background image

9

Snowfall

> 12 in. (305 mm)

Additional Rooftop Mounting Guidelines

•  The low ambient cooling hood increases the overall 

height of the unit and therefore makes it more suscep-

tible to wind stresses. Ensure that unit is secured to 

its support using either lag bolts or safety strap. See 

Figures 5, 6 and 7. 

•  Outdoor units should be located in an area protected 

from prevailing winds. Hood discharge should be di-

rected away from or perpendicular to the prevailing 

winds; never toward prevailing winds. 

• 

Add  an  additional  12  in.  (305  mm)  to  the  standard 

mounting clearances. See Page 6.

•  For all roof top and other high wind installa-

tions, weather resistant safety straps must 

be securely fastened between the discharge 

air hood and the equipment support system. 

 

Straps should not be installed where ser-

vice access is impeded or restricted. 

 

Straps should be a minimum 3/16” vinyl coated cable. 

See Figures 6 and 7.

•  Straps must be attached to the hood where they 

will not interfere with the movement of the dampers.  

Attachment to both the hood and mounting structure 

is to be with a bolt through connection using a bolt ¼” 

or larger in diameter.

Weather Resistant

Safety strap

Figure 4. Elevate Unit Above Snow Level

Figure 5. Secure Unit to Weather Resistant Support

Φ 3/8 in (10 mm)

Lag

 

bolt

Figure 6. Secure Unit with Safety Strap (Back)

Due to wind resistant construction, Low ambient cool-

ing kits are better suited for ground level applications. 

Should low ambient applications require the outdoor unit 

to be installed in elevated areas such as a roof top it is im-

portant to follow all installation guidelines and to observe 

local and national equipment fastening guidelines. 

Figure 7. Secure Unit with Safety Strap (Sides)

•  The outdoor unit and equipment support should be 

firmly attached to the structure. Or, if the equipment 

support is the type that does not attach to the struc-

ture, refer to the equipment support manufacturer’s 

guidelines for proper size and construction.

•  Depending on location, exposure and other factors in-

fluencing the wind, Additional support (or cables) may 

be required.

Содержание V8LAC01

Страница 1: ...ired in order for the appliance to satisfactorily meet the ap plication needs must be made by a licensed profes sional HVAC installer or equivalent using factory specified parts Do not use this system...

Страница 2: ...CAUTION As with any mechanical equipment contact with sharp sheet metal edges can result in personal injury Take care while handling this equipment and wear gloves and protective clothing To ensure pr...

Страница 3: ...ing Hood Assembly with Damper Control Box 1 Rear Wind Deflector 1 Side Wind Deflectors 2 LAKA 3 LAKB 1 LAKB 2 LAKB 3 V8LAC01 V8LAC02 Low Ambient Cooling Hood Assembly with Damper Control Box 1 Rear Wi...

Страница 4: ...4 LAKA 6 10 Ton Outdoor Unit Dimensions inches mm LAKA 2 LAKA 3 44 3 8 1127 45 5 8 1159 14 3 8 371 51 1295 51 1295 23 584 24 3 8 619 14 3 4 375 LAKA 1 31 1 8 791 29 1 8 740 27 3 4 705 55 1397 53 1346...

Страница 5: ...5 LAKB 12 16 Ton Outdoor Unit Dimensions inches mm 17 1 8 435 34 1 4 870 30 1 2 775 31 3 4 806 72 1 4 1835 68 1 8 1730 59 3 4 1518 61 1 8 1553 15 3 8 391 56 1 2 1435 24 5 8 625 23 1 4 590 56 1 2 1435...

Страница 6: ...ow Air Flow 39 991 39 991 Front Front 39 991 39 991 Front Front 31 800 Air Flow Air Flow Air Flow Air Flow Air Flow Air Flow 39 991 Front Front 12 in 305 mm 156 in 3962 mm 39 991 12 in 305 mm 156 in 3...

Страница 7: ...ions near walkways and egresses Use heated tape on condensate drain line Locate unit so winter prevailing winds do not blow directly on to the outdoor unit In heavy snow areas do not locate the unit w...

Страница 8: ...Side 30 in 762 mm Minimum Recommended Service Clearance Right Side 12 in 305 mm NOTEs Discharge air duct will remain free of obstructions at a minimum distance of 18 ft 5 5 m Discharge air shall not...

Страница 9: ...here they will not interfere with the movement of the dampers Attachment to both the hood and mounting structure is to be with a bolt through connection using a bolt or larger in diameter Weather Resi...

Страница 10: ...e securing 4 Install the side screws part way first and then hang the wind deflector over the coil 5 Install remaining screws and tighten all screws se curely Repeat with all wind deflectors 6 It is n...

Страница 11: ...LAKB 2 Back Wind Deflector LAKB 2 consists of one back wind deflector and two corner guards as shown in this illustration Hood Assembly Damper Motor LAKA B 3 Left Side Wind Deflector LAKA B 3 Right Si...

Страница 12: ...y Use caution when screwing in the self tapping screw DO NOT damage coil Self tapping screws allowed in this section of the outdoor unit only Use caution when screwing in the self tapping screw DO NOT...

Страница 13: ...ut 1 Open outdoor unit left side service panel 2 Locate outdoor unit control board Figure 14 3 Locate CN1 and CN3 connections on the PCB of the low ambient cooling kit hood damper Figures 13 16 4 Loca...

Страница 14: ...3 5 2 1 Red Black White Orange 0 10V Input 0 10V Output AC24V GND CN1 Main borad Outdoor Unit Main Control Box Power Communication BUS Control Box Mounted on Hood CN4 CN3 Figure 16 Connection Diagram...

Страница 15: ...Outdoor unit sub2 unit PQ main unit PQ MS Box PQ PQ MS Box PQ PQ H1 H2 H1 H2 H1 H2 Outdoor Unit Communication Terminal Block P Q H1 H2 X Y O A K1 K2 MS Box Communication Terminal Block P Q Indoor Unit...

Страница 16: ...es and any refrigerant piping inside the cabinet If necessary use plastic zip ties included with the kit to secure away from refrigerant piping Damper Position Setting Set the rotation switch at 0 act...

Отзывы: