![Lennox HSXA19 SERIES Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/lennox/hsxa19-series/hsxa19-series_installation-instructions-manual_1876910019.webp)
Page 19
Table 6
Normal Operating Pressure
s
(Liquid ±10 and Vapor ±5 psig)
First Stage (Low Capacity)
Outdoor Coil Entering
Air Temp. °F (°C)
−024
−036
−038
−048
−060
Air Temp. F ( C)
Liquid
Vapor
Liquid
Vapor
Liquid
Vapor
Liquid
Vapor
Liquid
Vapor
65 (18.3)
215
144
224
135
215
144
216
138
233
143
75 (23.9)
248
146
258
139
252
146
249
140
270
145
85 (29.4)
288
148
300
143
293
148
288
143
312
147
95 (35.0)
331
150
342
147
337
150
332
145
358
147
105 (40.6)
380
152
395
148
388
154
380
147
407
149
115 (46.1)
432
155
451
149
443
156
430
150
456
150
Second Stage (High Capacity)
Outdoor Coil Entering
Air Temp. °F (°C)
−024
−036
−038
−048
−060
Air Temp. F ( C)
Liquid
Vapor
Liquid
Vapor
Liquid
Vapor
Liquid
Vapor
Liquid
Vapor
65 (18.3)
222
142
233
131
224
133
226
132
251
127
75 (23.9)
258
144
266
134
259
139
261
135
291
135
85 (29.4)
300
146
306
137
299
143
301
137
334
141
95 (35.0)
343
148
361
141
343
146
347
140
375
142
105 (40.6)
394
150
401
142
395
148
395
142
434
146
115 (46.1)
446
153
455
144
448
150
448
145
487
149