Table 3. Multi-Zone Installation Wiring Requirements
System and Terminal
Designations
System Capacity
System Voltage
Number of
Conductors
Wire Type
Wire Gauge / MCA
Indoor to Outdoor Unit
Indoor to Outdoor
Wiring
(Communication/Power)
1, 2, 3 and GND
09K and 12K
208/230VAC
4
Stranded and
unshielded
16AWG
Outdoor to Main Power
L1, L2 and GND
09K and 12K
208/230VAC
3
Stranded and
unshielded
16AWG / 9A
Indoor to Outdoor
Wiring
(Communication/Power)
1, 2, 3 and GND
18K
208/230VAC
4
Stranded and
unshielded
16AWG
Outdoor to Main Power
L1, L2 and GND
18K
208/230VAC
3
Stranded and
unshielded
14AWG / 18A
Indoor to Outdoor
Wiring
(Communication/Power)
1, 2, 3 and GND
24K
208/230VAC
4
Stranded and
unshielded
16AWG
Multi-Zone Outdoor Unit to Main Power
Outdoor to Main Power
L1, L2 and GND
18K
208/230VAC
3
Stranded and
unshielded
14AWG / 18A
Outdoor to Main Power
L1, L2 and GND
30K
208/230VAC
3
Stranded and
unshielded
12AWG / 25A
Outdoor to Main Power
L1, L2 and GND
36K
208/230VAC
3
Stranded and
unshielded
10AWG / 30A
Outdoor to Main Power
L1, L2 and GND
48K
208/230VAC
3
Stranded and
unshielded
8AWG / 35A
MCA = Minimum Circuit Amps