Page 2

504953M 03/06

Unit Dimensions − inches (mm)

ELECTRICAL

INLETS

SUCTION

LINE INLET

LIQUID
LINE INLET

COMPRESSOR

B

TOP VIEW

SIDE VIEW

ACCESS VIEW

4-1/2
(114)

2-3/4 (70)

6-1/16

(154)

1-3/8

(35)

A

4

(102)

2-9/16
(65)

INLET AIR

3-1/8

(79)

3-1/8

(79)

3-1/8

(79)

32-1/8 (816)

34-1/16 (865)

26-5/8

(676)

18-5/8

(473)

27-5/8

(702)

2-1/4

(57)

2-1/4

(57)

9-1/8
(232)

9-1/8
(232)

INLET
AIR

INLET AIR

DISCHARGE AIR

4

(102)

CONTACTOR

RUN CAPACITOR

START CAPACITOR

(MODEL −024)

DISCHARGE LINE

COMPRESSOR

TERMINAL PLUG

TWO−STAGE

COMPRESSOR

VAPOR LINE

LOW PRESSURE

SWITCH

HIGH PRESSURE

SWITCH

VAPOR VALVE AND GAUGE PORT

FILTER DRIER

 Parts Arrangement

Model No.

Dim. A

Dim. B

−024, −036

30−7/8 (785)

32−1/8 (816)

−048

34−7/8 (886)

13−3/4 (349)

−060

44−7/8 (1140)

19−3/4 (502)

WARNING

This product and/or the indoor unit it is matched
with may contain fiberglass wool.
Disturbing the insulation during installation, main-
tenance, or repair will expose you to fiberglass wool
dust. Breathing this may cause lung cancer. (Fiber-
glass wool is known to the State of California to
cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact
your supervisor.

Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379−9900

General Information

These instructions are intended as a general guide and do
not supersede national or local codes in any way. Consult
authorities having jurisdiction before installation.

When servicing or repairing HVAC components, ensure
caps and fasteners are appropriately tightened. Table 1
lists torque values for typical service/repair items.

Table 1

Torque Requirements

Part

Recommended Torque

Service valve cap

8 ft.− lb.

11 NM

Gauge port seal cap

8 ft.− lb.

11 NM

Sheet metal screws

16 in.− lb.

2 NM

Machine screws #10

28 in.− lb.

3 NM

Compressor bolts

90 in.− lb.

10 NM

Содержание HSXA16 Series

Страница 1: ...IONS HSXA16 Series Units CONDENSING UNITS 504 953M 07 06 Supersedes 03 06 Table of Contents HSXA16 Outdoor Unit 1 Shipping Packing List 1 General Information 2 Unit Dimensions 2 Setting The Unit 3 Ele...

Страница 2: ...tallation main tenance or repair will expose you to fiberglass wool dust Breathing this may cause lung cancer Fiber glass wool is known to the State of California to cause cancer Fiberglass wool may a...

Страница 3: ...lectrical WARNING Electric Shock Hazard Can cause injury or death Unit must be grounded in accordance with national and local codes Line voltage is present at all compo nents when unit is not in opera...

Страница 4: ...de wall or where it can be affected by sunlight drafts or vibrations 4 Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit NOTE For proper voltages select thermos...

Страница 5: ...SXA16 Matched with New Indoor Coil and Line Set If an existing indoor coil that was equipped with an RFCI metering device is being replaced the liquid line must also be replaced prior to the installat...

Страница 6: ...eavy nylon wire ties Figure 6 8 feet 8 feet Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line FLOOR JOIST OR ROOF RAFTER Refrigerant Line Sets...

Страница 7: ...ends The pipe must remain round do not pinch end of the line 2 Before making line set connections use dry nitrogen to purge the refrigerant piping This will help to prevent oxidation and the introduc...

Страница 8: ...system per the in structions below will void the warranty IMPORTANT The Environmental Protection Agency EPA pro hibits the intentional venting of HFC refrigerants during maintenance service repair and...

Страница 9: ...d start the recovery machine Open the gauge set valves to allow the recovery machine to pull a vacuum on the ex isting system line set and indoor coil 6 Invert the cylinder of clean HCFC 22 and open i...

Страница 10: ...the stem cap Tighten finger tight then torque per table 1 Page 2 To Close Front Seated Service Valves 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension 3...

Страница 11: ...s been add ed fordetection refrigerantrequirements willvarywith line lengths Checkalljoints for leaks Purge drynitro gen and HFC 410A mixture Correct any leaks and re check IMPORTANT Leak detector mus...

Страница 12: ...d with a dip tube This system is charged with HFC 410A refrigerant which operates at much higher pressures than HCFC 22 This unit is NOT approved for use with coils which include me tering orifices or...

Страница 13: ...d A tem perature pressure chart for HFC 410A refrigerant is provided in table 5 for your convenience Verify ad justed charge using the approach method 4 Use the same digital thermometer you used to ch...

Страница 14: ...ervice port and the unit operating stably use a digital ther mometer to record the liquid line temperature 2 At the same time record the liquid line pressure reading 3 Use the temperature pressure cha...

Страница 15: ...insufficient cooling the unit should be gauged and refrigerant charge checked Re fer to section on refrigerant charging in this instruction NOTE Outdoor fan motor is prelubricated and sealed No furthe...

Страница 16: ...ntinuous in door blower operation regardless of whether the com pressor or furnace is operating This mode is required when constant air circulation or filtering is desired System Switch Set the system...

Отзывы: