15
No.
Function
Value
Description
Note
11
Setpoint
Control
Resolution
0
1°F/.5°C
(Default)
Set the setpoint resolution.
Cooling/heating will begin
when the room temperature
is the set value above or
below the setpoint.
1
2°F/1°C
12
Auto mode
change over
time
15
15 minutes
(default)
Set the minimum time gap
between heating and cooling
changeover.
30
30 minutes
60
60 minutes
90
90 minutes
13 Auto mode dead
band limit
3 (°F/°C)
3 (°F/°C)
(Default)
Set the cooling and heating
setpoint gap of auto mode.
4 (°F/°C)
4 (°F/°C)
5 (°F/°C)
5 (°F/°C)
6 (°F/°C)
6 (°F/°C)
7 (°F/°C)
7 (°F/°C)
14
Auto mode
dead band limit
- type
0
Minimum dead
band (default)
Set the cooling and heating
setpoint gap is a minimum
limit value of a fixed value.
1
Fixed dead band