Controller is located on the right side of the controls hat

section above compressor(s). The controller sensor is

located in the water compartment.

FIGURE 30

S116 ANTIFREEZE CONTROLLER

SET

FIGURE 31

S116 CONTROLLER FUNCTION IN HEATING MODE

ON

OFF

ON

OFF

Stage 1 Electric Heat
S1

47°F (default OFF)

DIF1

5°F (default differential ON at 42°F)

Mode

H1

(heating mode)*

Stage 2 Circulate Water
S2

42°F (default OFF)

DIF2

5°F (default differential ON at 37°F)

Mode

H2

(heating mode)*

*Mode must be set to H1 or H2 (heating); serious unit dam­
age to unit may result if C1 or C2 (cooling) mode is applied.

Stage 1 Electric Heat

Stage 2 Circulate Water

S1 Stage 1 Setpoint

S2 Stage 2 Setpoint

Antifreeze / Water Mixture

Controller is factory-set for 100% water mixture. When an
antifreeze/water mixture is used, controller settings may
be adjusted. See table 18 for antifreeze/water mixture
freezing points. Antifreeze type and mixture will affect
capacity and pressure drop.

TABLE 18

ANTIFREEZE MIXTURE FREEZING TEMPERATURES

% By

Volume

0%

10%

20%

30%

40%

50%

Propylene
Glycol

32

°

F

26

°

F

18

°

F

7

°

F

-8

°

F

-29

°

F

Ethylene
Glycol

32

°

F

23

°

F

14

°

F

2

°

F

-13

°

F

-36

°

F

Methanol

32

°

F

20

°

F

0

°

F

-15

°

F

-40

°

F

-65

°

F

Determining Setpoints

Set stage 1 to initiate a minimum of 10°F above the

antifreeze/water mixture freezing point. Set stage 2 to

initiate a minimum of 5°F above the antifreeze/water

mixture freezing point.

For example, the freezing point of a 10% mixture of

ethylene glycol and water is 23°F. Stage 1 initiation of

electric heat should be no less than 33°F (S1 - DIF1 or

38°F - 5°F = ON at 33°F). Stage 2 initiation of water

circulation should be no less than 28°F (S2 - DIF2 or 33°F

- 5°F = ON at 28°F).

Important - Setting the temperature too close to the

freezing temperature of the antifreeze/water mixture

could result in serious unit damage.

Adjusting Setpoints

Use the controller SET and UP/DOWN arrow keys to

adjust settings. See figure 30. The menus are sequential

in the following order:

Fahrenheit / Celsius

S1 (Stage 1 temperature)

DIF1 (Stage 1 differential)

H1 (Stage 1 htg./clg. mode)

S2 (Stage 2 temperature)

DIF2 (Stage 2 differential)

H1 (Stage 2 htg./clg. mode)

Use the UP/DOWN arrow keys to adjust the setting and

the SET key to save the change and advance to the next

selection. If no keys are pressed for 30 seconds the

switch will save any changes and return to the main

display screen.

1- Press the SET key once to access the Fahrenheit /

Celsius mode. F should be displayed. If not, use the
UP/DOWN arrow keys to toggle from C to F.

2- Press the SET key again to access Stage 1

Temperature. S1 will blink and the screen will display
the current temperature setting (47°F). Use the
UP/DOWN arrow keys to adjust the temperature.

Содержание SW 036

Страница 1: ...eneral Page 6 Safety Page 6 Unit Support Page 7 Duct Connection Page 7 Rigging Unit For Lifting Page 7 Condensate Drains Page 8 Water Supply Connections Page 8 Water Bypass Loop Page 11 Bleed Air From...

Страница 2: ...1 CHARGE COMPENSATOR 2 STG 2 WATER TO REFRIGERANT COIL SEE FIGURE 7 STG 2 WATER FLOW CONTROL VALVE SEE FIGURE 7 SW 240 Parts Arrangement STG 1 WATER FLOW CONTROL VALVE SEE FIGURE 8 STG 2 WATER FLOW CO...

Страница 3: ...5 1 4 133 41 3 8 1050 3 1 2 89 37 7 8 962 53 1 8 1350 12 1 2 318 OUTDOOR AIR CIRCUIT BREAKER COVER 4 1 4 108 ECONOMIZER DAMPERS Factory Installed Option 1 25 12 1 2 318 18 457 5 1 4 133 1 1 2 38 CONT...

Страница 4: ...964 12 3 8 314 12 3 8 314 13 3 8 340 OUTDOOR AIR CIRCUIT BREAKER COVER 4 1 4 108 ECONOMIZER DAMPERS Factory Installed Option OUTDOOR AIR HOOD For Outdoor Air Dampers 4 102 4 102 BOTTOM POWER ENTRY 5 x...

Страница 5: ...stalled OPTIONAL OUTDOOR AIR HOOD Factory or Field Installed COMPRESSOR 1 3 4 45 BOTTOM WATER ENTRY WATER TO REFRIGERANT COIL 17 3 8 440 CENTER OF GRAVITY FF EE BB 3 X 12 76 X 305 BOTTOM WATER ENTRY 2...

Страница 6: ...Code ANSI NFPA No 70 1984 is available from National Fire Protection Association 1 Batterymarch Park PO Box 9101 Quincy MA 02269 9101 The unit is ETL certified as a heat pump with cooling and with or...

Страница 7: ...r linear foot 5mm per linear meter in any direction 3 Frame or supports must be high enough to prevent any form of moisture from entering unit Recommended minimum frame height is 14 356mm 4 Duct must...

Страница 8: ...onnections See dimensions in the front of this manual 1 Remove two piece cover and install black iron pipes through openings in base Extend pipes 3 6in 76 152mm above the opening Use the following dia...

Страница 9: ...FOUR SCREWS FIGURE 6 WATER TO REFRIGERANT CIRCUIT SW 036 060 WATER IN MANUAL AIR VENT WATER TO REFRIGERANT COIL WATER OUT B39 WATER FLOW CONTROL VALVE ON OFF STRAINER THREE WAY VALVE IN BYPASS POSITIO...

Страница 10: ...RS FLEXIBLE MESH BY PASS HOSE DRAIN VALVE WITH HOSE END CONNECTION FIGURE 8 WATER TO REFRIGERANT CIRCUIT SW 240 WATER TO REFRIGER ANT COIL STG 1 B39 STG 1 WATER FLOW CONTROL VALVE ON OFF MANUAL AIR VE...

Страница 11: ...water inlet valve to main loop position If running water is not heard circulating make sure the main system pump is running 3 Slowly open the manual air vent bleed port s When the venting stops close...

Страница 12: ...ood to unit 2 Pivot hood as shown in figure 12 and secure sides of hood to unit mullions with two sheet metal screws on each side 120 240 Units Outdoor air hood is shipped folded down over the horizon...

Страница 13: ...d 6 Install back filter bracket on unit division panel as shown in figure 16 7 Secure side seals to the hood sides as shown in figure 17 8 Install longer front filter bracket on hood top as shown in f...

Страница 14: ...they must be routed away from line voltage wiring C Wiring Connections This unit is equipped with a series of integrated modular control IMC boards which control unit function Refer to the IMC manual...

Страница 15: ...up mode Refer to the IMC manual provided with each unit to change ECTO options See figure 19 for field wiring FIGURE 19 16 17 TB1 24 VOLT FIELD WIRING IN ZONE SENSOR MODE IMC in Zone Sensor Mode ECTO...

Страница 16: ...blower shaft RPM Air filters must be in place when measurements are taken 2 With all access panels in place measure static pressure external to unit from supply to return 3 Referring to tables 2 throu...

Страница 17: ...Motor shaft and blower shaft must be parallel 4 Tighten two bolts on other side of base BELT TENSION ADJUSTING BOLT TURN CLOCKWISE TO TIGHTEN FIGURE 22 BLOWER ASSEMBLY SW 240 TO INCREASE BELT TENSION...

Страница 18: ...to center of span X with enough pressure to deflect belt 1 64 for every inch of span length or 0 4mm per 25 4mm of span length Example Deflection distance of a 40 span would be 40 64 or 5 8 Example De...

Страница 19: ...0 94 991 1 03 1049 1 09 1086 1 13 1132 1 16 2500 907 0 94 968 1 04 1022 1 12 1069 1 16 1113 1 20 1159 1 23 Air Volume cfm EXTERNAL STATIC PRESSURE Inches Water Gauge Drive 0 70 0 80 0 90 1 0 1 10 1 20...

Страница 20: ...06 1107 1 09 2400 876 0 86 934 0 94 991 1 03 1040 1 09 1086 1 13 1132 1 16 2500 907 0 94 968 1 04 1022 1 12 1069 1 16 1113 1 20 1159 1 23 Air Volume cfm EXTERNAL STATIC PRESSURE Inches Water Gauge Dr...

Страница 21: ...2 27 4400 1 669 1 72 699 1 87 730 2 01 761 2 14 791 2 25 820 2 35 849 2 44 4600 693 1 92 724 2 07 755 2 21 785 2 34 814 2 45 842 2 54 871 2 62 4800 718 2 14 749 2 29 780 2 43 809 2 54 837 2 64 865 2 7...

Страница 22: ...2 91 7200 426 1 45 467 1 82 505 2 10 541 2 36 574 2 65 606 2 86 638 3 02 7400 435 1 55 475 1 93 513 2 22 548 2 49 580 2 77 612 2 98 644 3 14 7600 444 1 67 483 2 05 520 2 34 555 2 62 587 2 90 618 3 10...

Страница 23: ...775 4 20 812 4 42 849 4 64 886 4 86 8400 711 3 93 746 4 11 782 4 32 819 4 54 855 4 76 892 4 98 8600 718 4 06 752 4 24 788 4 44 825 4 66 862 4 88 898 5 10 8800 725 4 19 759 4 37 795 4 57 831 4 78 868...

Страница 24: ...in main loop position B Start Up 1 Initiate first and second cooling demand according to instructions provided with thermostat 2 036 060 Units First stage thermostat demand will energize compressor 1...

Страница 25: ...FLOW CONTROL VALVE ON OFF BYPASS CIRCUIT 10 ton units only one in each unit other components are one in each circuit FIGURE 27 REFRIGERANT ROUTING COOLING OPERATION 20 TON UNITS WATER IN WATER TO REFR...

Страница 26: ...ATER OUT BYPASS CIRCUIT THREE WAY VALVES 10 ton units only one in each unit other components are one in each circuit FIGURE 29 REFRIGERANT ROUTING HEATING OPERATION 20 TON UNITS REFRIGERANT WATER WATE...

Страница 27: ...Refrigerant Charge and Check WARNING Do not exceed nameplate charge under any condition This unit is factory charged and should require no further adjustment If the system requires charge reclaim the...

Страница 28: ...heater which must be on 24 hours before running compressors Energize by setting thermostat so that there is no cooling demand to prevent compressor from cycling and apply power to unit 4 Freezestats...

Страница 29: ...he antifreeze water mixture freezing point Set stage 2 to initiate a minimum of 5 F above the antifreeze water mixture freezing point For example the freezing point of a 10 mixture of ethylene glycol...

Страница 30: ...a Ammonium Hydroxide 0 5 ppm maximum Ammonium chloride Ammonium 0 5 ppm maximum Nitrate Ammonium Sulfate 0 5 ppm maximum Hydrogen Sulfide No level allowable Maintenance Water quality should be checked...

Страница 31: ...r and reinstall 5 Replace removable cap and hose end cap Close the hose end drain valve and manual air vents if opened 6 To place the water system valves in the main loop position follow procedure in...

Страница 32: ...n Ambient Temp ________Return Air Temp ________ Supply Air Temp ________ Compr Amps Compressor Volts Pressures CC Heater Amps L1 L2 L3 L1 L2 L1 L3 L2 L3 Disch Suct L1 1 2 Water To Refrigerant Coil Che...

Отзывы: