background image

Page 20

BALL (SHOWN

CLOSED)

SERVICE PORT

CORE

TO 

OPEN,

 ROTATE STEM

COUNTERCLOCKWISE 90°.

TO 

CLOSE, 

ROTATE STEM

CLOCKWISE 90°.

SERVICE PORT

SERVICE PORT

CAP

STEM CAP

VALVE

STEM

1 - Remove stem cap with an appropriately sized wrench.
2 - Use an appropriately sized wrench to open. To open valve, rotate

stem counterclockwise 90°. To close, rotate stem clockwise 90°.

OPERATING BALL-TYPE SERVICE VALVE

FIGURE 13 

(VALVE STEM SHOWN CLOSED)

INSERT HEX WRENCH HERE

SERVICE PORT CORE

SERVICE PORT CAP

ANGLE-TYPE SERVICE VALVE

(FRONT-SEATED CLOSED)

STEM CAP

(VALVE STEM SHOWN OPEN)

INSERT HEX WRENCH HERE

ANGLE-TYPE SERVICE VALVE

(BACK-SEATED OPENED)

1 - Remove stem cap with an appropriately sized wrench.
2 - Use a service wrench with a hex-head extension (3/16" for liquid

line valve sizes and 5/16" for vapor line valve sizes) to back the

stem out counterclockwise as far as it will go.

When service valve is 

CLOSED

, the service port is

open to the line set and indoor unit.

When service valve is 

OPEN

, the service port is

open to line set, indoor and outdoor unit.

NOTE -

 A label with specific torque requirements may be affixed to

the stem cap. If the label is present, use the specified torque.

OPERATING ANGLE-TYPE SERVICE VALVE

FIGURE 14 

1

2

3

4

5

6

7

8

9

10

11 12

1/12 TURN

A service port cap protects the service port core from contamination

and serves as the primary leak seal.

1 - Remove service port cap with an appropriately sized wrench.
2 - Connect gauge set to service port.

3 - When testing is completed, replace service port cap and tighten

as follows:

With torque wrench, finger tighten and torque

cap per table 2.
Without torque wrench, finger tighten and 

use an appropriately sized wrench to turn 

an additional 1/6 turn clockwise.

1

2

3

4

5

6

7

8

9

10

11 12

1/6 TURN

Reinstall Stem Cap

Stem cap protects the valve stem from damage and serves as the

primary seal. Replace the stem cap and tighten as follows:

With torque wrench, finger tighten and

then torque cap per table 2.
Without torque wrench, fi

en and use an appropriately sized

wrench to turn an additional 1/12

turn clockwise.

ACCESS SERVICE PORT

FIGURE 15 

Charging 

The SL25XPV unit is factory-charged with enough HFC-

410A refrigerant to accommodate a 15-foot length of re-

frigerant piping. For refrigerant piping greater than 15 

feet, calculate the additional charge using the table below. 

Then add the additional refrigerant charge to the system.

Charge should be checked and adjusted using the ta-

bles provided on the charging procedure sticker on 

the unit access panel

. Detailed information is given in 

the SL25XPV Installation and Service Procedures manu-

al, which is available on LennoxPros.com. 

 IMPORTANT

System charging should be performed with the unit 

operating at the maximum cooling capacity (100% 

capacity). The unit can be operated at maximum 

capacity by entering the test mode at the S30 

thermostat or using the Lennox Dealer Setup App. 

The S30 Test Mode can be selected by going to 

Menu> Advanced Settings> View Dealer Control 

Center> Test and then select Cooling - Maximum 

Rate Test. Seven-segment display on outdoor 

control will show outdoor unit running capacity. 

Refrigerant Charge per Line Set Length

LIQUID LINE DIA. OUNCES PER 5 FEET (G PER 1.5 M) ADJUST 

FROM 15 FEET (4.6 M) LINE SET*

3/8" (9.5 MM)

3 OUNCES PER 5' (85 G PER 1.5 M)

*If line length is greater than 15 ft. (4.6 m), add this amount. If line 

length is less than 15 ft. (4.6 m), subtract this amount. 
NOTE – Insulate liquid line when it is routed through areas where 

the surrounding ambient temperature could become higher than the 

temperature of the liquid line or when pressure drop is equal to or 

greater than 20 psig. 

Содержание SL25XPV Series

Страница 1: ...OL PANEL ACCESS LOCATION 6 152 36 914 12 305 30 762 24 610 LINE SET CONNECTIONS ACCESS PANEL REAR VIEW OF UNIT 48 1219 MINIMUM CLEARANCE BETWEEN TWO UNITS CLEARANCE ON ALL SIDES INCHES MILLIMETERS MIN...

Страница 2: ...E FOR EXTRA STABILITY Deck Top Mounting Elevated Slab Mounting using Feet Extenders Stabilizing Unit on Uneven Surfaces WOOD OR PLASTIC SLAB NO PLASTIC ANCHOR HOLE DRILL 1 8 INSTALL UNIT LEVEL OR IF O...

Страница 3: ...5XPV 024 47 00 35 50 39 40 35 00 15 97 SL25XPV 036 47 00 35 50 39 40 35 00 15 97 SL25XPV 048 47 00 35 50 39 40 35 00 15 97 SL25XPV 060 47 00 35 50 39 40 35 00 15 97 4 5 8 117 BASE WITH ELONGATED LEGS...

Страница 4: ...ly charged with mineral oil or if it is being matched with a coil which was manufactured before January of 1999 the coil and line set must be flushed prior to installation Take care to empty all exist...

Страница 5: ...gths may be more or less depending on remaining system design factors Maximum linear actual length 150 feet Maximum linear liquid lift 60 feet NOTE Maximum lifts are dependent on total length number o...

Страница 6: ...50 41 31 22 1 2 25 50 60 60 60 60 3 8 25 50 36 22 8 NR 1 2 25 50 60 60 60 59 Shaded rows indicate rated liquid line size A Find your unit on the left side of the table B Start with the rated liquid li...

Страница 7: ...t the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid r...

Страница 8: ...t nitrogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refrigerant li...

Страница 9: ...S POINT FLAME AWAY FROM SERVICE VALVE LIQUID LINE WATER SATURATED CLOTHS WATER SATURATED CLOTHS 6A 6B SUCTION VAPOR SERVICE PORT MUST BE OPEN AND MOVED TO ALLOW EXIT POINT FOR NITROGEN FLOW IMPORTANT...

Страница 10: ...l Shown Sensing bulb insulation is required if mountedexternal to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR AS...

Страница 11: ...psig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify th...

Страница 12: ...nifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned to deliver liquid...

Страница 13: ...ct Specifications bulletin EHB and unit rating plate WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit insta...

Страница 14: ...AT WIRING CONNECTION PUSH BUTTON 7 SEGMENT DISPLAY PUMP DOWN WHEN UNIT IS IN PUMP DOWN MODE Pd WILL BE DISPLAYED ON 7 SEGMENT TO ACTIVATE PUMP DOWN MODE THE CONTROL MUST BE IN THE IDLE STATE AND THE P...

Страница 15: ...Page 15 FIGURE 10 Typical Field Wiring...

Страница 16: ...BE SHOWN GOING TO PROPER LOCATION IN CONTROL BOX 8 TERMINAL LOCATION CHANGES FROM MFR TO MFR PLEASE NOTE TERMINAL NO 9 FILL ALL UNUSED HOLES WITH SCREWS 10 BUNDLE EXCESS WIRE BLUE LIQUID SENSOR FAN M...

Страница 17: ...d also include an additional wire that should be connected on each end to the C terminal as shown in the figure below Any excess high voltage field wiring should be trimmed and secured away from any l...

Страница 18: ...art Hub C i i R HD Display Subbase or Mag Mount COMMBUS A B ACC1 ACC2 SL25XPV Outdoor Unit SL25XPV RAST 6 Pin Connectors OATS Optional DATS Optional B A O Y1 FIGURE 12 SL25XPV with iComfort S30 Commun...

Страница 19: ...ch system defrost cycle The heat pump control monitors ambient temperature outdoor coil temperature and total run time to determine when a defrost cycle is required The coil temperature sensor is desi...

Страница 20: ...2 3 4 5 6 7 8 9 10 1112 1 6 TURN Reinstall Stem Cap Stem cap protects the valve stem from damage and serves as the primary seal Replace the stem cap and tighten as follows With torque wrench finger t...

Страница 21: ...structions month ly The indoor coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air Have your dealer show you the loca tion of the drain l...

Страница 22: ...Replace as necessary 7 Check outdoor fan motor for worn bearings bushings Replace as necessary 8 Inspect and clean outdoor coils if necessary and note any damage to coils or signs of leakage Indoor U...

Страница 23: ...y Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach tem...

Отзывы: