REFRIGERANT PIPING – Removing Existing Indoor Metering Device 

SENSING

LINE

TEFLON

®

 RING

FIXED ORIFICE

BRASS NUT

LIQUID LINE ASSEMBLY

(INCLUDES STRAINER)

LIQUID LINE ORIFICE HOUSING

DISTRIBUTOR TUBES

DISTRIBUTOR

ASSEMBLY

REMOVE AND DISCARD

WHITE TEFLON

®

 SEAL

(IF PRESENT)

 A -

On fully cased coils, remove the coil access and plumbing panels.

 B -

sembly.

 C -

Using two wrenches, disconnect liquid line from liquid line 

ing. T

cess.

 D -

Remove and discard fixed orifice, valve stem assembly (if present)

and Teflon

®

 washer as illustrated above.

 E -

Use a field-provided fitting to temporarily reconnect the liquid line to the

indoor unit's liquid line orifice housing.

TYPICAL EXISTING FIXED ORIFICE

REMOVAL PROCEDURE 

(UNCASED COIL SHOWN)

TYPICAL EXISTING EXPANSION VALVE REMOVAL

PROCEDURE (UNCASED COIL SHOWN)

TWO-PIECE PATCH PLATE

(UNCASED COIL ONLY)

VAPOR

LINE

DISTRIBUTOR

ASSEMBLY

DISTRIBUTOR

TUBES

LIQUID

LINE

MALE EQUALIZER

LINE FITTING

EQUALIZER

LINE

CHECK

EXPANSION

VALVE

TEFLON®

RING

STUB END

TEFLON

®

RING

SENSING BULB

LIQUID LINE

ORIFICE

HOUSING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

 A -

On fully cased coils, remove the coil access and plumbing panels.

 B -

Remove any shipping clamps from the liquid line and distributor

assembly.

 C -

Disconnect the  equalizer  line  from  the  check  expansion  valve

equalizer line fitting on the vapor line.

 D -

Remove the vapor line sensing bulb.

 E -

Disconnect the liquid line from the check expansion valve at the

liquid line assembly.

 F -

Disconnect the check expansion valve from the liquid line orifice

housing. Take care not to twist or damage distributor tubes during

this process.

 G -

Remove and discard check expansion valve and the two Teflon

®

rings.

 H -

Use a field-provided fitting to temporarily reconnect the liquid line to

the indoor unit's liquid line orifice housing.

LOW

HIGH

EXISTING

INDOOR

UNIT

GAUGE

MANIFOLD

CYLINDER CONTAINING

CLEAN HCFC-22 TO BE

USED FOR FLUSHING

(Positioned to deliver liquid

refrigerant)

LIQUID LINE SERVICE

VALVE

INLET

DISCHARGE

TANK

RETURN

CLOSED

OPENED

RECOVERY

CYLINDER

RECOVERY MACHINE

NEW

OUTDOOR

UNIT

VAPOR LINE

SERVICE VALVE

VAPO
R

LIQUID

1

 A -

HCFC-22 cylinder with clean refrigerant (positioned to deliver liquid

refrigerant) to the vapor service valve.

 B -

HCFC-22 gauge set (low side) to the liquid line valve.

 C -

HCFC-22 gauge set center port to inlet on the recovery machine with an

empty recovery tank connected to the gauge set.

 D -

Connect recovery tank to recovery machine per machine instructions.

CONNECT GAUGES AND EQUIPMENT FOR

FLUSHING PROCEDURE

A

B

C

D

B

OR

FLUSHING LINE SET

 A -

Set the recovery machine for liquid recovery and start the recovery

machine.  Open  the  gauge  set  valves  to  allow  the  recovery

machine to pull a vacuum on the existing system line set and indoor

unit coil.

 B -

Position  the  cylinder  of  clean  HCFC-22  for  delivery  of  liquid

refrigerant and open its valve to allow liquid refrigerant to flow into

the system through the vapor line valve. Allow the refrigerant to

pass from the cylinder and through the line set and the indoor unit

coil before it enters the recovery machine.

 C -

After all of the liquid refrigerant has been recovered, switch the

recovery machine to vapor recovery so that all of the HCFC-22

vapor is recovered. Allow the recovery machine to pull the system

down to 0.

 D -

Close the valve on the inverted HCFC-22 drum and the gauge set

valves.  Pump  the  remaining  refrigerant  out  of  the  recovery

machine and turn the machine off.

The line set and indoor unit coil must be flushed with at least the same

amount of clean refrigerant that previously charged the system. Check

the charge in the flushing cylinder before proceeding.

1A

2

3

1B

FIGURE 2 

Содержание SL25XPV Series

Страница 1: ...OL PANEL ACCESS LOCATION 6 152 36 914 12 305 30 762 24 610 LINE SET CONNECTIONS ACCESS PANEL REAR VIEW OF UNIT 48 1219 MINIMUM CLEARANCE BETWEEN TWO UNITS CLEARANCE ON ALL SIDES INCHES MILLIMETERS MIN...

Страница 2: ...E FOR EXTRA STABILITY Deck Top Mounting Elevated Slab Mounting using Feet Extenders Stabilizing Unit on Uneven Surfaces WOOD OR PLASTIC SLAB NO PLASTIC ANCHOR HOLE DRILL 1 8 INSTALL UNIT LEVEL OR IF O...

Страница 3: ...5XPV 024 47 00 35 50 39 40 35 00 15 97 SL25XPV 036 47 00 35 50 39 40 35 00 15 97 SL25XPV 048 47 00 35 50 39 40 35 00 15 97 SL25XPV 060 47 00 35 50 39 40 35 00 15 97 4 5 8 117 BASE WITH ELONGATED LEGS...

Страница 4: ...ly charged with mineral oil or if it is being matched with a coil which was manufactured before January of 1999 the coil and line set must be flushed prior to installation Take care to empty all exist...

Страница 5: ...gths may be more or less depending on remaining system design factors Maximum linear actual length 150 feet Maximum linear liquid lift 60 feet NOTE Maximum lifts are dependent on total length number o...

Страница 6: ...50 41 31 22 1 2 25 50 60 60 60 60 3 8 25 50 36 22 8 NR 1 2 25 50 60 60 60 59 Shaded rows indicate rated liquid line size A Find your unit on the left side of the table B Start with the rated liquid li...

Страница 7: ...t the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid r...

Страница 8: ...t nitrogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refrigerant li...

Страница 9: ...S POINT FLAME AWAY FROM SERVICE VALVE LIQUID LINE WATER SATURATED CLOTHS WATER SATURATED CLOTHS 6A 6B SUCTION VAPOR SERVICE PORT MUST BE OPEN AND MOVED TO ALLOW EXIT POINT FOR NITROGEN FLOW IMPORTANT...

Страница 10: ...l Shown Sensing bulb insulation is required if mountedexternal to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR AS...

Страница 11: ...psig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify th...

Страница 12: ...nifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned to deliver liquid...

Страница 13: ...ct Specifications bulletin EHB and unit rating plate WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit insta...

Страница 14: ...AT WIRING CONNECTION PUSH BUTTON 7 SEGMENT DISPLAY PUMP DOWN WHEN UNIT IS IN PUMP DOWN MODE Pd WILL BE DISPLAYED ON 7 SEGMENT TO ACTIVATE PUMP DOWN MODE THE CONTROL MUST BE IN THE IDLE STATE AND THE P...

Страница 15: ...Page 15 FIGURE 10 Typical Field Wiring...

Страница 16: ...BE SHOWN GOING TO PROPER LOCATION IN CONTROL BOX 8 TERMINAL LOCATION CHANGES FROM MFR TO MFR PLEASE NOTE TERMINAL NO 9 FILL ALL UNUSED HOLES WITH SCREWS 10 BUNDLE EXCESS WIRE BLUE LIQUID SENSOR FAN M...

Страница 17: ...d also include an additional wire that should be connected on each end to the C terminal as shown in the figure below Any excess high voltage field wiring should be trimmed and secured away from any l...

Страница 18: ...art Hub C i i R HD Display Subbase or Mag Mount COMMBUS A B ACC1 ACC2 SL25XPV Outdoor Unit SL25XPV RAST 6 Pin Connectors OATS Optional DATS Optional B A O Y1 FIGURE 12 SL25XPV with iComfort S30 Commun...

Страница 19: ...ch system defrost cycle The heat pump control monitors ambient temperature outdoor coil temperature and total run time to determine when a defrost cycle is required The coil temperature sensor is desi...

Страница 20: ...2 3 4 5 6 7 8 9 10 1112 1 6 TURN Reinstall Stem Cap Stem cap protects the valve stem from damage and serves as the primary seal Replace the stem cap and tighten as follows With torque wrench finger t...

Страница 21: ...structions month ly The indoor coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air Have your dealer show you the loca tion of the drain l...

Страница 22: ...Replace as necessary 7 Check outdoor fan motor for worn bearings bushings Replace as necessary 8 Inspect and clean outdoor coils if necessary and note any damage to coils or signs of leakage Indoor U...

Страница 23: ...y Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach tem...

Отзывы: