background image

Page 7

Combustion Air Inducer

A combustion air inducer proving switch checks
combustion air inducer operation before allowing power
to the gas controller. The gas controller will not operate if
the inducer is obstructed.

Under normal operating conditions, the combustion air
inducer wheel should be checked and cleaned prior to the
heating season. However, it should be examined
periodically during the heating season to establish an
ideal cleaning schedule.

Clean the combustion air inducer as follows:

1− Turn off the electrical power and the gas supply to the

unit.

2− Disconnect the pressure switch air tubing from the

combustion air inducer port.

3− Remove and retain the screws securing the

combustion air inducer to the flue box. Remove and
retain two screws from the bracket supporting the
vent connector. See figures 5 and 6.

4− Clean the inducer wheel blades with a small brush

and wipe off any dust from the housing. Clean
accumulated dust from the front of the flue box cover.

5− Return the combustion air inducer motor and the vent

connector to their original location and secure with
retained screws. It is recommended that the

combustion air inducer gasket be replaced during
reassembly.

6− Use a small brush to clean the combustion air inlet

louvers on the heat access panel.

Flue Passageway and Flue Box

1− Remove the combustion air inducer assembly as

described in the Combustion Air Inducer subsection.

2− Remove the flue box cover. Clean the flue box with a

wire brush as required.

3− Clean the tubes with a wire brush.

4− Reassemble the unit. The flue box cover gasket and

combustion air inducer gasket should also be
replaced during reassembly.

Service Reminder

Call a qualified service technician if the unit is inoperative.
Before calling, always check the following to be sure
service is required:

1− Be sure electrical disconnect switches are 

ON

.

2− Check room thermostat for proper setting.

3− Replace any blown fuses or reset circuit breakers.

4− Gas valve should be 

ON

.

5− Air filters should not be plugged, limiting air flow.

6− Make sure all access panels are in place.

Repair Parts Listing

When ordering repair parts, include the complete model number and serial number listed on the ETL/C.G.A./CSA rating
plate − e.g. LGA240H2BH1Y.

Gas Heat Section Parts

Heat Exchanger
Combustion Air Assembly
Combustion Air Proving Switch
Burner Assembly
Burner Manifold Assembly
Main Burner Orifices
Flame Roll−out Switches
Auxiliary Limit Controls
Ignition Electrode Assembly
Ignition Lead
Ignition Sensor Assembly
Sensor Lead
Combination Gas Valve
Limit Controls

Cooling Parts

Compressors
Low Pressure Switch
High Pressure Switch
Condenser Fan Motors
Condenser Fan Blades
Condenser Fan Run Capacitors
Freezestats
Low Ambient Pressure Switch
Low Ambient Thermostat
Condenser Fan Mounting Bracket
Fan Grille
Indoor Blower Motors
Blower Wheel
Expansion Valve 
Distributor
Crankcase Heaters
Exhaust Fans (Opt.)

Electrical Control Parts

Main Control Panel
Economizer Control Panel (Opt.)
Compressor 2 Control Panel
Compressor 3 and 4 Control Panel
Gas 2 Control Panel
Compressor Contactors
Circuit Breakers (Opt.)
Transformer (Control)
Transformer (Contactor)
Transformer (CAB)
Blower Contactor
Limit, Blower Relay
Heat Relays
Condenser Fan Relays
Capacitor CAB
Relay CAB
Low Ambient Relay
Low Amb. Low Pressure Switches
Disconnect Switch (Opt.)
Blower Motor Overload Relay

Содержание LGA042

Страница 1: ...ice must be per formed by a qualified installer ser vice agency or the gas supplier D Do not try to light any appliance D Do not touch any electrical switch do not use any phone in your building D Imm...

Страница 2: ...S DISCONNECT OPTIONAL ECONOMIZER OPTIONAL 120V GFCI OUTLET OPTIONAL LGA LGC090 102 120 and 150 Parts Arrangement COMBUSTION AIR INDUCER 120V GFCI OUTLET Factory installed option BLOWER MOTOR CONDENSER...

Страница 3: ...UBES BLOWERS CONDENSATE DRAIN FILTERS ECONOMIZER DAMPERS OPTIONAL CONTROL BOX 120V GFCI OUTLET Factory installed option DISCONNECT Factory installed option LGA LGC248 300H and 360 Parts Arrangement CO...

Страница 4: ...errors can cause improper and dangerous operation Verify proper operation after servicing WARNING Danger of electrical shock explosion and fire Improper servicing could result in dangerous operation...

Страница 5: ...HONEYWELL VR8205Q VR8305Q SERIES GAS VALVE Gas valve knob is shown in OFF position FIGURE 4 LOW FIRE ADJUSTMENT HIGH FIRE ADJUSTMENT INLET PRESSURE TAP MANIFOLD PRESSURE TAP 6 Wait five 5 minutes to c...

Страница 6: ...n using the inspection port provided on the burner access panel Flue Passage and Vent Inspection Annually before heating season inspect the combustion air louvers vent cap heat exchanger burners and c...

Страница 7: ...bearings so that a bead of grease appears at the seal lip contacts Manifold Pressures Manifold pressures are shown in table 2 Refer to figures 2 3 and 4 to locate pressure ports TABLE 2 MANIFOLD PRESS...

Страница 8: ...and combustion air inducer gasket should also be replaced during reassembly Service Reminder Call a qualified service technician if the unit is inoperative Before calling always check the following t...

Отзывы: