Lennox V8MSBB01 Скачать руководство пользователя страница 5

5

Mode Selection Box Location

Consider the following items when positioning the mode
selection box for installation:
• 

Sounds are made by refrigerant as solenoid valves 
open and close inside the mode selection box. Do not 
install the mode selection box where these sounds 
may disturb building occupants.

• 

The mode selection box must be sloped 1/8” toward 
condensate drain outlet. 

• Provide 

suf

fi

 cient clearance around mode selection 

box to allow 3 feet of straight pipe before the 

fi

 rst 

elbow or branch pipe is installed. See Figure 3.

• 

If the unit is being installed in an application that 
includes a sheet rock (plasterboard) ceiling, it is 
required that an access panel be installed in a 
suitable location. This will also allow access for 
future maintenance (requirement of Lennox warranty 
program).
Access is required during the commissioning process 
to check the internal components, solenoid valves and 
associated 

fl

 are nuts (See page 3), and to check the 

local disconnect.

ANGLE IRON

BOLTED IN PLACE

ACROSS WOODEN JOISTS

WOODEN JOIST

Ǫ´7+5($'(

D

ROD

ANGLE IRON

ACROSS

WOODEN JOISTS

$1&+25

CONCRETE CEILING

USING ANCHORS

Ǫ´7+5($'(

D

ROD

STRUCTURAL CEILING

LEVELING NUT

Ǫ´7+5($'('

52'

SUSPENSION

BRACKET

SUSPENSION

BRACKETS

%2;08676/23(´

72:$5'&21'(16$7('5$,1&211(&7,21

Mode Selection Box Installation

Use the provided suspension brackets to suspend the 
mode selection box(es) between the outdoor and indoor 
units. The mode selection box location must be able to 
accommodate the size of the box, as well as the required 
3 feet of straight pipe length between the box and the 

fi

 rst 

elbow or branch pipe. Refer to the dimension drawing on 
Page 3 and Figure 3.

1.  Make sure that the structural ceiling is able to support 

the weight of the mode selection box(es). It may be 
necessary to add extra support. If the structural ceiling 
is constructed of concrete, install anchors to accept 
four 

 inch threaded rods to suspend the mode 

selection box. If the structural ceiling includes wooden 
joists, use angle iron or a Unistrut channel 

fi

 xed 

securely in place to accept the 

 inch threaded rods. 

See Figure 1. 

Figure 1. Suspending Methods

Figure 2. Suspension Hardware

NOTE - Threaded rod (requirement of Lennox 
warranty program) is the ONLY acceptable method of 
suspending the unit; do not use chains or straps.

2.  Slide one nut and one washer onto each threaded rod. 

Use electrical tape to keep the washer from failing off. 
Position the nuts slightly above the 

fi

 nal resting place 

of the four suspension brackets.

Model No.

Application

V8MSBB01*

1 group, 1 indoor unit maximum

V8MSBB02

2 groups, 4 indoor units maximum per group,

8 indoor units maximum

V8MSBB03

4 groups, 4 indoor units maximum per group,

16 indoor units maximum

V8MSBB04

6 groups, 4 indoor units maximum per group

24 indoor units maximum

*Use with VHIA072 and VHIA096 only.

Table 1. Mode Selection Boxes

3.  Raise the mode selection box and insert the threaded 

rods into the suspension brackets. Slide a washer 
and then a nut onto each rod below each suspension 
bracket. Use the leveling nut (beneath suspension 
bracket) to adjust the mode selection box. Remove 
the electrical tape holding the upper washers and nuts 
in place and tighten each of the four nuts above the 
brackets down onto the brackets. The mode selection 
box must be sloped 1/8” toward condensate drain 
outlet. 

4.  Continue with refrigerant piping connections.

 IMPORTANT

The Clean Air Act of 1990 bans the intentional venting 
of refrigerant (CFC’s and HCFC’s) as of July 1, 1992. 
Approved methods of recovery, recycling or reclaiming 
must be followed. Fines and/or incarceration may be 
levied for non-compliance.

Содержание V8MSBB01

Страница 1: ...A heat recovery units indoor units branch pipes line sets and controls V8MSBB04 Shown These instructions are intended as a general guide and do not supersede local codes in any way Consult authorities...

Страница 2: ...llation If changes are required a new piping diagram will be produced and will supersede all other previously provided documents Failure to provide this information regarding changes to the original d...

Страница 3: ...29 19 1 4 489 V8MSBB02 24 3 4 629 19 1 4 489 V8MSBB03 37 3 4 959 32 1 4 819 V8MSBB04 37 3 4 959 32 1 4 819 Model No Pipe Diameter in Connections to Outdoor Unit Connections to Indoor Unit Low Pressure...

Страница 4: ...LING SUSPENDED CEILING PIPE HANGER REFRIGERANT PIPE 59 1500 Maximum 59 1500 Maximum Required Suitably sized access panel required to provide full access to electrical panel Suitably sized access panel...

Страница 5: ...weight of the mode selection box es It may be necessary to add extra support If the structural ceiling is constructed of concrete install anchors to accept four inch threaded rods to suspend the mode...

Страница 6: ...capacity and abnormally high operating pressures and may result in system failure or explosion Insulate all refrigerant piping Refrigerant pipes may be very hot during unit operation Do not allow con...

Страница 7: ...or units See Table 1 and Figure 4 Outgoing gas and liquid connections for the indoor units are on the front of the box Connections to the indoor units are made using the provided brass flare nuts Adap...

Страница 8: ...enches to continue to tighten the nuts without twisting the pipes Once snug continue another half turn on each nut which should create a leak free joint A torque wrench may be used to tighten flare nu...

Страница 9: ...1 4 Yes Factory Supplied 5 8 x 3 8 No 12 000 1 2 x 1 4 1 2 x 1 4 Yes Factory Supplied 5 8 x 3 8 No 15 000 1 2 x 1 4 1 2 x 1 4 Yes Factory Supplied 5 8 x 3 8 No 18 000 5 8 x 3 8 5 8 x 3 8 No 3 4 x 1 2...

Страница 10: ...ID 7 8 OD 7 8 ID 7 8 ID 1 ID 5 8 ID 3 4 OD 7 8 ID 1 2 ID 5 8 ID 3 4 OD 7 8 ID 7 8 OD 7 8 ID 7 8 ID 1 ID 5 8 ID 3 4 OD 7 8 ID 1 2 ID 1 2 ID 5 8 OD 3 4 ID 3 4 OD 3 4 ID 3 4 ID 7 8 ID 1 2 ID 5 8 OD 3 4 I...

Страница 11: ...gnation Outdoor Unit Connection Pipe g1 g2 g3 G1 Outdoor Unit Branch Pipe Assembly L M Main Pipe L1 Indoor Unit Main Pipe L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 Branch Pipe Assembly between Main Pipe...

Страница 12: ...e Figure 7 NOTE A maximum of four indoor units can be connected to one port on the Mode Selection Box The combined maxi mum capacity of all indoor units connected to one port on a Mode Selection Box m...

Страница 13: ...h OD condensate drain connection is provided on the mode selection box Route condensate piping to a suitable drain per best practices taking care to slope the drain properly to ensure drainage A 1 inc...

Страница 14: ...Legend Power Distribu on Box L1 L2 L3 MS Box MS Box L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 PQE PQE PQE PQE L1 L2 L1 L2 L1 L2 L1 L2 PQE PQE PQE PQE PQE L1 L2 L3 L1 L2 L3 L1 L2 L1 L2 Single Phase po...

Страница 15: ...15 Figure 12 Typical Communication Wiring Diagram VRF Heat Recovery System NOTE Each communication wire from the mode selection box should follow the refrigerant piping for that port...

Страница 16: ...1 1 2 1 2 P Q E INDOOR UNIT INDOOR UNIT P Q E P Q E P Q E EXVA 208 230V M O M I TRANS T2C1 T2C2 CN10 CN13 TO OUTDOOR TO INDOOR 1 2 S1 O N L1 L2 Y G YEIIOW GRAY BLACK BLACK RED BROWN 1 MS UNIT 1 MS UN...

Страница 17: ...ons cable must match indoor piping connections 2 MS UNIT 1 MS UNIT P Q E OUTDOOR UNIT 1 MS UNIT MS INDOOR MS OUTDOOR NO 6 NO 5 NO 4 NO 3 NO 2 NO 1 P Q E 1 2 3 4 5 6 1 2 3 4 5 6 P Q E P Q E P Q E P Q E...

Страница 18: ...all other piping sizes Figure 17 Piping for VHIA072 or 096 when V8MSBB01 is Equal To or Less Than 15 ft 4 5 m Away VRA Heat Recovery 3 8 5 8 VHIA072 096 V8MBB01 V8MBB01 Piping and Wiring Connection t...

Страница 19: ...iring Connect PQE wiring to Board A of the VHIA072 or 096 Indoor unit Incoming liquid line connection Incoming suction line connection Connect these two pipes as shown in A below Connect these two pip...

Страница 20: ...COOLING MODE 6 MAIN HEATING MODE LED Lamp Normally ON Slow Flash Flash LED 1 Outdoor unit ON Outdoor unit standby Outdoor unit communication error LED 2 Indoor unit ON of this MS Indoor unit OFF this...

Страница 21: ...operation mode is cooling under the port 6 T2 average of indoor units under the port if operation mode is heating under the port T2B average of indoor units under the port if operation mode is coolin...

Страница 22: ...22 Technical Support 1 844 GET VRF1 1 844 438 8731 vrftechsupport lennoxind com www LennoxVRF com Download the app from the Apple App Store or the Google Play store...

Отзывы: