8
Isolation In Wall Spaces
Side View
Wall
Isolator
Line Set
8 Feet Maximum
Secure Suction Line using isolators every 8 ft. Secure Liquid Line
directly to Suction Line using tape, wire, or other appropriate
method every 8 ft.
8 Feet Maximum
Isolation Through Wall
DO NOT hang line sets from ductwork
Sealant
Insulation
Suction Line
Wall
Ductwork
Isolator
Line Set
Section 7. Refrigerant Line Brazing
7.1 Braze The Refrigerant Lines
STEP 1
- Remove caps or plugs. Use a deburing
tool to debur the pipe ends. Clean both internal and
external surfaces of the tubing using an emery cloth.