background image

Page 10

504953M 03/06

Service Valves

The liquid line and vapor line service valves and gauge
ports are used for leak testing, evacuating, charging and
checking charge. Each valve is equipped with a service
port which has a factory−installed Schrader valve. A ser-
vice port cap protects the Schrader valve from contamina-
tion and serves as the primary leak seal.

Front-Seated Service Valve (Liquid Line)

The front-seated service valve is shown in figure 11. When
this valve is closed, the service port is open to the line set.
Access the service port and open and close valves as de-
scribed in the following paragraphs.

To Access Schrader Port:

1. Remove access panel.

2. Remove service port cap with an adjustable wrench.

3. Connect gauge to the service port.

4. When testing is completed, replace service port cap.

Tighten finger tight; then torque per table 1 (Page 2).

To Open Front-Seated Service Valves:

1. Remove stem cap with an adjustable wrench.

2. Use a service wrench with a hex−head extension

(3/16" for liquid-line valve sizes; 5/16" for vapor-line
valve sizes) to back the stem out counterclockwise as
far as it will go.

3. Replace the stem cap. Tighten finger tight; then torque

per table 1 (Page 2).

To Close Front-Seated Service Valves:

1. Remove the stem cap with an adjustable wrench.

2. Use a service wrench with a hex−head extension

(3/16" for liquid-line valve sizes; 5/16" for vapor-line
valve sizes) to turn the stem clockwise to seat the
valve. Tighten it firmly.

3. Replace the stem cap. Tighten finger tight; then torque

per table 1 (Page 2).

Vapor Line Ball Valve

Ball-type service valves (see figure 12) function the same
way as the other valves but cannot be rebuilt; if one fails,
replace with a new valve. The ball valve is equipped with a
service port with a factory−installed Schrader valve. A ser-
vice port cap protects the Schrader valve from contamina-
tion and assures a leak−free seal.

Front-Seated Liquid Line Service Valve

SERVICE
PORT

(Valve Shown Open)

insert hex wrench here

To outdoor coil

STEM

CAP

Service port Is open to
line set when valve is
closed (front seated)

Figure 11

To 
indoor coil

To outdoor coil

STEM

CAP

(Valve Shown Closed)

Insert hex wrench here

CAP

To 
indoor coil

SERVICE
PORT

CAP

SERVICE PORT

BALL (SHOWN
CLOSED)

STEM
CAP

SCHRADER VALVE

SERVICE
PORT CAP

TO
INDOOR
COIL

TO
OUTDOOR
COIL

STEM

USE ADJUSTABLE WRENCH

TO OPEN:  ROTATE STEM
COUNTER-CLOCKWISE 90°.
TO CLOSE:  ROTATE STEM
CLOCKWISE 90°.

Ball−Type Vapor Valve (Valve Closed)

Figure 12

Содержание HSXA16 Series

Страница 1: ...IONS HSXA16 Series Units CONDENSING UNITS 504 953M 07 06 Supersedes 03 06 Table of Contents HSXA16 Outdoor Unit 1 Shipping Packing List 1 General Information 2 Unit Dimensions 2 Setting The Unit 3 Ele...

Страница 2: ...tallation main tenance or repair will expose you to fiberglass wool dust Breathing this may cause lung cancer Fiber glass wool is known to the State of California to cause cancer Fiberglass wool may a...

Страница 3: ...lectrical WARNING Electric Shock Hazard Can cause injury or death Unit must be grounded in accordance with national and local codes Line voltage is present at all compo nents when unit is not in opera...

Страница 4: ...de wall or where it can be affected by sunlight drafts or vibrations 4 Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit NOTE For proper voltages select thermos...

Страница 5: ...SXA16 Matched with New Indoor Coil and Line Set If an existing indoor coil that was equipped with an RFCI metering device is being replaced the liquid line must also be replaced prior to the installat...

Страница 6: ...eavy nylon wire ties Figure 6 8 feet 8 feet Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line FLOOR JOIST OR ROOF RAFTER Refrigerant Line Sets...

Страница 7: ...ends The pipe must remain round do not pinch end of the line 2 Before making line set connections use dry nitrogen to purge the refrigerant piping This will help to prevent oxidation and the introduc...

Страница 8: ...system per the in structions below will void the warranty IMPORTANT The Environmental Protection Agency EPA pro hibits the intentional venting of HFC refrigerants during maintenance service repair and...

Страница 9: ...d start the recovery machine Open the gauge set valves to allow the recovery machine to pull a vacuum on the ex isting system line set and indoor coil 6 Invert the cylinder of clean HCFC 22 and open i...

Страница 10: ...the stem cap Tighten finger tight then torque per table 1 Page 2 To Close Front Seated Service Valves 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension 3...

Страница 11: ...s been add ed fordetection refrigerantrequirements willvarywith line lengths Checkalljoints for leaks Purge drynitro gen and HFC 410A mixture Correct any leaks and re check IMPORTANT Leak detector mus...

Страница 12: ...d with a dip tube This system is charged with HFC 410A refrigerant which operates at much higher pressures than HCFC 22 This unit is NOT approved for use with coils which include me tering orifices or...

Страница 13: ...d A tem perature pressure chart for HFC 410A refrigerant is provided in table 5 for your convenience Verify ad justed charge using the approach method 4 Use the same digital thermometer you used to ch...

Страница 14: ...ervice port and the unit operating stably use a digital ther mometer to record the liquid line temperature 2 At the same time record the liquid line pressure reading 3 Use the temperature pressure cha...

Страница 15: ...insufficient cooling the unit should be gauged and refrigerant charge checked Re fer to section on refrigerant charging in this instruction NOTE Outdoor fan motor is prelubricated and sealed No furthe...

Страница 16: ...ntinuous in door blower operation regardless of whether the com pressor or furnace is operating This mode is required when constant air circulation or filtering is desired System Switch Set the system...

Отзывы: