background image

14

7.2.  Indoor Unit Connection Points for 

Centralized Controller

Mini-split  indoor  units  can  be  connected  to  a  centralized 

controller (e.g. Lennox VRF Manager - LVM or Trane Tracer) 

or a BACnet or LonWorks gateway using the XYE terminals 

on the indoor unit main board.

To CCM

Comm.Bus

X

Y (E)

Y/G

Figure 15.  Indoor Unit Connection Points  

(Typical Wiring Diagram)

Figure 16.  Typical Indoor Unit Connection Points

7.3.  Dry Mode Operation - Indoor Units

7.3.1.  Procedure

1. 

Press the 

MODE

 button to select 

DRY

 mode.

2. 

 Press  the 

UP/ DOWN

  button  to  select  the  desired 

temperature. The temperature setting range is from 62°F 

to 86°F in one degree increments.

NOTE: 

The blower is preset at a low speed and cannot be 

changed therefore it will get cold and most likely 

will over shoot the temperature setting by 6-10 

degrees depending on the room size or other 

various factors. Also the Follow Me mode does 

not operate in this mode. The Follow Me mode is 

only available when a return air sensor is utilized. 

Typically in most cases the Follow Me mode will 

not be sufficient to remove excessive humidity. 

NOTE: 

In addition, the outdoor units do not have a 

humidistat installed therefore they are unable to 

determine humidity levels. This product is not 

recommend as a main source for dehumidification. 

Note, this well over shoot the temperature by 6-8 

degrees below what was set for dry mode.

NOTE: 

Using this mode will over shoot the temp by 6-8 

degrees below what was set for dry mode.

7.3.2.  Dry Mode Operation Sequence

When in dry mode operation the unit is actually in cooling 

mode with a low speed blower operation. The compressor 

will stop when the room temperature is two degrees Celsius 

lower than the temperature setting. 
However  there  is  a  temperature  compensation  for  cooling 

mode that is two degrees Celsius. So the unit will stop when 

the temperature is four degrees Celsius lower than the room 

temperature settings.

NOTE: 

Four degrees Celsius is equivalent to 8

°

difference.

7.4.  Test Run - Indoor Units

Only perform test run after you have completed the following 

steps:

• 

Electrical Safety Checks – Confirm that the unit’s 

electrical system is safe and operating properly

• 

Gas Leak Checks – Check all flare nut connections and 

confirm that the system is not leaking

• 

Confirm that gas and liquid (high and low pressure) 

valves are fully open.

7.4.1.  Test Run Instructions

You should perform the Test Run for at least 30 minutes.

1. 

Connect power to the unit.

2. 

Press the ON/OFF button on the remote controller to turn 

it on.

3. 

Press  the  mode  button  to  scroll  through  the  functions, 

one at a time:

4. 

Let each function run for five minutes, and perform the 

following checks:

7.4.2.  Before Test Run

Table 3.  Test Run Checklist

Checks

Pass

Fail

No electrical leakage
Unit is properly grounded
All electrical terminals 

properly covered
Indoor and outdoor units 

are solidly installed
All pipe connection points 

do not leak
Water drains properly from 

drain hose
All piping is properly 

insulated
Unit performs COOL 

function properly
Indoor unit louvers rotate 

properly

Indoor unit responds to 

remote controller

Содержание MWCA009S4

Страница 1: ...r Operation 12 6 5 6 Timer ON Operation 12 6 5 7 Timer OFF Operation 13 6 5 8 Modify Timer ON OFF settings 13 7 Connection to Centralized Controller 13 7 1 Set Indoor Unit Address for Centralized Cont...

Страница 2: ...Refrigeration Circuit 26 13 7 1 Evacuation of the Complete Refrigeration Circuit Indoor and Outdoor Unit 26 13 7 2 Refrigerant Charging 27 14 Electronic Function 27 14 1 Abbreviation 27 14 2 Electric...

Страница 3: ...ations Indoor Unit Model No MWCA009S4 MWCA012S4 MWCA018S4 MWCA024S4 Nominal Size Tons 0 75 1 1 5 2 Power Supply 60 hz 1 phase 208 230V 115V 208 230V 208 230V 208 230V Rated load amps 0 22 0 43 0 22 0...

Страница 4: ...VIEW BOTTOM VIEW SIDE VIEW SIDE VIEW Figure 1 Indoor Unit Dimensions Inches mm Size A B C in mm in mm in mm 9K 29 5 8 752 11 3 8 289 8 5 8 219 12K 32 3 4 832 11 3 4 298 8 3 4 222 18K 39 1 8 994 12 1...

Страница 5: ...Hole 2 1 2 in 64 mm diameter Left Rear Hole 2 1 2 in 64 mm diameter Wall Mount Unit Outline 1 3 4 44 1 3 4 44 16 3 4 425 9 1 8 232 5 127 31 5 8 803 7 1 2 191 11 3 4 298 1 3 4 44 Figure 3 12K Indoor U...

Страница 6: ...ft sec 1 6 ft sec 1 6 ft sec 1 6 ft sec 1 6 ft sec 1 6 ft sec 3 2 ft sec 6 6 ft sec 8 2 ft sec 11 5 ft sec 8 ft 9 in 6 ft 6 in 3 ft 3 in 0 ft 0 in 0 ft 0 in 3 ft 3 in 6 ft 6 in 9 ft 8 in 13 ft 1 in 19...

Страница 7: ...Electric Code NEC In Canada wiring must conform with current local codes and the current Canadian Electrical Code CEC 4 1 Overview Refer to unit nameplate for minimum circuit ampacity and maximum over...

Страница 8: ...4 4 1 1 2 2 3 3 5 5 6 6 7 7 C C 9 9 A A B B D D E E F F 1 1 2 2 ON ON 0 0 8 8 4 4 1 1 2 2 3 3 5 5 6 6 7 7 C C 9 9 A A B B D D E E F F 1 1 2 2 ON ON ENC2 S1 ENC2 S1 0 F 0 F 0 F 0 F 0 F 0 F 0 F 0 F NET...

Страница 9: ...WIRING DIAGRAM WIRING DIAGRAM 2 1 1 2 3 4 1 2 3 4 2 4 2 1 2 1 2 1 2 1 2 1 CN_L1 M M 2 2 WHITE WHITE CN_N1 CN_S FAN CAPACITOR BOARD FAN CAPACITOR BOARD PC1_1 PC1_1 PC2_1 PC2_1 1 2 3 4 5 1 2 3 4 5 SWIN...

Страница 10: ...peeds in the following order SLEEP Saves energy during sleeping hours NOTE Hold button for 2 seconds to activate Silence function TURBO Enables unit to reach preset temperature in shortest possible ti...

Страница 11: ...setpoint 2 F 1 C per hour for the first two hours The modified setpoint will be set for five hours After seven total hours the indoor unit will shut off Pushing the on button will turn the unit back...

Страница 12: ...s low Sleep mode Icon displays to indicate that sleep mode operation is on Follow me This icon displays when the air temperature sensor in the wireless remote controller is the sensor being used by th...

Страница 13: ...S1 dip switch and the S2 dial switch to set the address for each indoor unit The table below shows how to set the unique addresses All indoor units are factory set to 0 To change the address to 1 move...

Страница 14: ...was set for dry mode 7 3 2 Dry Mode Operation Sequence When in dry mode operation the unit is actually in cooling mode with a low speed blower operation The compressor will stop when the room tempera...

Страница 15: ...the indoor unit installation process 7 6 Ambient Temperature is Below 63 F 17 C You can t use the remote controller to turn on the COOL function when the ambient temperature is below 17 C In this ins...

Страница 16: ...1 51 5 53 5 57 Refrigerant R 410A Charge furnished 115V 1 lb 5 oz Charge furnished 208 230V 1 lb 2 oz 1 lb 3 oz 2 lbs 0 oz 2 lbs 9 oz Maximum line length with furnished charge ft 20 20 20 30 Additiona...

Страница 17: ...perature F Dry Bulb Indoor Temperature F Dry Bulb Wet Bulb 65 F 54 F 70 F 59 F 75 F 63 F 80 F 67 F Total mBtuh Sensible mBtuh Total mBtuh Sensible mBtuh Total mBtuh Sensible mBtuh Total mBtuh Sensible...

Страница 18: ...98 6 78 8 44 7 17 8 76 7 44 9 17 7 79 122 7 14 6 35 7 43 6 61 7 79 6 94 8 16 7 26 8 3 3 012 208 230V Outdoor Temperature F Dry Bulb Indoor Temperature F Dry Bulb Wet Bulb 65 F 54 F 70 F 59 F 75 F 63...

Страница 19: ...5 11 76 10 59 12 53 11 27 13 09 11 78 13 92 12 53 122 10 59 9 85 11 09 10 31 11 71 10 89 12 39 11 52 8 3 5 024 208 230V Outdoor Temperature F Dry Bulb Indoor Temperature F Dry Bulb Wet Bulb 65 F 54 F...

Страница 20: ...IDE VIEW 12 5 8 322 11 1 4 286 2 3 8 60 3 5 8 92 DRAIN HOLE bottom of unit 11 3 4 298 Figure 18 09 12K and 18K Outdoor Unit Dimensions Inches mm MCA024S4S 27 5 8 702 BOTTOM VIEW FRONT VIEW SIDE VIEW S...

Страница 21: ...TS If the height of the wall C is less than or equal to the height of the smallest unit A the distance from the unit to the wall B must be a minimum of 10 inches 254 mm If 1 2 the height of the unit A...

Страница 22: ...itations OUTDOOR UNIT OUTDOOR UNIT INDOOR UNIT INDOOR UNIT Maximum Line Set Length Maximum Line Set Length Maximum Elevation Outdooor Unit BELOW Indoor Unit Maximum Elevation Outdooor Unit ABOVE Indoo...

Страница 23: ...n x 25 ft 90X52 N A N A 1 4 in x 1 2 in x 50 ft X0259 N A N A 3 8 in x 5 8 in x 25 ft X8406 N A 3 8 in x 5 8 in x 50 ft X8407 N A 10 1 Pipe Length Maximum piping length and height difference Table 5 P...

Страница 24: ...risk of fire Wiring must be installed so that all cover plates can be securely closed In the U S A wiring must conform with current local codes and the current National Electric Code NEC In Canada wir...

Страница 25: ...there are any leaks Fully close the Handle Lo valve of the manifold valve and turn off the vacuum pump After five minutes confirm that the gauge needle is not moving Turn the flare nut on the three wa...

Страница 26: ...18N m Be sure to check for gas leakage 13 6 2 Air Purging with Vacuum Pump Completely tighten the flare nuts of the indoor and outdoor units confirm that both the two way and three way valves are set...

Страница 27: ...refer to the previous instruction when vacuum and recycle refrigerant 14 Electronic Function 14 1 Abbreviation T1 Indoor ambient temperature T2 Middle indoor heat exchanger coil temperature T3 Outdoo...

Страница 28: ...hen the compressor discharge is getting higher the running frequency will be limited as below rules If 215 6 F 102 C T5 244 4 F 115 C decrease the frequency to the lower level every two minutes until...

Страница 29: ...5 162 80 67 26 67 19 44 103 104 123 138 135 129 132 140 162 173 90 73 32 22 22 78 112 113 139 152 149 138 145 154 180 189 17 2 Capacity Request Calculations Total capacity Request Norm code HP 10 modi...

Страница 30: ...while the maximum running frequency will be adjusted according to the outdoor ambient temp 17 3 Outdoor Fan Control 17 3 1 Cooling Mode Normally the system will choose the running fan speed according...

Страница 31: ...31 38 Exit low ambient cooling mode run with high fan for 1 minute Low 30 27 23 off...

Страница 32: ...the front panel by the tabs on the both sides and lift it TAB Step 2 Push up the bottom of an air filter step 1 and then pull it out downwards step 2 FILTER Step 3 Open the horizontal louver and push...

Страница 33: ...eft then remove it Step 6 Disconnect the connector for display board Step 7 Slide the front panel side to side to release each axis Step 8 Open the screw cap and then remove the three screws Step 9 Re...

Страница 34: ...in the direction shown in the right picture 18 1 2 Electrical Parts NOTE When handling electrical parts use anti static gloves NOTE Remove the front panel see Step 1 on page 32 before disassembling el...

Страница 35: ...the step motor and the T2 sensor Step 6 Open the left side plate of electronic control box Step 7 Open the two clips on the front of the electric box Step 8 Open the upper cover plate of electronic c...

Страница 36: ...front panel and electrical parts see both Front Panel on page 32 and Electrical Parts on page 34 Electrical parts before disassembling evaporator Step 1 Disassembly the pip holder located at the rear...

Страница 37: ...ard of the fan motor Screws Step 2 Remove the bearing sleeve Step 3 Remove the fixing screw Step 4 Pull out the fan motor and fan assembly from the side Fixing Screw 18 1 5 Step Motor NOTE Remove the...

Страница 38: ...ker Step 2 Remove the screw of the big handle and then remove the handle Step 3 Remove the screws of the top cover and then remove top cover One of the screws is located underneath the big handle Top...

Страница 39: ...Panel 18 2 2 Panel Plate MWCA024S4 Step 1 Turn off the air conditioner and the power breaker Step 2 Remove the screws that secure the handle and then remove the handle Step 3 Remove the screws from th...

Страница 40: ...nsor T3 outdoor ambient temperature sensor T4 and discharge temperature sensor TP Step 4 Disconnect the expansion valve Step 5 Remove electronic control box Compressor T3 T4 and TP EEV Fan Motor 4 way...

Страница 41: ...emove electronic control box Compressor Reactor 4 way valve Fan Motor EEV T3 T4 and TP 18 2 6 Fan Disassembly MWCA009S4 and MWCA012S4 NOTE Antistatic gloves must be worn when you dissemble the electro...

Страница 42: ...e screws securing the cover of the electronic control box cover Step 3 Disconnect connector from electronic control board plug Step 4 Remove the screws securing the fan motor to body Then remove fan m...

Страница 43: ...securing the fan motor from body Remove the fan Fan Motor 18 2 9 Sound Blanket NOTE Recover refrigerant before removing the compressor Sound Blanket Sound Blanket side 18 2 10 Compressor NOTE Recover...

Страница 44: ...the hex nuts and washers which are located on the bottom of the plate which are securing the compressor Step 4 Heat up the brazed parts and then remove the discharge and suctions pipes Step 5 Lift the...

Отзывы: