background image

Page 8

3−Strike Lockout

The demand defrost system control board includes a
3−strike lockout feature. This internal feature registers
protection circuit interruptions while Y1" (input) is ener-
gized. If any protection circuit switch opens three times
during a single Y1" (input) cycle, the control initiates lock-
out. If the circuit is interrupted once or twice during a single
Y1" (input) cycle, the control resets the strike register to
zero at the end of the cycle.

The 3−strike register can be reset by interrupting 24V
power to the control board or by shorting the TEST"
pins.

TEST Mode

The control board includes a test mode to facilitate ser-
vice. During the test mode, the 14−minute defrost period is
shortened. Initiate the test mode by placing the defrost
temperature selection jumper across the TEST" pins.

Normal test mode operation is described below and in fig-
ure 12:

 

24V power must be applied to the demand defrost con-
trol board BEFORE the jumper is installed on the
TEST" pins.

 

If test pins are shorted before 24V power is applied to
the board, the test mode will be ignored until the short
is removed and reapplied. Each test pin short will result
in one test event.  For each test, the shunt (jumper)
must be removed for at least 1 second then reapplied.

 

If the Y signal is interrupted, the unit will exit the test
mode.

 

LO − PS input is ignored during test mode operation.

 

Test mode operation is limited to 5 minutes. The control
will revert to normal operation and ignore the test mode
after this period of time.

Defrost Temperature Selection Jumper

The control board can be set to terminate defrost at one of
four temperature settings: 70°F, 80°F, 90°F, or 100°F. If the
jumper is removed, the control board will terminate defrost
at the default setting of 100°F.

Communication Port

The demand defrost system control board is equipped
with a communication port. This port has been included for
future use and is not functional at this time.

IMPORTANT

Do not connect an electronic device to the commu-
nication port. Incompatibility between the control
board and the device could result in damage to both.

Defrost Operation (Table 5)

The demand defrost control board has three modes of op-
eration: normal, calibration and defrost.

Normal Operation

During normal operation, the control board continuously
monitors the system operation mode (heating / cooling),
the outdoor ambient temperature, the outdoor coil temper-
ature and compressor run time to determine the need for a
defrost cycle.

Calibration Mode

The demand defrost control board is considered uncali-
brated when one of the following conditions applies:  im-
mediately after power has been applied to the control
board, immediately after operation in the cooling mode, or
any time the outdoor coil temperature exceeds the ter-
mination temperature during the heating mode. During the
calibration mode, the demand defrost control board mea-
sures the outdoor coil and outdoor ambient temperatures
to establish an average (calibrated) temperature differen-
tial between the two.

Defrost Mode

The following operation sequence applies when the de-
mand defrost control initiates a defrost cycle:

 1 − The control board energizes the reversing valve and

de−energizes the condenser fan motor.

 2 − The control energizes the W1" (auxiliary heat) circuit.

The unit will operate in this mode until the outdoor coil
temperature rises above the selected termination
temperature, the 14−minute defrost interval has been
completed, or the room temperature rises to satisfy
the heating demand.

NOTE − If the termination temperature selection jump-
er has been left off, the defrost termination tempera-
ture is set at the 100°F default.

 3 − If the defrost cycle is terminated by the room thermo-

stat because the heating demand has been satisfied,
the call for a defrost cycle will be carried over to the
next heating demand cycle. If the outdoor coil temper-
ature is still below the selected termination tempera-
ture when the heating demand is re−initiated, the de-
frost cycle will be continued until it is terminated by
one of the three methods outlined in step 2.

 4 − If the defrost cycle is terminated by the 14−minute de-

frost interval and the outdoor coil has not remained
above 35

°

F (2

°

C) for 4 minutes, the control will initiate

a 34−minute time/temperature defrost mode.

Ambient Thermistor & Service Light Connection

The defrost control board provides terminal connections
for the ambient thermistor and a service light. The thermis-
tor compensates for changes in ambient temperature
which might cause thermostat droop. The service light
thermostat provides a signal which activates the room
thermostat service light during periods of inefficient opera-
tion.

Содержание HP27?024

Страница 1: ...22 866 22 866 22 866 22 866 Diameter in mm No of blades 24 610 3 24 610 3 24 610 3 24 610 3 C d Motor hp W 1 10 75 1 10 75 1 10 75 1 10 75 Condenser Fan Cfm L s 2800 1320 2800 1320 2800 1320 2800 132...

Страница 2: ...it is in constant contact with discharge gas FIGURE 2 SCROLL FORM FIGURE 3 STATIONARY SCROLL ORBITING SCROLL DISCHARGE SUCTION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRE...

Страница 3: ...ated in the unit control box for making thermostat wiring connections refer to figure 6 C Compressor Table 1 shows the specifications of compressors B1 used in HP27 series units TABLE 1 Unit Phase LRA...

Страница 4: ...ee wiring diagrams for specific unit The con tactor is energized by indoor thermostat terminal Y when thermostat demand is present DANGER Electric Shock Hazard May cause injury or death Disconnect all...

Страница 5: ...unit control box see figure 6 Table 3 shows the ratings of the dual ca pacitor TABLE 3 HP27 DUAL CAPACITOR RATING UNITS FAN MFD HERM MFD VAC HP27 024 4 40 370 HP27 030 4 40 370 HP27 036 4 45 370 HP27...

Страница 6: ...fety Circuits The defrost control incorporates a safety circuit that allows the application of an additional pressure switch The unit s high pressure switch S4 is factory wired into this circuit See f...

Страница 7: ...continuous line cycles If a system protection switch opens while the Y1 OUT cir cuit is energized the timed off control will initiate a 5 min ute delay when the pressure switch closes The timed off co...

Страница 8: ...ion During normal operation the control board continuously monitors the system operation mode heating cooling the outdoor ambient temperature the outdoor coil temper ature and compressor run time to d...

Страница 9: ...rol board initiates a defrost cycle based on either frost detection or time Frost Detection If the compressor runs longer than 34 minutes and the actual difference between the clear coil and frosted c...

Страница 10: ...en the unit will remain in Heating Mode Remove and reapply test jumper to return to test mode if desired If sensor circuits are closed the unit will go into Defrost Mode Defrost mode ends Unit enters...

Страница 11: ...on will not function again until the jumper is removed and re ap plied Time Delay The timed off delay is five minutes long The delay helps protect the compressor from short cycling in case the pow er...

Страница 12: ...Use Lennox L10 flare or L15 sweat series line sets as shown in table 7 or field fabricated refrigerant lines Refer to the piping section of the Lennox Unit Information Service Manual for proper size...

Страница 13: ...APOR LINE VALVE SUCTION SERVICE PORT TO HCFC 2 2 DRUM HIGH PRESSURE LIMIT THERMOME TER WELL ACCUMULATOR FIGURE 15 NOTE Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant l...

Страница 14: ...LVE VALVE CLOSED VALVE FRONT SEATED FIELD SIDE UNIT SIDE To Access Schrader Port 1 Remove access panel 2 Remove service port cap with an adjustable wrench 3 Connect gauge to the service port 4 When te...

Страница 15: ...uge to center port of gauge manifold With both manifold service valves open start pump and evac uate indoor coil and refrigerant lines IMPORTANT A temperature vacuum gauge mercury vacuum U tube or the...

Страница 16: ...Below 60 F 16 C NOTE It may be necessary to restrict air flow in order to reach liquid pressures in the 200 250 psig range which are required for checking charge Block equal sections of air intake pa...

Страница 17: ...ason the system should be cleaned as follows A Outdoor Unit 1 Clean and inspect outdoor coil Coil may be flushed with a water hose 2 Visually inspect all connecting lines joints and coils for evidence...

Страница 18: ...ELD WIRING DIAGRAM HP27 WITH INDOOR UNIT 1 2 3 THERMOSTAT HEAT ANTICIPATION SET TING 4 AMP ELECTRIC HEAT WHEN TWO STAGE THERMOSTAT IS USED CONNECT SECOND STAGE HEAT BULB TO TER MINAL W2 AND REMOVE JUM...

Страница 19: ...Page 19 C Diagram HP27 1 208 230 Volt 1 2 3 4 5 6 7 8...

Страница 20: ...Page 20 D Diagram HP27 6 208 230 Volt 1 2 3 4 5 6 7 8...

Страница 21: ...Page 21 E Diagram HP27 7 208 230 Volt 1 2 3 4 5 6 7 8...

Страница 22: ...Page 22 F Diagram HP27 7 208 230 Volt 1 2 3 4 5 6 7 8...

Страница 23: ...ODE 9 During heating operation when outdoor coil tempera ture drops below 35 F 2 C or 42 5 5 C see de frost system description for specific unit dash number defrost switch thermostat S6 closes 10 Defr...

Отзывы: