to the mains. Check all joints for leaks with soapy 

solution or other material suitable for the purpose. 

• 

The furnace and its field supplied manual shutoff valve 

must be disconnected from the gas supply piping 

system during any pressure testing of that system at 

test pressures in excess of 1/2 PSIG (3.48kPa).

•  A 1/8” N.P.T. plugged tapping, accessible for test 

gauge connections, must be installed immediately 

upstream of the gas supply connection to the furnace.

Gas Connection

The gas supply line is routed through the gas entry 

location on the side of the unit (see Figure 4). A grommet is 

provided in the instruction bag and should be used to seal 

gas supply line to gas entry of control compartment.

Thermostat

Wire Entry

High Voltage

Power Entry

Gas Entry

Figure 4. 

The furnace must be isolated from the gas supply piping 

system by closing the field supplied manual shutoff valve 

during any pressure testing of gas supply piping system 

at test pressures equal to or less than 1/2 psig or 14” 

w.c. If the piping system is to be tested at pressures in 

excess of 1/2 psig, the furnace and its individual shutoff 

valve must be disconnected from the gas supply piping 

system.

WARNING

NOTE: 

LP/Propane Units, Tanks, and Piping are shipped 

equipped for use with natural gas, but can be converted to 

LP/propane in the field by an approved licensed technician. 

If conversion is required, use the approved conversion kit.

When converting a low NOx unit (designated by an L in 

some model numbers) to propane, the NOx inserts must 

be removed. 

All LP/propane gas equipment must conform to the safety 

standards of the National Fire Protection Association.

Electrical Wiring

See Figure 5 and Figure 6

All wiring should be done in accordance with the National 

Electrical Code, ANSI/NFPA No. 70 (latest edition); 

Canadian Electrical Code Part 1, CSA C22.1 (latest 

edition); or local codes where they prevail. Use wiring with 

a temperature limitation of 75°C minimum. Run the 208 or 

230 volt, 60 hertz electric power supply through a fused 

disconnect switch to the control box of the unit and connect 

as shown in the wiring diagram located on the inside of the 

control access panel.

Power supply to the unit must be N.E.C. Class 1, and must 

comply with all applicable codes. A fused disconnect switch 

should be field provided for the unit. The switch must be 

separate from all other circuits. If any of the wire supplied 

with the unit must be replaced, replacement wire must be 

of the type shown on the wiring diagram. Electrical wiring 

must be sized to carry minimum circuit ampacity marked 

on the unit. 

For satisfactory operation, LP/propane gas pressure must 

be a minimum of 11” w.c. at the unit under full load.

Complete information regarding tank sizing for 

vaporization, recommended regulator settings, and pipe 

sizing is available from most regulator manufacturers and 

LP/propane gas suppliers.

Check all connections for leaks when piping is completed, 

using a soapy, non-chlorine based solution. 

Some soaps 

used for leak detection are corrosive to certain metals. 

Carefully rinse piping thoroughly after completing 

leak detection.

NOTE: 

An optional bottom-entry gas kit is available for 

these units. See the kit instructions for proper installation 

details.

Danger of explosion. 

Can cause injury or product or property 

damage. Do not use matches, candles, flame 

or other sources of ignition to check for leaks.

WARNING

If  a  flexible  gas  connector  is  required  or  allowed  by 

the authority that has jurisdiction, black iron pipe shall 

be installed at the gas valve and must extend outside 

the cabinet. The flexible connector can then be added 

between the black iron pipe and the gas supply line.

CAUTION

Содержание LRP16GE Series

Страница 1: ...stries Inc Dallas Texas USA THIS MANUAL MUST BE LEFT FOR FUTURE REFERENCE WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss o...

Страница 2: ...17 07 13 44 13 44 14 32 16 06 6 20 40 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS 11 49 2 33 47 66 1 98 16 77 2 48 14 02 47 66 POWER ENT...

Страница 3: ...AGE ENTRY 7 8 DIA KNOCKOUT GAS SUPPLY 44 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS TOP VIEW POWER ENTRY GAS ENTRY RETURN AIR 2 11 19 49...

Страница 4: ...44 3 8 1127 44 3 8 1127 16 7 8 429 13 7 8 352 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 4 19 1 25 5 1 2 140 5 3 4 146 11 1 2 287 17 1 4 438 1 3 8 35 3 3 4 95 13 3...

Страница 5: ...13 in 76 x 330 mm 52 7 8 1343 44 3 8 1127 19 1 2 380 11 1 2 287 19 1 2 380 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 3 4 95 22 7 8 581 7 178 3 4 19 1 25 NOTE If bo...

Страница 6: ...8 203 SIDES AND BACK FLANGE 6 152 UNIT BASE RAIL CLIPS 4 NOTE Minimum Height 4 102 UNIT BASE RAIL CLIPS 4 Usage A B C in mm in mm in mm 24 36 42 7 8 1089 13 7 8 352 16 7 8 429 48 60 51 3 8 1305 19 1 2...

Страница 7: ...nits are not suitable for use with conventional venting systems Inspection As soon as the unit is received it should be inspected for possible damage during transit If damage is evident the extent of...

Страница 8: ...s may be installed on combustible floors Units must be installed outdoors Clearance to combustibles below the unit flue is 10 inches since the flue points down Do not permit overhanging structures or...

Страница 9: ...truction bag see Figure 2 Vent Hood Attach with Screws Figure 2 Installing the Vent Cover Rigging Unit Exercise care when moving the unit Do not remove any packaging until the unit is near the place o...

Страница 10: ...ilter rack kit If an existing gas furnace is being removed from a common venting system when this packaged unit is installed then read and follow the instructions in the Removal of Unit from Common Ve...

Страница 11: ...rating plate Gas Piping Recommendations A drip leg and a ground joint union must be installed in the gas piping A ground joint union is recommended by the manifold valve When required by local codes a...

Страница 12: ...he National Electrical Code ANSI NFPA No 70 latest edition Canadian Electrical Code Part 1 CSA C22 1 latest edition or local codes where they prevail Use wiring with a temperature limitation of 75 C m...

Страница 13: ...d insulated wires 18 AWG should be used to connect the thermostat to the unit Compressor Units are shipped with compressor mountings factory adjusted and ready for operation Do not loosen compressor m...

Страница 14: ...as valve and connecting a water manometer or gauge Under no circumstances should the final manifold pressure vary more than 0 3 w c from the above specified pressures To adjust the regulator turn the...

Страница 15: ...roughout the external static range A particular CFM can be obtained by positioning jumpers COOL HEAT and ADJUST on the blower control The HEAT and COOL jumpers are labeled A B C and D Each of the numb...

Страница 16: ...duce the selected air flow rate by 25 percent when humidity levels are high An LED D1 lights when the blower is operating in the dehumidification mode Cooling System The cooling system is a factory ch...

Страница 17: ...nds of the ignition trial If the flame is established within 10 seconds the control de energizes the spark If flame is not established within 10 seconds the gas valve and spark are de energized and th...

Страница 18: ...need cleaning Sooting of a gas appliance is highly irregular and once cleaned the cause of the sooting must be determined If the heat exchanger should become sooted it can be cleaned as follows 1 Remo...

Страница 19: ...eration Call for heat 2 Flash Two flashes in second with 1 second pause System lockout Failed to detect or sustain flame 3 Flash Three flashes in 1 5 seconds with 1 second pause Pressure switch senses...

Страница 20: ...00 400 1260 1080 900 720 1400 1200 1100 975 630 540 450 360 048 Blower Performance 0 through 0 80 in w g External Static Pressure Range 1980 1760 1540 1320 1350 1200 1100 1000 990 880 770 660 NORM 180...

Страница 21: ...Page 21 Figure 9 Wiring Diagram Single Phase Wiring Diagram LRP16GE...

Страница 22: ...being pulled through the condensate line will prevent positive drainage without a proper trap The condensate drain line must be properly trapped routed to a suitable drain and primed prior to unit com...

Страница 23: ...JUST jumper is labeled Test and Norm The and pin settings are used to add or subtract a percentage of the CFM selected The Test jumper is used to operate the motor in the test mode Figure 12 shows the...

Страница 24: ...e is no demand for heating or cooling the blower control will provide 50 percent of the COOL CFM selected DEHUMIDIFICATION The blower control includes an HUM terminal which provides for connection of...

Страница 25: ...l Board 24V TERMINAL STRIP CONNECTIONS DIAGNOSTIC LEDS HIGH PRESSURE SWITCH TEST PINS DEFROST TIMING PINS P1 REVERSING VALVE DEFROST THERMOSTAT S6 LOW PRESSURE SWITCH COMPRESSOR DELAY PINS S4 S87 SERV...

Страница 26: ...he compressor delay jumper is removed NOTE The 30 second off cycle is not functional when jumpering the TEST pins Time Delay The defrost control includes a compressor timer which ensures the compresso...

Страница 27: ...ance normally consists of changing or cleaning the filters and cleaning the evaporator coil On occasion other components may also require cleaning Filters Filters are not supplied with the unit Inspec...

Страница 28: ...49 150 36 132 134 136 137 138 139 140 142 144 145 147 148 48 136 138 140 142 143 144 145 147 148 149 150 151 60 134 135 137 138 139 140 141 142 144 145 147 148 24 Liquid 237 257 278 298 306 320 343 36...

Страница 29: ...36 26 33 40 50 54 61 68 75 83 95 103 117 131 48 28 36 43 53 57 65 72 79 89 102 107 116 125 60 31 39 46 56 60 68 75 82 89 99 106 117 128 24 Liquid 264 271 279 289 294 301 309 316 324 335 340 348 357 36...

Страница 30: ...Page 30 Wiring Diagram LRP16HP Figure 14 HP Wiring Diagram...

Отзывы: