Page 4
MS8C / MS8H (208-230V)
Specifications
- AIR CONDITIONER SYSTEMS
OUTDOOR UNIT
Nominal Tonnage
0.75
1
1.5
2
Outdoor Unit Model No.
MS8CO09P
MS8CO12P
MS8CO18P
MS8CO24P
Connections (in.)
Small line o.d. flare
1/4
1/4
1/4
1/4
Large line o.d. flare
3/8
3/8
1/2
5/8
Ambient Temperature Operating Range °F
0 109
0 109
5 109
5 109
1
Refrigerant (R410A) furnished
2 lbs. 14 oz.
2 lbs. 14 oz.
3 lbs. 1 oz.
3 lbs. 9 oz.
Outdoor Coil
Net face area sq. ft.
4.08
4.49
5.96
7.66
Tube diameter in.
1/4
3/8
1/4
1/4
Number of rows
2
2
2
2
Fins per inch
20
20
20
20
Outdoor Fan
Motor
Diameter in.
153/4
153/4
201/2
213/4
No. of blades
3
3
3
3
Cfm
940
940
1885
2355
Rpm
680/900
680/900
800
800
Shipping Data lbs.
Outdoor Unit
91
97
110
132
ELECTRICAL DATA
Line voltage data 60 hz 1ph
208/230V
208/230V
208/230V
208/230V
2
Maximum overcurrent protection (amps)
15
15
20
25
3
Minimum circuit ampacity
10
10
13
16
Compressor
Rated load amps
27.2
6.5
9.7
11
4
Compressor Power Input (W)
1075
860
1200
1420
Outdoor Fan
Motor
Rated load amps
0.13
0.13
0.28
1.1
Output (W)
40
30
60
90
MATCHING INDOOR UNIT
Indoor Unit Model No.
MS8CI09P
MS8CI12P
MS8CI18P
MS8CI24P
Connections (in.)
Small line o.d. flare
1/4
1/4
1/4
1/4
Large line o.d. flare
3/8
3/8
1/2
5/8
Indoor Blower Air Volume (cfm)
Turbo
305
335
500
590
High
275
275
460
470
Medium
255
255
385
410
Low
220
220
325
355
Indoor Blower RPM
Turbo
1260
1330
1500
1500
High
1100
1100
1200
1200
Medium
950
950
1050
1050
Low
750
750
900
900
Indoor Coil
Net face area sq. ft.
1.65
1.65
2.33
3.23
Tube diameter in.
1/4
1/4
1/4
1/4
Number of rows
2
2
2
2
Fins per inch
20
20
20
18
Indoor Blower
Diameter x Length in.
3.6 x 25.4
3.6 x 25.4
3.9 x 28
3.9 x 30
Type
Crossflow
Crossflow
Crossflow
Crossflow
Shipping Data lbs.
Indoor Unit
31
29
38
47
ELECTRICAL DATA
Line voltage data 60 hz 1ph
208/230V
208/230V
208/230V
208/230V
Rated Load Amps
0.20
0.20
0.32
0.24
Output (W)
20
20
20
60
NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Refrigerant charge sufficient for 15 ft. of line set.
2
HACR type circuit breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
4
Rated Input