16
No.
Function
Value
Description
Note
15
External Static
Pressure
0~25
Set value * 25 in.
wg (10Pa)
Set the indoor unit external
static pressure, only applies
to ducted indoor units. One
controller to one indoor unit
connections only.
16
Draft prevention
59°F(15°C)
59°F (15°C)
default
When the indoor unit is in
heating, when the coil tem-
perature is lower than the
set value, the indoor unit fan
will force to run low speed or
stop for preventing providing
cold air.
68°F(20°C)
68°F (20°C)
75°F(24°C)
75°F (24°C)
79°F(26°C)
79°F (26°C)
17
Indoor unit fan
setting when
cooling satisfied
- -
OFF (default)
Set the indoor unit fan status
when cooling is satisfied.
1
Low speed
2
Medium speed
3
High speed
F
Maintain last
speed