Page 13
Corp. 1244-L9
at a slight angle 1/4” (6 mm) shorter than the thickness
of the wall.
CUT PVC FOR WALL SLEEVE AT SLIGHT ANGLE
CUTTING PVC FOR WALL SLEEVE
FIGURE 14
4. Place a field-provided plastic cover over the end of the
pipe that will be visible from the inside wall and insert
the pipe in the wall.
PLASTIC COVER
(FIELD PROVIDED)
INSIDE
OUTSIDE
SLIGHT
ANGLE
WALL
PVC PIPE
PVC WALL SLEEVE INSTALLATION
FIGURE 15
SECURE WALL MOUNTING BRACKET TO WALL
Determine that wall will support the weight of the indoor
unit. See table 1 for indoor unit weight. Install the wall
mounting bracket so that is is correctly positioned
horizontally and vertically. The indoor unit must be installed
level on the wall to allow proper condensate drainage.
1. Use a carpenter's level or tape measure to verify the
wall mounting bracket is horizontally level.
2. Secure the wall mounting bracket to the wall using the
provided screws. If possible, align the rear panel screw
holes with wall stud locations marked on the wall.
HINT
—
Use the wall mounting bracket as a template to
mark locations where screws will be used.
3. Secure the wall mounting bracket to the wall using as
many screws into studs as possible. All other screws
must be secured using plastic wall anchors.
NOTE
—
It is important to use all screws provided to secure
the wall mounting bracket to the wall. Additional holes may
be drilled through the metal wall mounting bracket to better
secure wall bracket to wall studs.
WALL MOUNTING
BRACKET
SECURING WALL MOUNTING BRACKET TO WALL
FIGURE 16
4. The wall mounting bracket must be installed flush
against the wall so that the indoor unit will be flush after
installation. Any space between the wall and unit will
cause noise and vibration.
5. The wall mounting bracket must be installed
horizontally level on the wall.
6. If the wall is made of brick, concrete or other similar
material, then drill pilot holes in the wall. Insert
field-provided plastic anchors for mounting screws.
DRILL PILOT HOLES
USE ANCHORS
INSTALL ANCHORS
MASONRY APPLICATIONS
FIGURE 17
CONDENSATE DRAIN CONFIGURATION
If the condensate line needs to be moved, use the following
procedure to change the drain line exit location.
NOTICE
Care must be taken when moving the condensate line to
the opposite position to prevent damaging the
condensate line or connector.