Page 15

System Operation

The outdoor unit and indoor blower cycle on demand from
the room thermostat. When the thermostat blower switch is
in the 

ON

 position, the indoor blower operates continuously.

CAUTION

Danger of equipment damage. Do not bypass the dis-
charge thermostat.

High Pressure Switch

HS27 units are equipped with a high pressure switch that is
located in the discharge line of the compressor. The switch
(SPST, manual reset, normally closed) removes power
from the compressor when discharge pressure rises above
factory setting at 410 + 10 psi.

Low Pressure Switch

HS27 units are also equipped with a low pressure switch
that is located in the vapor line of the compressor. The
switch (SPST, auto−reset, normally closed) removes power
from the compressor when vapor line pressure drops be-
low factory setting at 25 + 5 psi.

Maintenance

 

WARNING

Electric shock hazard. Can cause inju-
ry or death. Before attempting to per-
form any service or maintenance, turn
the electrical power to unit OFF at dis-
connect switch(es). Unit may have
multiple power supplies.

Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each cooling
season, the system should be checked as follows:
 1 − Clean and inspect the outdoor coil. The coil may be

flushed with a water hose. Ensure the power is turned
off before you clean the coil.

 2 − The outdoor fan motor is prelubricated and sealed. No

further lubrication is needed.

 3 − Visually inspect connecting lines and coils for evidence

of oil leaks.

 4 − Check wiring for loose connections.
 5 − Check for correct voltage at unit (unit operating).
 6 − Check amp−draw outdoor fan motor.

Unit nameplate _________ Actual ____________ .

NOTE − If the owner complains of insufficient cooling,
the unit should be gauged and refrigerant charge
checked. Refer to section on refrigerant charging in
this instruction.

Indoor Coil

 1 − Clean coil, if necessary.
 2 − Check connecting lines and coils for evidence of oil leaks.
 3 − Check the condensate line and clean it if necessary.

Indoor Unit

 1 − Clean or change filters.
 2 − Adjust blower speed for cooling. Measure the pressure

drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.

 3 −

Belt Drive Blowers − 

Check belt for wear and proper

tension.

 4 − Check all wiring for loose connections
 5 − Check for correct voltage at unit (blower operating).
 6 − Check amp−draw on blower motor
Unit nameplate_________ Actual ____________.

Optional Accessories

The following optional accessories are available for use
with outdoor units:

 

 

Loss of Charge Kit

 

 

High Pressure Switch Kit

 

 

Compressor Monitor

 

 

Compressor Crankcase Heater

 

 

Hail Guards

 

 

Mounting Bases

 

 

Timed Off Control

 

 

Stand−off Kit

 

 

Sound Cover

 

 

Low Ambient Kit

Содержание HS27 Series

Страница 1: ...4 669M 02 04 Supersedes 12 02 Table of Contents HS27 Outdoor Unit 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Parts Arrangement 3 Setting the Unit 3 Electrical 3 Refrigerant Pipi...

Страница 2: ...View Access View 4 1 2 114 2 3 4 70 4 102 6 1 16 154 1 3 8 35 A 4 7 8 22 4 102 2 9 16 65 18 5 8 473 26 5 8 676 34 1 16 865 2 51 28 1 8 714 7 1 2 191 7 1 2 191 3 7 8 98 3 7 8 98 air inlet air inlet 2 5...

Страница 3: ...o avoid accidental contact with sharp edges Refer to unit dimensions for sizing mounting slab platform s or supports Refer to figure 2 for installation clearances 36 914 mm 36 914 mm 36 914 mm 36 914...

Страница 4: ...structions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size WARNING Unit must be grounded in accordance with...

Страница 5: ...R W Y G C Thermostat Furnace Outdoor Unit Y1 Outdoor Unit C Outdoor Unit power heat cooling indoor blower common NOTE see unit wiring diagram for power supply connections NOTE If the indoor unit is no...

Страница 6: ...ing Refrigerant Line During the installation of any heat pump or a c system it is important to properly isolate the refrigerant lines to prevent unnecessary vibration Line set contact with the structu...

Страница 7: ...id Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve W...

Страница 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Страница 9: ...ne Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 8 Outsid...

Страница 10: ...ps If you install an expansion valve with an indoor coil that includes a fixed orifice remove the orifice before instal ling the expansion valve IMPORTANT Failure to remove RFC orifice when installing...

Страница 11: ...t hex wrench here valve front seated to outdoor coil to indoor coil Service Valve Valve Open Schrader valve service port service port cap insert hex wrench here to indoor coil to outdoor coil stem cap...

Страница 12: ...ollows low pressure gauge to vapor line service valve high pressure gauge to liquid line service valve 2 Connect micron gauge 3 Connect the vacuum pump with vacuum gauge to the center port of the mani...

Страница 13: ...or unit should be charged during warm weather However applications arise in which charging must occur in the colder months The method of charging is deter mined by the unit s refrigerant metering devi...

Страница 14: ...tdoor ambient temperature to check the liquid line temperature 5 The difference between the ambient and liquid temper atures should match values given in table 4 If the val ues don t agree with the th...

Страница 15: ...shed with a water hose Ensure the power is turned off before you clean the coil 2 The outdoor fan motor is prelubricated and sealed No further lubrication is needed 3 Visually inspect connecting lines...

Страница 16: ...oor Fan Checked Job No City City Serial No Date State State Service Technician Compressor Outdoor Fan Indoor Filter Clean Electrical Connections Tight Supply Voltage Unit Off Vapor Pressure Thermostat...

Отзывы: