©2018 Lennox Industries Inc.
Dallas, Texas, USA
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
NOTICE !
For more in-depth information, consult the Installa
tion and Service Procedures manual, available as
Corp. 0638-L10 on LennoxPros.com or through the
Technical Support Department at 800-453-6669.
INSTALLATION
INSTRUCTIONS
Merit
®
Series 14ACX
Units
AIR CONDITIONERS
507465-01
09/2018
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or
damage to property.
Installation and service must be performed by a licensed
professional installer (or equivalent) or a service agency.
GENERAL
This 14ACX outdoor air conditioner is designed for use with
HFC-410A refrigerant only. This unit must be installed with
an approved indoor air handler or coil. See the Lennox
14ACX Product Specifications bulletin (EHB) for approved
indoor component match ups.
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
STEP 1 -- SETTING THE UNIT -- Clearances
NOTES -
Service clearance of 30 in. (762 mm) must be maintained on one of
the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. (914 mm).
Clearance to one of the remaining two sides may be 12 in. (305
mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit.
See
NOTES
See NOTES
See NOTES
See
NOTES
CONTROL
BOX
FIGURE 1