Shipping and Packing List
Package 1 of 1 contains;
1 – Wired Controller
2 – Plastic spacers
3 – Screws
1 – Installation and operation manual
General
The V0STAT54P-3 is a wired non-pro-
grammable local controller that controls
up to 16 VRF indoor units. These instruc-
tions are intended as a general guide and
do not supersede local codes in any way.
Consult authorities having jurisdiction be-
fore installation.
Requirements
• Four-conductor, 18-gauge, stranded,
shielded, polarity-sensitive cable is re-
quired for installation.
• Be sure that the indoor unit power sup-
ply has been turned off before begin
-
ning installation.
• This controller should be used only as
described in this manual.
• Do not install the controller on outside
walls (where there is unconditioned
space on opposite side of wall) or in
locations where direct sunlight may be
present.
Installation
Clean controller using a clean,
damp cloth. Do not spray cleanser
on or around controller.
Do not install controller in areas
where harmful gases containing
sulfur or other damaging agents
may exist or the controller may be
damaged.
CAUTION
!
Power wiring between controller and
first indoor unit:
• Minimum 18 AWG stranded shielded
cable up to 164 feet (50 m).
• Ensure there are no gaps between
the controller back cover and the
mounting surface.
• Fill any holes in the wall behind the
controller to avoid false readings from
infiltration.
• Ground the shielded control wiring at
the indoor unit.
• Do not use a megger to test insulation.
Communication wiring between indoor
units:
• Minimum 18 AWG stranded shielded
cable.
CAUTION
!