background image

Page 11

NOTE − Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.

 3 − Replace the stem cap. Tighten finger tight, then tighten

an additional 1/6 turn.

To Close Service Valve:

 1 − Remove stem cap with an adjustable wrench.

 2 − Use a service wrench with a hex−head extension to turn

the stem clockwise to seat the valve. Tighten firmly.

NOTE − Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.

 3 − Replace the stem cap. Tighten finger tight, then tighten

an additional 1/6 turn.

Vapor Line (Ball Type) Service Valve

Vapor line service valves function the same way as the oth-
er valves, the difference is in the construction. These
valves are not rebuildable. If a valve has failed, you must
replace it. A ball valve is illustrated in figure 12.

The ball valve is equipped with a service port with a factory−
installed Schrader valve. A service port cap protects the
Schrader valve from contamination and assures a leak−
free seal.

Service Valve

(Valve Closed)

Schrader valve open

to line set when valve is

closed (front seated)

service

port

service

port cap

stem cap

insert hex

wrench here

(valve front seated)

to outdoor coil

to indoor coil

Service Valve

(Valve Open)

Schrader

valve

service

port

service port

cap

insert hex

wrench here

to indoor coil

to outdoor coil

stem cap

Figure 11

Vapor Line (Ball Type) Service Valve 

(Valve Open)

Schrader

valve

stem cap

To open:  rotate stem counter-clockwise 90

To close:  use adjustable wrench and

rotate stem clockwise 90

.

ball

(shown open)

service port

cap

service

port

field side

unit side

stem

Figure 12

Leak Testing

After the line set has been connected to the indoor and

outdoor units, the line set connections and indoor unit

must be checked for leaks.

 

WARNING

Danger of fire. Bleeding the refrigerant
charge from only the high side may
result in the low side shell and suc-
tion tubing being pressurized. App-
plication of a brazing torch while pres-
surized may result in ignition of the
refrigerant and oil mixture − check the
high and low pressures before unbra-
zing.

WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.

Failure to follow this warning may result in person-
al injury or death.

 

WARNING

Danger of explosion:  Can cause
equipment damage, injury or death.
Never use oxygen to pressurize a re-
frigeration or air conditioning system.
Oxygen will explode on contact with
oil and could cause personal injury.

Содержание HS27 Series

Страница 1: ...4 669M 02 04 Supersedes 12 02 Table of Contents HS27 Outdoor Unit 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Parts Arrangement 3 Setting the Unit 3 Electrical 3 Refrigerant Pipi...

Страница 2: ...View Access View 4 1 2 114 2 3 4 70 4 102 6 1 16 154 1 3 8 35 A 4 7 8 22 4 102 2 9 16 65 18 5 8 473 26 5 8 676 34 1 16 865 2 51 28 1 8 714 7 1 2 191 7 1 2 191 3 7 8 98 3 7 8 98 air inlet air inlet 2 5...

Страница 3: ...o avoid accidental contact with sharp edges Refer to unit dimensions for sizing mounting slab platform s or supports Refer to figure 2 for installation clearances 36 914 mm 36 914 mm 36 914 mm 36 914...

Страница 4: ...structions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size WARNING Unit must be grounded in accordance with...

Страница 5: ...R W Y G C Thermostat Furnace Outdoor Unit Y1 Outdoor Unit C Outdoor Unit power heat cooling indoor blower common NOTE see unit wiring diagram for power supply connections NOTE If the indoor unit is no...

Страница 6: ...ing Refrigerant Line During the installation of any heat pump or a c system it is important to properly isolate the refrigerant lines to prevent unnecessary vibration Line set contact with the structu...

Страница 7: ...id Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve W...

Страница 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Страница 9: ...ne Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 8 Outsid...

Страница 10: ...ps If you install an expansion valve with an indoor coil that includes a fixed orifice remove the orifice before instal ling the expansion valve IMPORTANT Failure to remove RFC orifice when installing...

Страница 11: ...t hex wrench here valve front seated to outdoor coil to indoor coil Service Valve Valve Open Schrader valve service port service port cap insert hex wrench here to indoor coil to outdoor coil stem cap...

Страница 12: ...ollows low pressure gauge to vapor line service valve high pressure gauge to liquid line service valve 2 Connect micron gauge 3 Connect the vacuum pump with vacuum gauge to the center port of the mani...

Страница 13: ...or unit should be charged during warm weather However applications arise in which charging must occur in the colder months The method of charging is deter mined by the unit s refrigerant metering devi...

Страница 14: ...tdoor ambient temperature to check the liquid line temperature 5 The difference between the ambient and liquid temper atures should match values given in table 4 If the val ues don t agree with the th...

Страница 15: ...shed with a water hose Ensure the power is turned off before you clean the coil 2 The outdoor fan motor is prelubricated and sealed No further lubrication is needed 3 Visually inspect connecting lines...

Страница 16: ...oor Fan Checked Job No City City Serial No Date State State Service Technician Compressor Outdoor Fan Indoor Filter Clean Electrical Connections Tight Supply Voltage Unit Off Vapor Pressure Thermostat...

Отзывы: