Page 19
BL
OWE
R DA
TA
1.
5 H
P
BLOWER T
ABLE INCLUDES RESIST
ANCE FOR BASE UNIT ONL
Y WITH DR
Y INDOOR COIL
AND
AIR FIL
TERS IN PLACE.
FOR
ALL
UNITS ADD:
1 -
Any factory installed options air resistance (heat section, economizer
, etc.).
2 -
Any field installed accessories air resistance (duct resistance, diffuser
, etc.).
Minimum
Air V
olume Required For Different Gas Heat Sizes:
Standard Heat - 1075 cfm; Medium Heat - 1
150 cfm; High Heat - 1500 cfm
See page 20 for wet coil and options/accessory air resistance data.
HORIZONT
AL
Total
Air
cfm
Total Static Pressure - in. w
.g.
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
RPM
W
atts
RPM
W
atts
RPM
W
atts
RPM
W
atts
RPM
W
atts
RPM
W
atts
RPM
W
atts
RPM
W
atts
RPM
W
atts
RPM
W
atts
RPM
W
atts
RPM
W
atts
RPM
W
atts
400
708
16
793
37
872
53
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
600
835
46
918
65
1000
82
1077
95
1149
107
1221
109
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
800
981
75
1064
92
1144
109
1221
124
1294
139
1365
148
1434
154
1497
163
1555
179
1607
200
1656
226
1704
254
- - -
- - -
1000
1166
105
1241
124
1315
141
1387
159
1454
176
1520
191
1582
207
1638
227
1689
252
1737
279
1783
308
1829
335
1873
362
1200
1374
142
1440
162
1506
182
1569
203
1630
224
1687
246
1739
271
1787
299
1832
330
1876
361
1920
391
1964
419
2007
444
1400
1591
183
1647
209
1701
235
1755
263
1806
291
1854
320
1899
351
1942
382
1984
412
2026
442
2068
469
21
10
496
2153
520
1600
1778
258
1827
290
1876
323
1923
355
1970
386
2015
416
2059
444
2102
470
2144
494
2185
519
2227
545
2268
572
2309
600
1800
1973
352
2018
383
2063
415
2107
445
2151
476
2194
504
2237
531
2279
557
2319
584
2359
613
2397
645
2435
679
2471
713
2000
2182
437
2224
468
2265
499
2306
531
2346
563
2385
596
2424
630
2461
666
2496
705
2530
745
2564
786
2598
826
2631
866
2200
2388
540
2426
576
2464
613
2500
651
2536
691
2571
731
2605
774
2637
819
2668
863
2700
907
2732
949
2764
990
2795
1029
2400
2589
679
2624
719
2658
761
2691
803
2724
846
2756
890
2786
935
2816
980
2846
1025
2876
1068
2907
1109
2937
1149
2967
1188
2600
2787
845
2819
887
2850
930
2881
973
291
1
1017
2941
1060
2970
1104
2999
1147
3028
1189
3057
1230
3087
1270
- - -
- - -
- - -
- - -
2800
2983
1021
3013
1063
3042
1106
3070
1149
3099
1191
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
Total
Air cfm
Total Static Pressure - in. w
.g.
1.4
1.5
1.6
1.7
1.8
1.9
2.0
RPM
W
atts
RPM
W
atts
RPM
W
atts
RPM
W
atts
RPM
W
atts
RPM
W
atts
RPM
W
atts
800
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
1000
1916
386
1957
408
1998
428
2037
447
2077
465
- - -
- - -
- - -
- - -
1200
2049
468
2089
490
2128
510
2168
529
2207
549
2246
569
2285
591
1400
2194
543
2235
565
2274
588
2313
611
2350
637
2387
664
2423
694
1600
2349
627
2387
657
2423
688
2457
722
2490
757
2522
793
2554
830
1800
2506
749
2539
787
2571
825
2602
864
2632
903
2662
942
2692
981
2000
2663
906
2694
945
2725
985
2755
1024
2785
1063
2815
1101
2845
1138
2200
2826
1068
2857
1107
2887
1146
2916
1184
2946
1221
2975
1259
3005
1296
2400
2997
1227
3027
1266
3056
1304
3085
1342
- - -
- - -
- - -
- - -
- - -
- - -
2600
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
2800
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -