icomfort
Touch Screen 7−Day Programmable Thermostat
Page 27
Parameter Name:
Increment
Parameter Value Setting
Default
AIR HANDLER
Equipment Name
Air Handler
(Typewriter input screen)
Electric Heating Airflow
nnnn CFM
SEE NOTE −.
NOTE: CFM Default and Values Settings are dependent on the tonnage of the unit
5CFM
Low Cooling Airflow
5CFM
High Cooling Airflow
5CFM
Cooling Airflow Profile
1
1: No Delays,
2: ON: No delays; OFF: 45 sec delay
3: ON: 82%/7.5min; OFF: No delays
4: ON: 50%/30s,82%/7.5min; OFF:50%/30s
Low Heating Airflow
nnnn CFM
SEE NOTE −.
NOTE: CFM Default and Values Settings are dependent on the tonnage of the unit
5CFM
High Heating Airflow
5CFM
Continuous Indoor Blower Airflow
10CFM
Humidification Airflow
10CFM
Dehumidification Airflow
70%
60 to 80% (percentage of reduction of High Cooling Airflow)
1%
Heating Indoor Blower OFF Delay
10 sec
0 to 10 Seconds
1 sec
Heating Indoor Blower ON Delay
0 sec
0 to 5 Seconds
1 sec
Cooling Indoor Blower OFF Delay
0 sec
0 to 30 Seconds
2 sec
Cooling Indoor Blower ON Delay
2 sec
0 to 10 Seconds
1 sec
HP Indoor Blower OFF Delay
45 sec
0 to 60 Seconds
5 sec
HP Indoor Blower ON Delay
0 sec
0 to 30 Seconds
5 sec
THERMOSTAT
Equipment Name
(Typewriter input screen)
Temp Reading Calibration
0ºF
−5ºF to 5ºF
1ºF
Humidity Reading Calibration
0%
−10 to 10%
1%RH
OUTDOOR EQUIPMENT
Equipment Name (HP and AC)
Outdoor Unit
(Typewriter input screen = up to 35 characters in string)
Compressor Short Cycle Delay (HP and AC)
300 Seconds
60 to 300 Seconds
60 Sec
Compressor Shift Delay On/Off (HP only)
On
On, Off
Defrost Termination Temp (HP only)
50ºF
50 to 100ºF
10ºF