background image

Page 29

Gas supply piping should not allow more than 0.5”W.C. 

drop in pressure between gas meter and unit. Supply gas 

pipe must not be smaller than unit gas connection.
Compounds used on gas piping threaded joints should be 

resistant to action of liquefied petroleum gases.

C-Testing Gas Piping

 IMPORTANT

I

n  case  emergency  shutdown  is  required,  turn  off 

the  main  shut-off  valve  and  disconnect  the  main 

power  to  unit.  These  controls  should  be  properly 

labeled by the installer.

When pressure testing gas lines, the gas valve must be 

disconnected and isolated. Gas valves can be damaged if 

subjected to more than 0.5 psig (14” W.C.). See FIGURE 

18. If the pressure is greater than 0.5psig (14”W.C.), use 

the manual shut-off valve before pressure testing to iso

-

late furnace from gas supply.

MANUAL MAIN

SHUT-OFF VALVE

WILL NOT HOLD

NORMAL TEST

PRESSURE

CAP

ISOLATE

GAS VALVE

FURNACE

1/8 NPT PLUG

FIGURE 18

 

When checking piping connections for gas leaks, use 

preferred means. Kitchen detergents can cause harmful 

corrosion on various metals used in gas piping. Use of a 

specialty Gas Leak Detector is strongly recommended. It 

is available through Lennox under part number 31B2001. 

See Corp. 8411-L10, for further details.

Do  not  use  matches,  candles,  flame  or  any  other 

source of ignition to check for gas leaks.
D-Testing Gas Supply Pressure

 IMPORTANT

For  safety,  connect  a  shut-off  valve  between  the 

manometer and the gas tap to permit shut off of gas 

pressure to the manometer.

A port on the inlet side of the gas valve provides access 

to the supply pressure tap. See FIGURE 17. Loosen the 

screw and connect a manometer to measure supply pres-

sure.

The minimum supply line pressure is 4.5” - 13.0”w.c. For 

natural and 11.0 - 13.0” wc for LP/Propane. Tighten after 

measurements have been taken.

E- Proper Gas Flow (Approximate)

Furnace should operate at least 5 minutes before check-

ing gas flow. Determine time in seconds for two revolu

-

tions of gas through the meter. (Two revolutions assures 

a more accurate time.) Divide by two and compare to time 

in table 17 below.

NOTE- 

To obtain accurate reading, shut off all other gas 

appliances connected to meter.

TABLE 17 

GAS METER CLOCKING CHART

Unit

Seconds for One Revolution

Natural

LP/Propane

1 cu ft 

Dial

2 cu ft 

Dial

1 cu ft 

Dial

2 cu ft 

Dial

-060

60

120

150

300

-080

45

90

112

224

Natural - 1000btu/cu ft           Propane-2500 btu/cu ft

F-Check Manifold Pressure

 IMPORTANT

For  safety,  connect  a  shut-off  valve  between  the 

manometer and the gas tap to permit shut off of gas 

pressure to the manometer.

Manif

old and Signal Pressure Check

1 - 

 Turn off the electrical power and gas supply to the 

furnace.

2 -   Remove the threaded plug from the outlet side of 

the  gas  valve  and  install  a  field-provided  barbed 

fitting.  Connect  measuring  device  positive  “+”  to 

barbed  fitting  to  measure  manifold  pressure.  See 

FIGURE 17 for manifold location.

3 -   Install hoses and meter as shown in FIGURE 20 for 

signal pressure measurement.

4 - 

 After allowing unit to stabilize for 8 minutes, record 

manifold pressure and compare to value in TABLE 

18  or  TABLE  19.  If  manifold  pressure  is  within 

range, rate check is complete move to step 6. If 

manifold pressure is not within range continue. 

Valve is not adjustable. Do not adjust manifold 

pressure.

5 -   Record signal pressure and compare to value in 

TABLE 18 or TABLE 19. If signal pressure is within 

range continue. If the signal is not within range go 

to “Troubleshooting”.

6 - 

 Shut  off  unit  and  remove  manometer  and  signal 

meter after accurate readings has been obtained.

7 - 

 Restart unit and check for gas leaks. Seal any leaks 

found.

If the unit has difficulty igniting or ignites with loud 

resonance the air orifice must be checked and re

-

placed if necessary.

Содержание SL280DF060NV36B

Страница 1: ...es of 60 000 to 80 000 Btuh and cooling applications up to 5 tons Refer to Engineering Handbook for proper sizing SL280DFNV model units are equipped with a communi cating enabled SureLight two stage v...

Страница 2: ...otection 15 15 Shipping Data lbs 1 package 123 145 NOTE Filters and provisions for mounting are not furnished and must be field provided 1 Annual Fuel Utilization Efficiency based on DOE test procedur...

Страница 3: ...minimum 380 cfm Lennox Smart Zoning System Applications Minimum blower speed is 380 cfm SL280DF060NV36B BLOWER MOTOR WATTS COOLING 1 Cooling Speed DIP Switch Settings Motor Watts Various External Stat...

Страница 4: ...1380 1575 1575 1800 2000 2270 Factory Default 990 1110 1250 1440 1400 1600 1820 2050 890 995 1135 1300 1270 1435 1635 1855 1 Cooling and heating speeds are based on a combination of DIP switch settin...

Страница 5: ...Control box Flue chase Internal flue pipe assembly Blower assembly Blower assembly Heat exchanger assembly Air fuel intake assembly Gas valve Combustion air inducer Access panel Parts Arrangement FIG...

Страница 6: ...noperable simply replace entire control Can cause injury or death Unsafe operation will result if repair is attempted 4 Integrated Control A92 Units are equipped with the communicating enabled Sure Li...

Страница 7: ...ners will always fire on first stage heat The combustion air in ducer will operate on low speed and indoor blower will operate on low heat speed The unit will switch to second stage heat after a recog...

Страница 8: ...ST STAGE T STAT R CLASS 2 VOLTAGE TO THERMOSTAT G MANUAL FAN FROM T STAT C THERMOSTAT SIGNAL GROUND CONNECTED TO TRANSFORMER GRD TR CHASIS GROUND GRD Y1 THERMOSTAT 1ST STAGE COOL SIGNAL Y2 THERMOSTAT...

Страница 9: ...OFF OPTION B OFF 82 100 OFF OPTION C OFF 100 100 OFF OPTION D OFF 100 OFF DEFAULT 10 10 HIGH SPEED MEDIUM HIGH SPEED MEDIUM LOW SPEED LOW SPEED 7 PROTECTIVE PLASTIC FILM ON DIP SWITCHES MAY BE REMOVED...

Страница 10: ...the flame signal mode The integrated control will display the flame current on 7 segment LED in in micro amps uA Flame signal mode is exited after any of the follow ing Power is reset Pressing and hol...

Страница 11: ...ect Alarm clears 5 seconds after fault recovered E111 Low line voltage Reverse line power voltage wiring System resumes normal operation 5 seconds after fault recovered E112 Ground not detected System...

Страница 12: ...ture will be set as installed and that could be seen in About screen In normal operation after control recognizes sensors alarm will be sent if valid temperature reading is lost To get rid of setting...

Страница 13: ...tion and restriction Resumes normal operation after fault is cleared E227 Low pressure switch open during trial for ignition or run mode Check pressure inches w c of low pressure switch closing on hea...

Страница 14: ...hour soft lockout Clears when calibration has finished successfully E290 Ignitor circuit fault Failed ignitor or triggering cir cuitry Measure resistance of hot surface ignitor Replace if open or not...

Страница 15: ...tween R O on integrated control with non communicating outdoor unit Dual fuel module required for heat pump application Configuration link R to O needs to be restored Replace link or hard wire Applica...

Страница 16: ...tory set in the OFF position which provides a 7 minute delay before second stage heat is initiated If the switch is toggled to the ON position it will provide a 12 minute delay before second stage hea...

Страница 17: ...nutes mo tor runs at 100 until demand is satisfied Once demand is met motor ramps down to stop OFF OFF 82 CFM 100 CFM COMPRESSOR DEMAND 7 1 2 MIN Ramping Option C Motor runs at 100 until demand is sat...

Страница 18: ...integrated control W915 must be cut if two stage cooling will be used If the Y1 to Y2 link is not cut the outdoor unit will operate in second stage cooling only TABLE 12 OPERATING SEQUENCE SL280DFV N...

Страница 19: ...allowing the room space to maintain a cooler room thermostat setpoint ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING BASIC MODE only active on a Y1 thermostat demand Normal Operation 1 On O...

Страница 20: ...sor which monitors varying conditions inside the motor such as motor workload BLOWER MOTOR COMPONENTS STATOR WINDINGS BEARING ROTOR FIGURE 7 The controller uses sensing devices to sense what posi tion...

Страница 21: ...ximately 5 minutes to discharge when the dis connect is opened For this reason it is necessary to wait at least 5 minutes after turning off power to the unit before attempting to service motor Power C...

Страница 22: ...Line Voltage Connector J49 4 Pin Control Connector J48 5 Pin J49 4 Pin FIGURE 8 BLOWER B3 HARNESS CONNECTORS MOTOR with INTEGRATED CONTROLLER SHAFT P49 4 Pin P48 5 Pin P48 5 Pin P49 4 Pin J48 Connecto...

Страница 23: ...Measure the resistance between each of the three motor leads 3 pin plug and the unpainted part of the end shield If the winding resistance to ground is 100k ohms re place the motor and control module...

Страница 24: ...et and outlet pressure taps are located on the valve A regulator adjustment screw is located on the valve 4 Thermal Switch The auto reset switch is located on the front of the in take air elbow The sw...

Страница 25: ...e 25 HEATING COMPONENTS Air Gas Plenum Burner Gasket Orifice Housing Gas Valve Air Orifice Sensor Ignitor Gas Orifice Thermal Switch location Intake Air Screen Intake Air Elbow Coupling O Ring FIGURE...

Страница 26: ...then then there is a problem with the wiring between the jack plug and control If the reading is not correct the issue is the ignitor Meter set to ohms Test 3 Insert meter probes into the terminals 1...

Страница 27: ...f the combustion air inducer is not operating or if the flue becomes obstructed On heat demand first or second stage the switch senses that the combustion air inducer is operating It closes a circuit...

Страница 28: ...gas line Turning Off Gas To Unit 1 Set thermostat to lowest setting 2 Turn off all electrical power to unit if service is to be performed 3 Remove access panel 4 Move switch on valve to OFF Do not fo...

Страница 29: ...r measurements have been taken E Proper Gas Flow Approximate Furnace should operate at least 5 minutes before check ing gas flow Determine time in seconds for two revolu tions of gas through the meter...

Страница 30: ...ws corresponding steps with the steps below 1 Turn off the electrical power and gas supply to the furnace 2 Remove the air hose fitting from the brass fitting on the air inlet screen 3 Use a 5 16 nut...

Страница 31: ...compare to TABLE 21 The maximum carbon monoxide reading should not exceed 100 ppm TABLE 21 Firing Rate CO2 For Natural CO2 For LP High Fire 6 0 7 8 7 5 9 9 Low Fire H High Altitude Units may be instal...

Страница 32: ...signal Pressure Signal pressure within range Replace gas valve Check the following 1 Vent air intake pipe restriction 2 Plugged air inlet screen 3 Signal hoses to gas valve for kinks loose fit or plug...

Страница 33: ...TEMPERATURE RISE Supply Duct Temperature Return Duct Temperature _ Temperature Rise FIGURE 22 C External Static Pressure 1 Tap locations shown in FIGURE 23 2 Punch a 1 4 diameter hole in supply and re...

Страница 34: ...ir inducer and clean if necessary 8 Evaluate the heat exchanger integrity by inspecting the heat exchanger per the AHRI heat exchanger inspection procedure This procedure can be viewed at www ahrinet...

Страница 35: ...ally inspect inside the burner for any blockage caused by foreign matter Remove any blockage FIGURE 25 shows burner detail Replace gasket between burner plate and air fuel plenum then re install burne...

Страница 36: ...age 36 Flue chase Internal flue pipe assembly Gas valve Combustion air inducer Heat Exchanger and Burner Air Fuel Plenum Burner Re install screws per the numbered sequence shown Gasket Gasket FIGURE 2...

Страница 37: ...ontacts The control also checks for S102 high heat and S128 low heat prove switch normally open contacts Once self check is complete and all safety switches are operational heat call can continue NOTE...

Страница 38: ...is satisfied the gas valve is de energized and the field selected indoor blower off delay begins The combustion air inducer begins a 5 second post purge period 9 When the combustion air post purge pe...

Страница 39: ...STAGE OPERATION Communicating Integrated Control Communicating Thermostat Outdoor Unit nace air handler control and four wires between the outdoor unit and the furnace air handler control When a ther...

Страница 40: ...W Gh Gs Cf HVAC EQUIP DEHUMIDIFIER CONTROL HVAC EQUIPMENT DH 24V IN JUMPER COMMUNICATING ENABLED FURNACE COMMUNICATING ENABLED FURNACE ICOMMUNICATING THERMOSTAT CONVENTIONAL NON COMMUNICATING SYSTEM C...

Страница 41: ...NOX COMMUNICATING THERMOSTAT OR DAMPER CONTROL MODULE CONVENTIONAL TERMINALS FLOAT SWITCH LENNOX COMMUNICATING INDOOR UNIT CONVENTIONAL OUTDOOR UNIT 1 OR 2 STAGE LENNOX COMMUNICATING FURNACE EL296V SL...

Страница 42: ...NOT CUT ANY ON BOARD LINKS S1 T STAT FURNACE TERM STRIP OUTDOOR UNIT 1 Heat 2 Cool NOTE Use DIP switch 2 to set second stage heat ON delay OFF 7 minutes ON 12 minutes ON CUT ON BOARD LINK W915 2 STAG...

Страница 43: ...TAGE COMPR S1 T STAT FURNACE TERM STRIP OUTDOOR UNIT 2 Heat 2 Cool with t stat with humidity control OFF CUT ON BOARD LINK W915 2 STAGE COMPR CUT ON BOARD LINK W914 DEHUM OR HARMONY S1 T STAT FURNACE...

Страница 44: ...ARD LINK W951 HEAT PUMP T STAT FURNACE TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 T T outdoor sensor Dual Fuel Two Stage Heat Pump ComfortSense thermostat w bilities Capable of 2 stage gas heat cont...

Страница 45: ...LINK W914 DEHUM OR HARMONY T STAT FURNACE TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 T T outdoor sensor Dual Fuel Two Stage Heat Pump ComfortSense thermostat w bilities Capable of 2 stage gas heat m...

Страница 46: ...for 10 second period During that period press and hold push button for 5 seconds Integrated control will store code in memory and will automatically exit Program Unit Capacity Size Mode and reset If s...

Страница 47: ...S H S I OFF NO INDUCER OFF AFTER POST PURGE HARD LOCKOUT ERROR CODE FLASHES YES YES YES 1 2 1 LOW PRESSURE SWITCH OPENS 1 2 HARD LOCKOUT REQUIRES THERMOSTAT RESET OR CYCLING OF POWER TO RESET THE LOCK...

Страница 48: ...FOR 1ST REQUEST FOR 2ND STAGE HEAT YES CALL FOR HEAT SATISFIED INDUCER SWITCHED TO HIGH SPEED SINGLE STAGE THERMOSTAT 2 STAGE THERMOSTAT NO INDUCER SWITCHED TO LOW SPEED 5 MINUTE DELAY ERROR CODE FLA...

Страница 49: ...AGE CALL FOR HEAT SATISFIED NO YES DE ENERGIZE 2ND STAGE GAS VALVE INDUCER SPEED SWITCHED TO LOW SPEED 1 2 3 1ST STAGE HEAT 1ST STAGE CALL FOR HEAT SATISFIED NO YES GAS VALVE DE ENERGIZED INDUCER OFF...

Страница 50: ...PROFILES THE SPECIFIC PROFILE IS SELECTED USING THE 1 1 2 2 1 1 1 2 2 DE ENERGIZE 1ST STAGE COOLING CONTACTOR COMPRESSOR FAN 2ND STAGE COOLING REQUEST STILL ACTIVE COOLING REQUEST STILL ACTIVE CALL F...

Страница 51: ...FOR HEAT RECEIVED REQUEST FOR COOLING RECEIVED GO TO CALL FOR 1ST STAGE HEAT YES GO TO CALL FOR COOLING 1 1 1 4 YES NO CALL FOR FAN INDOOR BLOWER ON CONTINUOUS FAN SPEED MAINTAIN INDOOR BLOWER AT CON...

Отзывы: