 2. Refrigerant Piping Connections
(Up to a maximum of 32 ft. only)
6. Then, use two wrenches to continue to tighten the nuts
without twisting the pipes. Once snug, continue another
half-turn on each nut which should create a leak-free
joint. A torque wrench may be used to tighten
fl
are
nuts using table 3 recommendations. See Figure 6.
Do
not over-tighten a fl ared joint. Flared connections
should always be accessible and must be insulated
to prevent condensation.
7. After refrigerant piping has been installed and checked
for leaks, apply insulation over the piping and all
fl
are
connections.
A
B
CANT ON THE OUTSIDE OF
THE FLARE
MALE FLARE
CONNECTION
Figure 5. Making Connections
(Male to Female Connection)
Figure 6. Tighten Flare Nut
To
Mode
Selection
Box
To Indoor Unit
Backup
Wrench
Torque
Wrench
Always refer to the provided piping diagram for correct pip-
ing sizes. Contact Lennox VRF Application support for as-
sistance with piping sizing or an updated piping diagram.
NOTE - 5/8” and 3/8” fl are nuts are part of the reducing
adapters. Cut the reducing adapters to release the 5/8”
and 3/8” fl are nuts.
IMPORTANT
Always use two wrenches when tightening
fl
are nuts to
avoid twisting refrigerant piping. DO NOT over-tighten
fl
are nuts.