PCUS Thermostat - User Manual - 0821EN
10
Example: Time band 3
To activate the operation of the time bands, press and hold the ventilation button until the clock icon with the
number of the currently active time band appears in the lower part of the display.
The photo below illustrates the operation with time band 1
active.
To disable the operation of the time bands and return to normal operation, press the ventilation button until the
clock icon disappears.
2.13 USER PARAMETERS
Press at length the M and + key until the first parameter 0.0 is displayed and then with the M key pressed again
you pass to the next parameter, if you press it at length you pass to the next menu.
You can modify the parameters with the + and - keys and then press M to confirm the values.
The user parameters table is shown below.
Meaning
U0.0 Temperature set point (°C)
min 15
max 35
U0.1 Temperature differential (°C)
min 0
max 5
U0.2 Antifreeze set point (°C)
min -10
max 5
U0.3 Antifreeze differential (°C)
min 0
max 10
U0.4 Set Point Defrost (°C)
min -10
max 5
U0.5 Defrost differential (°C)
min 1
max 10
U0.5 Analog regulation band for heating and cooling (°C)
min 0
max 10
U0.7 Delay on fans (s)
min 0
max 180
U0.8 Shut-off delay (s)
min 0
max 180
U0.9 Defrost type
0 - 7
nobody
1 - speed
variation
2 - recirculation
U1.0 CO2 sensor range (ppm)
min 0
max 2000
U1.1 RH sensor range (%)
min 20
max 90
U1.2 VOC sensor range
min 0
max 50
U1.3 PM2.5 sensor range
min 0
max 900
U1.4 CO2 Adjustment band
400
U1.5 RH Adjustment band
min 1
max 10
U1.6 VOC Adjustment band
min 10
max 10
U1.7 PM2.5 Adjustment band
min 200 max 200
U1.8 FAN adjustment band in AUTO mode (V)
min 1 max 10
Example: Time band 4