Page 14 

3.  Slide the gas valve switch to the “ON” position (see 

Figure 7).

4.  Turn on electrical power to the unit.
5.  Set the room thermostat to the desired temperature. 

(If the thermostat “set” temperature is above room 

temperature after the pre-purge time expires, main 

burners will light.)

To Shut Down Main Burners

1. 

Turn off electrical power to unit.

2.  Slide the gas valve switch to the “OFF” position (see 

Figure 7).

Figure 7. Gas Valve









Post-Start Check List

After the entire control circuit has been energized and the 

heating section is operating, make the following checks:
1.  Check for gas leaks, using soapy solution, in the unit 

piping as well as the supply piping.

2.  Check for correct manifold gas pressures (see Manifold 

Gas Pressure Adjustment Regulator sections).

3.  Check the supply gas pressure. It must be within the 

limits shown on the rating plate. Supply pressure 

should be checked with all gas appliances in the 

building at full fire. At no time should the standby gas 

pressure exceed 13” w.c., nor the operation pressure 

drop below 5” w.c. for natural gas units or 11” w.c. for 

propane gas. If gas pressure is outside these limits, 

contact the gas supplier for corrective action.

4. 

Adjust temperature rise to the range specified on the 

rating plate.

Manifold Gas Pressure Adjustment Regulator – 

Natural Gas

For purpose of input adjustment, the minimum permissible 

gas supply pressure is 5” w.c. for natural gas.

Gas input must never exceed the input capacity shown on 

the rating plate. 

Units fueled by natural gas are rated for 

manifold pressures of 2.0 inches W.C. for first stage 

and 3.5 inches W.C. for second stage.

The  manifold  pressure  can  be  measured  by  shutting  off 

the gas, removing the pipe plug in the downstream side 

of the gas valve, and connecting a water manometer 

or gauge. 

Under  no  circumstances  should  the  final 

manifold pressure vary more than 0.3” w.c. from the 

above specified pressures.

 To adjust the regulator, turn 

the adjusting screw on the regulator clockwise to increase 

pressure and input or counterclockwise to decrease 

pressure and input.  See Figure 7 to assist in locating the 

regulator on the gas valve.

Check the furnace rate by observing the gas meter, making 

sure all other gas appliances are turned off. The test hand 

on the meter should be timed for at least one revolution, 

noting the number of seconds per revolution. The heating 

value of the gas can be obtained from the local utility.

BTU/HR 

Input

=

Cubic Feet per 

Revolution

x 3600 x Heating 

Value

# Seconds per 

Revolution

Example

: By actual measurement, it takes 38 seconds for 

the hand on the 1-cubic foot dial to make a revolution with 

a 100,000 BTU/HR furnace running. The result is 99,750 

BTU/HR, which is close to the 100,000 BTU/HR rating of 

the furnace.

Manifold Gas Pressure Adjustment Regulator – 

LP/Propane Gas

LP/propane units require a LPG regulator on both the gas 

valve and on the LP/propane tank.

IMPORTANT

For purpose of input adjustment, the 

minimum permissible gas supply pressure (inlet side of 

gas valve) is 11” w.c. for LP/propane.

If at any time ignition is slow and burner does not seem to 

be operating correctly, check manifold pressure (outlet side 

of the gas valve).

 It should be 10” to 10.5” w.c. pressure 

for LP/propane.

Units fueled by LP/propane gas are rated for manifold 

pressures of 5.6 inches W.C. for first stage and 10.0 

inches

High Altitude

The input rate shown on the rating plate is for elevations 

up to 2000 feet. For elevations from 2001 to 4500 feet, 

the input rate is reduced by 5%. For elevations above 

4500 feet, refer to the National Fuel Gas Code Z223.1 

(latest edition) or the Canadian Installation Codes CAN/

CGA-B149.1 & B149.2 for further details. 

Содержание LRP16GE Series

Страница 1: ...stries Inc Dallas Texas USA THIS MANUAL MUST BE LEFT FOR FUTURE REFERENCE WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss o...

Страница 2: ...17 07 13 44 13 44 14 32 16 06 6 20 40 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS 11 49 2 33 47 66 1 98 16 77 2 48 14 02 47 66 POWER ENT...

Страница 3: ...AGE ENTRY 7 8 DIA KNOCKOUT GAS SUPPLY 44 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS TOP VIEW POWER ENTRY GAS ENTRY RETURN AIR 2 11 19 49...

Страница 4: ...44 3 8 1127 44 3 8 1127 16 7 8 429 13 7 8 352 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 4 19 1 25 5 1 2 140 5 3 4 146 11 1 2 287 17 1 4 438 1 3 8 35 3 3 4 95 13 3...

Страница 5: ...13 in 76 x 330 mm 52 7 8 1343 44 3 8 1127 19 1 2 380 11 1 2 287 19 1 2 380 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 3 4 95 22 7 8 581 7 178 3 4 19 1 25 NOTE If bo...

Страница 6: ...8 203 SIDES AND BACK FLANGE 6 152 UNIT BASE RAIL CLIPS 4 NOTE Minimum Height 4 102 UNIT BASE RAIL CLIPS 4 Usage A B C in mm in mm in mm 24 36 42 7 8 1089 13 7 8 352 16 7 8 429 48 60 51 3 8 1305 19 1 2...

Страница 7: ...nits are not suitable for use with conventional venting systems Inspection As soon as the unit is received it should be inspected for possible damage during transit If damage is evident the extent of...

Страница 8: ...s may be installed on combustible floors Units must be installed outdoors Clearance to combustibles below the unit flue is 10 inches since the flue points down Do not permit overhanging structures or...

Страница 9: ...truction bag see Figure 2 Vent Hood Attach with Screws Figure 2 Installing the Vent Cover Rigging Unit Exercise care when moving the unit Do not remove any packaging until the unit is near the place o...

Страница 10: ...ilter rack kit If an existing gas furnace is being removed from a common venting system when this packaged unit is installed then read and follow the instructions in the Removal of Unit from Common Ve...

Страница 11: ...rating plate Gas Piping Recommendations A drip leg and a ground joint union must be installed in the gas piping A ground joint union is recommended by the manifold valve When required by local codes a...

Страница 12: ...he National Electrical Code ANSI NFPA No 70 latest edition Canadian Electrical Code Part 1 CSA C22 1 latest edition or local codes where they prevail Use wiring with a temperature limitation of 75 C m...

Страница 13: ...d insulated wires 18 AWG should be used to connect the thermostat to the unit Compressor Units are shipped with compressor mountings factory adjusted and ready for operation Do not loosen compressor m...

Страница 14: ...as valve and connecting a water manometer or gauge Under no circumstances should the final manifold pressure vary more than 0 3 w c from the above specified pressures To adjust the regulator turn the...

Страница 15: ...roughout the external static range A particular CFM can be obtained by positioning jumpers COOL HEAT and ADJUST on the blower control The HEAT and COOL jumpers are labeled A B C and D Each of the numb...

Страница 16: ...duce the selected air flow rate by 25 percent when humidity levels are high An LED D1 lights when the blower is operating in the dehumidification mode Cooling System The cooling system is a factory ch...

Страница 17: ...nds of the ignition trial If the flame is established within 10 seconds the control de energizes the spark If flame is not established within 10 seconds the gas valve and spark are de energized and th...

Страница 18: ...need cleaning Sooting of a gas appliance is highly irregular and once cleaned the cause of the sooting must be determined If the heat exchanger should become sooted it can be cleaned as follows 1 Remo...

Страница 19: ...eration Call for heat 2 Flash Two flashes in second with 1 second pause System lockout Failed to detect or sustain flame 3 Flash Three flashes in 1 5 seconds with 1 second pause Pressure switch senses...

Страница 20: ...00 400 1260 1080 900 720 1400 1200 1100 975 630 540 450 360 048 Blower Performance 0 through 0 80 in w g External Static Pressure Range 1980 1760 1540 1320 1350 1200 1100 1000 990 880 770 660 NORM 180...

Страница 21: ...Page 21 Figure 9 Wiring Diagram Single Phase Wiring Diagram LRP16GE...

Страница 22: ...being pulled through the condensate line will prevent positive drainage without a proper trap The condensate drain line must be properly trapped routed to a suitable drain and primed prior to unit com...

Страница 23: ...JUST jumper is labeled Test and Norm The and pin settings are used to add or subtract a percentage of the CFM selected The Test jumper is used to operate the motor in the test mode Figure 12 shows the...

Страница 24: ...e is no demand for heating or cooling the blower control will provide 50 percent of the COOL CFM selected DEHUMIDIFICATION The blower control includes an HUM terminal which provides for connection of...

Страница 25: ...l Board 24V TERMINAL STRIP CONNECTIONS DIAGNOSTIC LEDS HIGH PRESSURE SWITCH TEST PINS DEFROST TIMING PINS P1 REVERSING VALVE DEFROST THERMOSTAT S6 LOW PRESSURE SWITCH COMPRESSOR DELAY PINS S4 S87 SERV...

Страница 26: ...he compressor delay jumper is removed NOTE The 30 second off cycle is not functional when jumpering the TEST pins Time Delay The defrost control includes a compressor timer which ensures the compresso...

Страница 27: ...ance normally consists of changing or cleaning the filters and cleaning the evaporator coil On occasion other components may also require cleaning Filters Filters are not supplied with the unit Inspec...

Страница 28: ...49 150 36 132 134 136 137 138 139 140 142 144 145 147 148 48 136 138 140 142 143 144 145 147 148 149 150 151 60 134 135 137 138 139 140 141 142 144 145 147 148 24 Liquid 237 257 278 298 306 320 343 36...

Страница 29: ...36 26 33 40 50 54 61 68 75 83 95 103 117 131 48 28 36 43 53 57 65 72 79 89 102 107 116 125 60 31 39 46 56 60 68 75 82 89 99 106 117 128 24 Liquid 264 271 279 289 294 301 309 316 324 335 340 348 357 36...

Страница 30: ...Page 30 Wiring Diagram LRP16HP Figure 14 HP Wiring Diagram...

Отзывы: