Page 31
Operating Signal Pressure Measurement
FIGURE 20
TABLE 20
Unit
Production
Resonance (more air)
Difficulty Igniting (less air)
Orifice Size (Part No)
Orifice Size
Cat No
Orifice Size
Cat No
-060
0.969 (08)
1.000
19X30
0.937
19X37
-080
1.094 (07)
1.125
19X31
0.995
19X36
G- Proper Combustion
Furnace should operate a minimum 15 minutes with cor-
rect manifold pressure and gas flow rate before check
-
ing combustion. Take combustion sample beyond the flue
outlet and compare to TABLE 21.
The maximum carbon
monoxide reading should not exceed 100 ppm.
TABLE 21
Firing Rate
CO
2
% For Natural
CO
2
% For LP
High Fire
6.0 - 7.8
7.5-9.9
Low Fire
H- High Altitude
Units may be installed at altitudes up to 7,500 ft. above
sea level. See TABLE 18 and TABLE 19 for de-rate man
-
ifold values. Units installed at altitude of 4501 - 7,500 feet
require a pressure switch change which can be ordered
separately. TABLE 22 lists pressure switch requirements
at high altitude.
The combustion air pressure switch is factory-set and re-
quires no adjustment.
TABLE 22
Unit
Pressure Switch 4501-7500ft
Natural
LP/Propane
-060
20K91
No Change
-080
No Change
N/A
-100