background image

Page 1

INSTALLATION INSTRUCTIONS FOR LOW AMBIENT CONTROL KIT LB-57113BM (27J00)

USED WITH SINGLE-COMPRESSOR HEAT PUMP UNITS

Litho U.S.A.

502,818M

11/98

Supersedes 3/96

®

E

1998 Lennox Industries Inc.

Dallas, Texas

LOW AMBIENT CONTROL KIT

KITS COMMON TO HEATING

AND COOLING EQUIPMENT

INSTALLATION INSTRUCTIONS

SHIPPING AND PACKING LIST

Package 1 of 1 contains:

 1- Low ambient pressure switch assembly (S11)
 1- 36" (914 mm) length of 1/4" (6.35 mm) copper tube

with flare nuts

 1- Relay
 1- 20ĆFoot length of wire
 4- 20" Lengths of wire
 1- Bag assembly each containing:

8-Wire nuts
2-Saddle valves
4-#10-16 X 5/8" S.D.S.T. screws
1-Schrader depressor tee with seal cap

APPLICATION

The  low  ambient  pressure  switch  (S11)  cycles  the
outdoor fan while allowing compressor operation in the

cooling cycle. This intermittent fan operation results in
a  high  evaporating  temperature  which  allows  the

system to operate without icing the evaporator coil and
losing capacity. This kit is designed for use in ambient

temperatures no lower than 30°F.
Lennox recommends a belly-band style crankcase heater

(P-8-8852, 240v, 45w) be added to compressors which
do not have one. A freezestat (LB-62858CA) should also

be added to any system using a low ambient kit.

NOTE - Do not use this low ambient kit on units with

capillary tube metering devices. Install an expansion

valve metering device if using this kit.

INSTALLATION

A-Pressure Switch Assembly

 1- Disconnect power to unit.
 2- Remove compressor compartment access panel.
 3- Install valve depressor tee discharge line gauge port.
 4- Install pressure switch in compressor compartment

with screws provided. Switch should be installed in a
vertical position higher than mid-point of compressor.

See figure 1.

FIGURE 1

TYPICAL INSTALLATION

S11 LOW AMBIENT

PRESSURE SWITCH

HIGH

PRESSURE

SWITCH

COMPRESSOR

DISCHARGE

LINE

S24 LOSS

OF CHARGE

SWITCH

VALVE

DEPRESSOR

TEE

SHOCK

LOOP

 5- Connect  copper  line  to  low  ambient  pressure

switch and open side of depressor tee (provided).

Provide a shock loop in copper tubing to prevent

breakage  from  vibration.  Tighten  connections.

Depressor  tee  port  with  valve  core  is  used  as

service port. If necessary, valve core can be moved

to other leg of tee.

Содержание LB57113BM

Страница 1: ...ures no lower than 30 F Lennox recommends a belly band style crankcase heater P 8 8852 240v 45w be added to compressors which do not have one A freezestat LB 62858CA should also be added to any system...

Страница 2: ...knob located on the left to set cut in pressure Refer to left set of indicating numbers on face of control See figure 2 2 Rotate the square knob located on the right to set differential indicator to 1...

Страница 3: ...priate wiring diagram in figures 3 through 13 for wiring connections 8 K4 DEFROST RELAY 9 7 5 6 4 2 3 1 9 7 6 4 3 1 S11 LOW AMBIENT PRESSURE SWITCH L1 REVERSING VALVE B4 K58 LOW AMBIENT RELAY FIGURE 3...

Страница 4: ...Page 4 FIGURE 4 TYPICAL SINGLE COMPRESSOR HEAT PUMP UNIT WIRING DIAGRAM S11 LOW AMBIENT CONTROL SWITCHES OUTDOOR FAN DIRECTLY SEE PICTORIAL FIGURE 3...

Страница 5: ...1 9 7 6 4 3 1 L1 REVERSING VALVE K10 CONDENSER FAN CONTACTOR TO 24V COM K45 REVERSING VALVE RELAY HP17 953 1353 TWO SPEED S11 LOW AMBIENT PRESSURE CONTROL SWITCHES OUTDOOR FAN S THROUGH A RELAY OR CO...

Страница 6: ...Page 6 FIGURE 6 TYPICAL SINGLE COMPRESSOR HEAT PUMP UNIT WIRING DIAGRAM S11 LOW AMBIENT CONTROL SWITCHES OUTDOOR FAN THROUGH A RELAY OR CONTACTOR PILOT CIRCUIT SEE PICTORIAL FIGURE 5...

Страница 7: ...T3 B4 OUTDOOR FAN MOTOR 1 P35 J35 12 13 12 13 L1 REVERSING VALVE S11 LOW AMBIENT PRESSURE SWITCH COMP 1 FIELD WIRING FACTORY WIRING C1 CAPACITOR REMOVE THIS WIRE 4 1 FIGURE 8 TYPICAL SINGLE COMPRESSO...

Страница 8: ...Page 8 TYPICAL SINGLE COMPRESSOR PACKAGED HEAT PUMP UNIT WIRING DIAGRAM S11 LOW AMBIENT CONTROL SWITCHES OUTDOOR FAN DIRECTLY CHP16 2 TO 5 TON UNITS FIGURE 9 SEE PICTORIAL FIGURE 7...

Страница 9: ...L 1 K4 DEFROST RELAY 9 7 5 6 4 3 1 9 7 6 4 3 1 S11 LOW AMBIENT PRESSURE SWITCH L1 REVERSING VALVE B4 K58 LOW AMBIENT RELAY TO 24V COM OUTDOOR FAN MOTOR TO C12 TERMINAL F REMOVE THIS WIRE FIELD WIRING...

Страница 10: ...Page 10 FIGURE 11 SEE PICTORAL FIGURE 10 TYPICAL SINGLE COMPRESSOR TWO STAGE SINGLE PHASE HEAT PUMP UNIT WIRING DIAGRAM S11 Low Ambient Control Switches Outdoor Fan Directly...

Страница 11: ...9 7 6 4 3 1 S11 LOW AMBIENT PRESSURE SWITCH L1 REVERSING VALVE B4 K58 LOW AMBIENT RELAY TO 24V COM OUTDOOR FAN MOTOR REMOVE THIS WIRE FIELD WIRING FACTORY WIRING TO K10 1 TERMINAL 3 2 3 1 THREE PHASE...

Страница 12: ...Page 12 FIGURE 13 SEE PICTORAL FIGURE 12 TYPICAL SINGLE COMPRESSOR TWO STAGE THREE PHASE HEAT PUMP UNIT WIRING DIAGRAM S11 Low Ambient Control Switches Outdoor Fan Directly...

Отзывы: