43
9.2.
MPC Single-Zone Specifications (0.75 - 1.5 Ton)
Nominal Size - Tons
0.75
1
1.5
Outdoor Unit Model No.
MPC009S4S
MPC012S4S-1L
MPC012S4S-1P
MPC018S4S
Ambient Temperature Operating
Range - °F
Cooling
–13 - 122
–13 - 122
–13 - 122
Heating
–13 - 86
–13 - 86
–13 - 86
Energy Star
Yes
Yes
Yes
Sound Data (dBA)
Cooling/Heating (115V)
- - -
54
- - -
Cooling/Heating (208/230V)
53
53.5
58
Refrigerant
(R-410A)
Charge furnished (115V)
- - -
2 lbs. 8 oz.
- - -
Charge furnished (208/230V)
2 lbs. 6 oz.
2 lbs. 6 oz.
3 lbs. 8 oz.
Maximum line length with furnished charge - ft.
15
15
15
Additional charge required per ft. - oz.
0.16
0.16
0.16
Compressor
No. and Type
(1) Rotary
(1) Rotary
(1) Rotary
Refrigerant oil type
Ester Oil VG74
Ester Oil VG74
Ester Oil VG74
Refrigerant oil charge - oz.
10.5
10.5
14.9
Connections - in.
Liquid/Gas pipe (flare)
1/4 / 3/8
1/4 / 1/2
1/4 / 1/2
Maximum refrigerant pipe length - ft.
82
82
98
Max. difference in level of indoor unit - ft.
33
33
66
Outdoor
Fan
(No.) Diameter - in.
16-1/2
16-1/2
16-1/2
Total air volume - cfm
1295
1295
1765
rpm
800
800
810
Outdoor Coil
Number of rows
2
2
3
Fins per inch
21
21
19
Fin type
Hydrophilic aluminum
Tube outside diameter - in.
5/16
5/16
5/16
Tube type
Rifled copper tubing
Net face area - ft.
2
4.04
4.04
5.90
Application area - sq. ft.
130 - 195
170 - 250
260 - 375
Design Pressure
PSIG
550/340
550/340
550/340
Shipping
Data
Net/Shipping weight (lbs.) (115V)
64 / 69
67 / 72
95 / 102
(208/230V)
64 / 69
64 / 69
95 / 102
ELECTRICAL DATA
Electrical Characteristics - 60 Hz - 1 Phase
208/230V
115V
208/230V
208/230V
1
Maximum Over-current Protection (amps)
15
25
15
25
2
Minimum circuit ampacity
13
19
13
17
Compressor Rated load amps
6.4
6.4
6.4
12
Outdoor Fan Motor
Rated load amps
0.4
0.6
0.4
0.76
Output - W
34
34
34
80
NOTE - Extremes of operating range are plus and minus 10% of line voltage.
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.