background image

Page 8

14ACX SERIES

STEP 2 -- REFRIGERANT PIPING -- Installing Indoor Expansion Valve 

This outdoor unit is designed for use in systems that use either an fixed orifice (RFC) (included with outdoor unit), or
expansion valve metering device (purchased separately) at the indoor coil. See the

 14ACX

 

Product Specifications bulletin

(EHB) 

for approved expansion valve kit match ups. The expansion valve unit can be installed internal or external to the

indoor coil. In applications where an uncased coil is being installed in a field-provided plenum, install the expansion valve in a
manner that will provide access for field servicing of the expansion valve. Refer to below illustration for reference during
installation of expansion valve unit. After installation of the indoor coil metering device, proceed to 

Step 5.

TWO-PIECE

PATCH PLATE

(UNCASED

COIL ONLY)

SUCTION

LINE

LIQUID LINE

ORIFICE

HOUSING

DISTRIBUTOR

TUBES

LIQUID LINE

MALE EQUALIZER LINE

FITTING (SEE

EQUALIZER LINE

INSTALLATION FOR

DETAILS)

SENSING

LINE

EQUALIZER
LINE

CHECK/

EXPANSION

VALVE

TEFLON

®

RING

(Uncased Coil Shown)

Sensing bulb insulation is required if
check/expansion valve is installed external
to the coil casing. See sensing bulb
installation for bulb positioning.

STUB

END

TEFLON

®

RING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

DISTRIBUTOR

ASSEMBLY

ON 7/8” AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O'CLOCK
POSITION. NEVER MOUNT
THE SENSING BULB ON
BOTTOM OF LINE.

12

ON LINES SMALLER THAN
7/8”, MOUNT SENSING
BULB AT EITHER THE 3 OR
9 O'CLOCK POSITION.

12

BULB

SUCTION LINE

SUCTION LINE

NOTE

 — NEVER MOUNT SENSING BULB ON BOTTOM OF LINE.

BULB

BULB

BULB

SUCTION LINE

FLARE NUT

COPPER FLARE
SEAL BONNET

MALE BRASS EQUALIZER
LINE FITTING

FLARE SEAL CAP

OR

SENSING BULB INSTALLATION

EQUALIZER LINE INSTALLATION

A -

Remove and discard either the flare seal cap or flare nut with
copper flare seal bonnet from the equalizer line port on the suc­
tion line as illustrated in the figure below.

B -

Remove the field-provided fitting that temporarily reconnected
the liquid line to the indoor unit's distributor assembly.

INDOOR EXPANSION VALVE INSTALLATION

C -

Install one of the provided Teflon

®

 rings around the

stubbed end of the check/expansion valve and use re­
frigerant oil to lightly lubricate the connector threads
and exposed surface of the Teflon

®

 ring.

D -

Attach the stubbed end of the check/expansion valve
to the liquid line orifice housing. Finger tighten, then use
an appropriately sized wrench to turn an additional 1/2
turn clockwise as illustrated in the figure to the right, or
tighten to 20 ft-lb.

E -

Place the remaining Teflon

®

 washer around the other

end of the check expansion valve. Lightly lubricate
connector threads and expose surface of the Teflon

®

ring with refrigerant oil.

F -

Attach the liquid line assembly to the check expansion
valve. Finger tighten, then use an appropriately sized
wrench to turn an additional 1/2 turn clockwise as illus­
trated in the figure above or tighten to 20 ft-lb.

A -

Attach the suction line sensing bulb in the proper orien­
tation as illustrated below using the clamp and screws
provided.

B -

NOTE

 - Though it is preferred to have the sensing bulb

installed on a horizontal run of the suction line, installa­
tion on a vertical run of piping is acceptable if necessary.

NOTE 

- Confirm proper thermal contact between the suction

line and check/expansion bulb before insulating the sensing
bulb.

C -

Connect the equalizer line from the check/expansion
valve to the equalizer  port on the suction line. Finger
tighten the flare nut, then tighten an additional 1/8 turn (7
ft-lbs) as illustrated to the right.

1

2

3

4

5

6

7

8

9

10

11

12

1/8 Turn

1

2

3

4

5

6

7

8

9

10

11 12

1/2 Turn

FIGURE 9

Содержание Merit 14ACX-018-230

Страница 1: ...tdoor air conditioner is designed for use with HFC 410A refrigerant only This unit must be installed with an approved indoor air handler or coil See the Lennox 14ACX Product Specifications bulletin EH...

Страница 2: ...ing or stowing the panels consider any weather conditions especially wind that may cause panels to be blown around and damaged NOTICE Roof Damage This system contains both refrigerantand oil Some rubb...

Страница 3: ...e rises above 40 psig DO NOT REPLACE COMPRESSOR LIQUID LINE FILTER DRIER INSTALLATION The provided filter drier must be field installed in the liquid line between the outdoor unit s liquid line servic...

Страница 4: ...THE LIQUID LINE TO THE SUCTION LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices should be used if line set is to be installed on ext...

Страница 5: ...ndoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SER...

Страница 6: ...d debur the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the suction and liquid line service ports 1 2 ANGLE TYPE SERVICE VALVE SERVICE PORT CORE...

Страница 7: ...WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated clo...

Страница 8: ...TION EQUALIZER LINE INSTALLATION A Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the suc tion line as illustrated in the figur...

Страница 9: ...door unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector F After leak testing disconnect gauge...

Страница 10: ...utting off the vacuum pump and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylin...

Страница 11: ...re only with this product CAUTION Failure to use properly sized wiring and circuit breaker may result in property damage Size wiring and circuit breaker s per Product Specifications bulletin EHB and u...

Страница 12: ...t and secure with provided wire tie B Make 24VAC thermostat wire connections Locate the two wires from the contactor and make connection using field provided wire nuts Yellow to Y1 Black to C common R...

Страница 13: ...ped with a service port which has a factory installed valve stem Figures 15 and 16 provide information on how to access and operate both angle and ball type service valves Torque Requirements When ser...

Страница 14: ...he tables provided on the charging procedure sticker located on the unit access panel Detailed information is provided in the 14ACX Installation and Service Procedures manual Corp0638 L10 which is ava...

Страница 15: ...as necessary 6 Inspect contactor contacts for pitting or burn marks Replace as necessary 7 Check outdoor fan motor for worn bearings bushings Replace as necessary 8 Inspect and clean outdoor coils if...

Страница 16: ...re Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and appr...

Отзывы: