Page 20

Troubleshooting:   Burner fails to start

Source

Correction

Causes

Procedure

Primary Control

Place trouble light between
the black and white leads.
No light indicates that no
power is going to the
control.

Primary or auxiliary control
switch is open

Check adjustment. Set the maximum setting.

Jumper terminals; if burner starts, switch is faulty,
replace control.

Open circuit between
disconnect switch and limit
control

Trace wiring and repair or replace it.

Low line voltage or power
failure

Call the power company.

Place trouble light between
the orange and white leads.
No light indicates faulty
control.

Defective internal control
circuit

Replace the control.

Burner

Place the trouble light
between the black and
white leads to the burner
motor. No light indicates
that no power is getting to
the motor.

Blown fuse

Replace the fuse.

Place trouble light between
the black and white leads to
the blower motor. Light
indicates power to the
motor and burner fault.

Binding burner blower
wheel

Turn off power and rotate the blower wheel by hand.
If seized, free the wheel or replace the fuel pump.

Sized fuel pump

Defective burner motor

Replace the motor.

 

Troubleshooting:   Burner starts, but no flame is established

Source

Procedure

Causes

Correction

Oil Supply

Check tank gauge or use dip stick.

No oil in tank

Fill tank.

Coat dip stick with litmus paste and
insert into bottom of tank.

Water in oil tank

If water depth exceeds 1 inch, pump
or drain water.

Listen for pump whine.

Tank shut−off valve closed

Open valve.

Oil Filters & Oil
Line

Listen for pump whine.

Oil line filter is plugged

Kinks or restriction in oil line

Plugged fuel pump strainer

Replace filter cartridges.

Repair or replace oil line.

Clean strainer or replace pump.

Open bleed valve or gauge port.
Start the burner. No oil or milky oil
indicates loss or prime.

Air leak in oil supply line

Locate and correct leak.

Tighten all connections.

Oil Pump

Install pressure gauge on pump and
read pressure. Should not be less
than 140 psi.

Pump is partially or completely
frozen. No pressure and the motor
locks out on overload.

Replace pump.

Coupling disengaged or broken − no
pressure

Re−engage or replace coupling.

Fuel pressure too low

Adjust to 100 psi.

Nozzle

Disconnect ignition leads. Observe
the oil spray (gun assembly must be
removed from unit). Inspect the
nozzle for plugged orifice or carbon
build−up around orifice.

Nozzle orifice plugged

Nozzle strainer plugged

Poor or off center spray

Replace nozzle with the same size,
spray angle, and spray type.

table continued on next page

Downloaded from 

ManualsNet.com

 search engine

Содержание O23V Series

Страница 1: ...sedes 10 2005 Table of Contents General 1 Shipping Packing List 1 O23V Unit Dimensions 2 O23V Unit Parts Arrangement 3 O23V Oil Burner Parts Arrangement 3 Requirements 4 Locate Level the Unit 4 Unit A...

Страница 2: ...OW TOP VIEW RETURN AIR SIDE VIEW E RETURN AIR FRONT VIEW Figure 1 O23V Unit Dimensions Inches mm O23V Model A B C D E Q2 3 70 90 Q3 4 105 120 19 1 2 495 30 5 8 778 18 457 19 5 8 498 16 406 Q5 140 154...

Страница 3: ...0 8 Figure 3 AIR TUBE SCREWS ELECTRONIC IGNITION TRANSFORMER FLANGE GASKET RETAIN ING CLIP IGNITOR PRIMARY CONTROL REAR ACCESS DOOR GASKET MAIN HOUSING ASSY AIR ADJUST DIAL 4X4 BOX BLOWER WHEEL INLET...

Страница 4: ...i mum free area one half square inch per 1 000 Btu per hour input This combustion air should be brought into the area containing the furnace below the level of the furnace burner Table 2 O23V Installa...

Страница 5: ...rner assembly from the vestibule By loosen ing the nuts and by turning the whole burner assembly counterclockwise figure 4 the entire burner assembly will come out of the furnace There is adequate wir...

Страница 6: ...n outside or through any unconditioned space 6 Chimney should extend 3 feet 0 9 m above highest point where the vent passes through the roof and 2 feet 0 6 m higher than any portion of a building with...

Страница 7: ...OR DEATH A living space which provides insufficient combustion air to the furnace can result in headaches nausea dizziness or asphyxiation CAUTION Insufficient combustion air to the furnace can cause...

Страница 8: ...space shall be provided with two perma nent openings One opening shall be within 12 305 mm of the top of the enclosure and one within 12 305 mm of the bottom These openings must communicate directly o...

Страница 9: ...from Common Venting System In the event that an existing furnace is removed from a venting system commonly run with separate appliances the venting system is likely to be too large to properly vent t...

Страница 10: ...of the cabinet See unit dimensions on page 2 Using it as the center point cut a 6 inch 152 mm round hole in the cabinet s side Install the barometric draft control within 18 inches of the furnace flue...

Страница 11: ...bing or steel pipe for oil supply pipe Install oil supply pipe under floor or near walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings...

Страница 12: ...de the building between the tank shut off valve and the burn er Locate filter close to burner for easy maintenance Table 5 lists the filters for the O23V furnace Table 5 Installation Clearances inches...

Страница 13: ...ted The Test jumper is used to operate the motor in the test mode See figure 17 Factory settings for the blower speed jumpers are given in the wiring diagram in figure 18 Figure 17 shows the blower co...

Страница 14: ...age cooling closes the R to Y1 circuit on the A54 blower control board The blower motor runs at 57 CFM for the first 7 1 2 minutes of the 1st stage cooling demand After 7 1 2 minutes the blower motor...

Страница 15: ...output to an electronic air cleaner The EAC terminal is energized when there is a call for heat cool or continuous blower See figure 18 Table 6 Blower Performance 0 through 0 80 in w g 0 through 200 P...

Страница 16: ...Page 16 Figure 18 O23V Wiring Diagram P535277W Downloaded from ManualsNet com search engine...

Страница 17: ...s above the range shown in the table check for high static pres sure Table 7 O23V Unit Nozzle Size Spray Angle Pattern Pump PSIG Input Rating BTU Hr Output Rating BTU Hr Head Temp Rise F 70 50GPH 80 A...

Страница 18: ...ive Cleaning the Heat Exchanger 1 Remove the vent pipe from the furnace 2 Remove the locking screws and the caps from the clean out tubes Remove flue access elbow 3 Using a long spiral wire brush swee...

Страница 19: ...rt Source Procedure Causes Correction Thermostat Check thermostat settings Thermostat in OFF or COOL Switch to HEAT Thermostat is set too low Turn thermostat to higher temperature Safety Overloads Che...

Страница 20: ...flame is established Source Procedure Causes Correction Oil Supply Check tank gauge or use dip stick No oil in tank Fill tank Coat dip stick with litmus paste and insert into bottom of tank Water in o...

Страница 21: ...ause of overloading Faulty motor Replace motor Troubleshooting Burner starts and fires but lock out on safety Source Procedure Causes Correction Poor Fire After burner fires immediately jumper across...

Страница 22: ...ocedure Causes Correction Poor Fire After burner fires immediately jumper across flame detector terminals at the primary control SIf burner continues to run does not lock out of safety fault may be po...

Страница 23: ...n air Air leaks into heat exchanger around inspection door etc Correct cause of air leak Excessive draft Adjust barometric draft control for correct draft Incorrect burner head adjustment Correct burn...

Страница 24: ...nk Lift D Filter Type Inspect Change E Pressure Test F All fittings checked for tightness Thermostat A Type Heating Cooling B Anticipator Set C Wires New Old Air Filter A Filter Type Permanent Disposa...

Отзывы: