Page 43
F- Proper Gas Flow (Approximate)
TABLE 18
GAS METER CLOCKING CHART
ML196
Unit
Seconds For One Revolution
Natuarl
LP/Propane
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
Dial
-045
80
160
200
400
-070
55
110
136
272
-090
41
82
102
204
-110
33
66
82
164
Natural-1000 btu/cu ft LP-2500 btu/cu ft
NOTE -
To obtain accurate reading, shut off all other gas
appliances connected to meter.
Furnace should operate at least 5 minutes before check
-
ing gas flow. Determine time in seconds for two revolu
-
tions of gas through the meter. (Two revolutions assures
a more accurate time). Divide by two and compare to time
in TABLE 18. If manifold pressure matches TABLE 17 and
rate is incorrect, check gas orifices for proper size and
restriction. Remove temporary gas meter if installed.
G- Proper Combustion
Furnace should operate at least 15 minutes with correct
manifold pressure and gas flow rate before checking com
-
bustions. Take sample beyond the flue outlet and compare
The maximum carbon monoxide reading
should not exceed 100 ppm.
TABLE 19
ML196 Unit
CO
2
% Nat
CO
2
% LP
-045
7.5 - 8.5
8.6 - 9.6
-070
-090
-110
H- High Altitude
NOTE -
In Canada, certification for installations at eleva
-
tions over 4500 feet (1372 m) is the jurisdiction of local
authorities.
ML196DFE-1, -2 and -3 units require no manifold pres
-
sure adjustments for operation at altitudes up to 10,000
feet (3048 m) above sea level. However, -4 and later
units installed at altitude of 4501 - 10,000 feet (1373 to
3048m) may require a pressure switch change which can
be ordered separately and manifold de-rate. See TABLE
17 for manifold pressures at varying altitudes. TABLE 20
lists conversion kit and pressure switch requirements at
varying altitudes. The combustion air pressure switch is
factory-set and requires no adjustment.
NOTE -
A natural to LP/propane gas changeover kit is
necessary to convert this unit. Refer to the changeover kit
installation instruction for the conversion procedure.
TABLE 20
Conversion Kit and Pressure Switch Requirements at Varying Altitudes
ML196
Unit
Natural to LP/
Propane
High Altitude
Natural Burner
Orifice Kit
High Altitude
LP/Propane Burner
Orifice Kit
High Altitude Pressure Switch
0 - 7500 ft
(0 - 2286m)
7501 - 10,000 f t
(2286 - 3038m)
7501 - 10,000 ft
(2286 - 3038m)
4501 - 7500 ft
(1373 - 2286m)
7501 -10,000 ft
(2286 - 3048m)
-045
11K49
73W37
11K44
11U65
11U66
-070
11U70
11U68
-090
11U71
11U68
-110
11U70
11U68
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-
1370 m).