Page 10
Burner Box Assembly
Gas Valve
Burner Box Front
Rollout Switch(s)
Flame Sensor
Ignitor
Burner Assembly
FIGURE 6
B-Heating Components
Combustion air inducer (B6), primary limit control (S10),
SureLight ignitor, burners, flame rollout switch (S47), gas
valve (GV1), combustion air prove switch (S18), and clam
-
shell heat exchangers are located in the heating compart
-
ment. The heating compartment can be accessed by re
-
moving the outer access panel.
1. Flame Rollout Switches (FIGURE 6)
Flame rollout switches S47 are SPST N.C. high tempera
-
ture limits located on the top left and bottom right of the
front buner box plate. S47 is wired to the burner ignition
control A92. When either of the switches sense flame roll
-
out (indicating a blockage in the combustion passages),
the flame rollout switch trips, and the ignition control im
-
mediately closes the gas valve. Switch S47 in all ML196D
-
FE units is factory preset to open at 210 F + 12 F (99 C +
6.7 C) on a temperature rise. All flame rollout switches are
manual reset. See table 4 flash code 8 for troubleshooting.
ML196DFE units use an aluminized steel primary and
stainless steel secondary heat exchanger assembly. Heat
is transferred to the air stream from all surfaces of the heat
exchanger. The shape of the heat exchanger ensures
maximum efficiency.
The combustion air inducer pulls fresh air through the
burner box. This air is mixed with gas in the burners. The
gas / air mixture is then burned at the entrance of each
clamshell. Combustion gases are then pulled through the
primary and secondary heat exchangers and exhausted
out the exhaust vent pipe.
3. Primary Limit Control (FIGURE 7)
Primary limit (S10) used on ML196DFE units is locat
-
ed in the heating vestibule panel. When excess heat is
sensed in the heat exchanger, the limit will open. Once
the limit opens, the furnace control energizes the supply
air blower and de-energizes the gas valve. The limit auto
-
matically resets when unit temperature returns to normal.
The switch is factory set and cannot be adjusted. For limit
replacement remove wires from limit terminals and rotate
limit switch 90 degrees. Slowly remove from the vestibule
panel. Install replacement limit with same care.