4
Min. 20” to
Shrubber y
Av oid Install
Near Bedroom s
Min. 60” Unrestricted
Access Panel
Min. 36”
Unrestricted
2.4 Location Restrictions
Ensure the top discharge area is unrestricted for
at least 60 inches above the unit.
Clearance must be provided in front of the
control box (access panels) and any other side
requiring service.
Do not locate close to bedrooms, operational
sounds may be objectionable.
Min. 20” to
Shrubber y
Position the outdoor unit a minimum of 20 inches from
any wall or surrounding shrubbery to ensure
adequate airflow.
Outdoor unit location must be far enough away
from any structure to prevent excess roof runoff
water from pouring directly on the unit.
Note: It is recommended that these precautions be
taken for units being installed in areas where snow
accumulation
and
prolonged
below-freezing
temperatures occur.
• Units should be elevated 3-12 inches above the pad
or rooftop, depending on local weather. This addi-
tional height will allow drainage of snow and ice
melted durIng defrost cycle prior to its refreezlng.
Ensure that drain holes in unit base pan are not
obstructed, preventing drainage of defrost water.
• If possible, avoid locations that are likely to accu-
mulate snow drifts. if not possible, a snow drift barrier
should be installed around the unit to prevent a
build-up of snow on the sides of the unit.
Min 12"
Snow
barrier
3- 12" Elevation
Snow legs
pad
Cold Climate Considerations (Heat Pump Only)
Min. 36” to
Shrubber
Access Panel