14ACX SERIES

STEP 2 -- REFRIGERANT PIPING -- Removing Existing Indoor Metering Device

SENSING

LINE

TEFLON

®

 RING

FIXED ORIFICE

BRASS NUT

LIQUID LINE ASSEMBLY

(INCLUDES STRAINER)

LIQUID LINE ORIFICE HOUSING

DISTRIBUTOR TUBES

DISTRIBUTOR

ASSEMBLY

REMOVE AND DISCARD

WHITE TEFLON

®

 SEAL

(IF PRESENT)

A -

On fully cased coils, remove the coil access and plumbing panels.

B -

Remove any shipping clamps from the liquid line and distributor as­
sembly.

C -

Using two wrenches, disconnect liquid line from liquid line orifice hous­
ing. Take care not to twist or damage distributor tubes during this pro­
cess.

D -

Remove and discard fixed orifice, valve stem assembly (if present)
and Teflon

®

 washer as illustrated above.

E -

Use a field-provided fitting to temporarily reconnect the liquid line to the
indoor unit's liquid line orifice housing.

TYPICAL EXISTING FIXED ORIFICE
REMOVAL PROCEDURE 
(UNCASED COIL SHOWN)

TYPICAL EXISTING EXPANSION VALVE REMOVAL
PROCEDURE (UNCASED COIL SHOWN)

TWO-PIECE PATCH PLATE

(UNCASED COIL ONLY)

SUCTION

LINE

DISTRIBUTOR

ASSEMBLY

DISTRIBUTOR

TUBES

LIQUID

LINE

MALE EQUALIZER

LINE FITTING

EQUALIZER
LINE

EXPANSION

VALVE

TEFLON®
RING

STUB END

TEFLON

®

RING

SENSING BULB

LIQUID LINE

ORIFICE

HOUSING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

A -

On fully cased coils, remove the coil access and plumbing panels.

B -

Remove any shipping clamps from the liquid line and distributor
assembly.

C -

Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the suction line.

D -

Remove the suction line sensing bulb.

E -

Disconnect the liquid line from the check expansion valve at the
liquid line assembly.

F -

Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during
this process.

G -

Remove and discard check expansion valve and the two Teflon

®

rings.

H -

Use a field-provided fitting to temporarily reconnect the liquid line
to the indoor unit's liquid line orifice housing.

LOW

HIGH

EXISTING

INDOOR

UNIT

GAUGE

MANIFOLD

CYLINDER CONTAINING
CLEAN HCFC-22* TO BE
USED FOR FLUSHING
(Positioned to deliver liquid
refrigerant)

LIQUID LINE SERVICE

VALVE

INLET

DISCHARGE

TANK
RETURN

CLOSED

OPENED

RECOVERY

CYLINDER

RECOVERY MACHINE

NEW

OUTDOOR

UNIT

SUCTION LINE

SERVICE VALVE

SUCTION

LIQUID

1

A -

HCFC-22 cylinder with clean refrigerant* (positioned to deliver liquid
refrigerant) to the suction service valve.

B -

HCFC-22 gauge set (low side) to the liquid line valve.

C -

HCFC-22 gauge set center port to inlet on the recovery machine with an
empty recovery tank connected to the gauge set.

D -

Connect recovery tank to recovery machine per machine instructions.

CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE

A

B

C

D

B

OR

FLUSHING LINE SET

A -

Set the recovery machine for liquid recovery and start the
recovery machine. Open the gauge set valves to allow the
recovery machine to pull a vacuum on the existing system line
set and indoor unit coil.

B -

Position the cylinder of clean HCFC-22* for delivery of liquid
refrigerant and open its valve to allow liquid refrigerant to flow
into the system through the suction line valve. Allow the
refrigerant to pass from the cylinder and through the line set and
the indoor unit coil before it enters the recovery machine.

C -

After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC-22
vapor is recovered. Allow the recovery machine to pull the
system down to 0.

D -

Close the valve on the inverted HCFC-22 drum and the gauge
set valves. Pump the remaining refrigerant out of the recovery
machine and turn the machine off.

The line set and indoor unit coil must be flushed with at least the same
amount of clean refrigerant* that previously charged the system.
Check the charge in the flushing cylinder before proceeding.

1A

2

3

1B

*IMPORTANT - Clean refrigerant is any refrigerant in a system that has not had compressor burn out. If the system
has experienced burn out, it is recommended that the existing line set and indoor coil be replaced.

FIGURE 7

Содержание Merit 14ACX-018-230

Страница 1: ...tdoor air conditioner is designed for use with HFC 410A refrigerant only This unit must be installed with an approved indoor air handler or coil See the Lennox 14ACX Product Specifications bulletin EH...

Страница 2: ...ing or stowing the panels consider any weather conditions especially wind that may cause panels to be blown around and damaged NOTICE Roof Damage This system contains both refrigerantand oil Some rubb...

Страница 3: ...e rises above 40 psig DO NOT REPLACE COMPRESSOR LIQUID LINE FILTER DRIER INSTALLATION The provided filter drier must be field installed in the liquid line between the outdoor unit s liquid line servic...

Страница 4: ...THE LIQUID LINE TO THE SUCTION LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices should be used if line set is to be installed on ext...

Страница 5: ...ndoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SER...

Страница 6: ...d debur the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the suction and liquid line service ports 1 2 ANGLE TYPE SERVICE VALVE SERVICE PORT CORE...

Страница 7: ...WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated clo...

Страница 8: ...TION EQUALIZER LINE INSTALLATION A Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the suc tion line as illustrated in the figur...

Страница 9: ...door unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector F After leak testing disconnect gauge...

Страница 10: ...utting off the vacuum pump and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylin...

Страница 11: ...re only with this product CAUTION Failure to use properly sized wiring and circuit breaker may result in property damage Size wiring and circuit breaker s per Product Specifications bulletin EHB and u...

Страница 12: ...t and secure with provided wire tie B Make 24VAC thermostat wire connections Locate the two wires from the contactor and make connection using field provided wire nuts Yellow to Y1 Black to C common R...

Страница 13: ...ped with a service port which has a factory installed valve stem Figures 15 and 16 provide information on how to access and operate both angle and ball type service valves Torque Requirements When ser...

Страница 14: ...he tables provided on the charging procedure sticker located on the unit access panel Detailed information is provided in the 14ACX Installation and Service Procedures manual Corp0638 L10 which is ava...

Страница 15: ...as necessary 6 Inspect contactor contacts for pitting or burn marks Replace as necessary 7 Check outdoor fan motor for worn bearings bushings Replace as necessary 8 Inspect and clean outdoor coils if...

Страница 16: ...re Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and appr...

Отзывы: