background image

Page 7

M−Defrost System HP27−4 and −6 ONLY

HP27−4 and −6 units are equipped with a demand defrost

system. The self−calibrating defrost control board includes

defrost relays, sensors (two) which monitor coil and out-

door ambient temperatures, a timed−off control, protection

circuits (two), a 3−strike lockout feature, a test mode jump-

er and a terminal strip. The demand defrost control board

initiates a defrost cycle based on temperature differential

and compressor run time. This type of system allows

greater frost accumulation on the outdoor coil and initiates

fewer defrost cycles than the time/temperature defrost

system. The defrost board is shown in figure 10.

Temperature Sensors

The demand defrost control board includes two perma-

nently attached sensors which monitor coil and outdoor

ambient temperatures. The coil temperature sensor is

equipped with a spring clip to allow proper positioning on

the outdoor coil. These sensors must not be detached

from the control board and must be replaced as part of the

control board. Do not attempt to cut or splice the tempera-

ture sensor wires. See figure 11 for ambient and coil tem-

perature sensor location.

Timed−Off Control

The control board includes a 5−minute timed−off delay
which protects the compressor from short cycling. The
5−minute delay is initiated at the end of a compressor
cycle, any time a system protection switch is reset, or if the
Y1 circuit is interrupted for more than two continuous line
cycles.

If a system protection switch opens while the Y1 OUT" cir-
cuit is energized, the timed−off control will initiate a 5−min-
ute delay when the pressure switch closes.

The timed−off control run times can be bypassed by
shorting the TEST" pins.

Protection Circuits

The control board includes two protection circuits.

The unit high pressure switch is factory−wired to the HI −
PS terminals. The circuit through Y1" (input and Y1
OUT") is completed through the high pressure switch.
When the high pressure switch opens, the control board
de−energizes the compressor and the 3−strike lockout
counter registers one strike. 

If, for any reason, the high

pressure switch is removed, a jumper must be applied
across the HI − PS terminals to complete the circuit.

The second protection circuit is not used in this application

A jumper must be applied across the LO − PS terminals
to ensure proper control board operation.

Inputs (24V Terminal Strip Connections)

Y1

Thermostat input, controls unit operation

O

Thermostat input, reversing valve

R

24VAC power

C

24VAC common

W1

24VAC input/output from indoor thermostat to indoor unit

L

Service light  thermostat

T

Ambient sensor (connection for Room Thermostat with
ambient compensation)

(1/4" Quick Connect Terminal Factory Connections)

HI−PS

Pressure switch / system fault sensor

LO−PS

Pressure switch / system fault sensor

Y1 Out

Compressor contactor

O Out

Reversing valve

FAN

Condenser fan

W/L/C

Service light thermostat

T/T

Ambient sensor

Defrost Control Board

FIGURE 10

Y1

O

W1

R

CL

T

W1

C

L

T

FAN

FAN

CC

Y

HI−PS

LO−PS

RV

C

O−OUT

Y1−OUT

LED1

LED2

AMB

COIL

PS2

AUX

PS1

DIS

IND

CUR

70

80

90

100

TEST

PRESS

Содержание HP27?024

Страница 1: ...22 866 22 866 22 866 22 866 Diameter in mm No of blades 24 610 3 24 610 3 24 610 3 24 610 3 C d Motor hp W 1 10 75 1 10 75 1 10 75 1 10 75 Condenser Fan Cfm L s 2800 1320 2800 1320 2800 1320 2800 132...

Страница 2: ...it is in constant contact with discharge gas FIGURE 2 SCROLL FORM FIGURE 3 STATIONARY SCROLL ORBITING SCROLL DISCHARGE SUCTION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRE...

Страница 3: ...ated in the unit control box for making thermostat wiring connections refer to figure 6 C Compressor Table 1 shows the specifications of compressors B1 used in HP27 series units TABLE 1 Unit Phase LRA...

Страница 4: ...ee wiring diagrams for specific unit The con tactor is energized by indoor thermostat terminal Y when thermostat demand is present DANGER Electric Shock Hazard May cause injury or death Disconnect all...

Страница 5: ...unit control box see figure 6 Table 3 shows the ratings of the dual ca pacitor TABLE 3 HP27 DUAL CAPACITOR RATING UNITS FAN MFD HERM MFD VAC HP27 024 4 40 370 HP27 030 4 40 370 HP27 036 4 45 370 HP27...

Страница 6: ...fety Circuits The defrost control incorporates a safety circuit that allows the application of an additional pressure switch The unit s high pressure switch S4 is factory wired into this circuit See f...

Страница 7: ...continuous line cycles If a system protection switch opens while the Y1 OUT cir cuit is energized the timed off control will initiate a 5 min ute delay when the pressure switch closes The timed off co...

Страница 8: ...ion During normal operation the control board continuously monitors the system operation mode heating cooling the outdoor ambient temperature the outdoor coil temper ature and compressor run time to d...

Страница 9: ...rol board initiates a defrost cycle based on either frost detection or time Frost Detection If the compressor runs longer than 34 minutes and the actual difference between the clear coil and frosted c...

Страница 10: ...en the unit will remain in Heating Mode Remove and reapply test jumper to return to test mode if desired If sensor circuits are closed the unit will go into Defrost Mode Defrost mode ends Unit enters...

Страница 11: ...on will not function again until the jumper is removed and re ap plied Time Delay The timed off delay is five minutes long The delay helps protect the compressor from short cycling in case the pow er...

Страница 12: ...Use Lennox L10 flare or L15 sweat series line sets as shown in table 7 or field fabricated refrigerant lines Refer to the piping section of the Lennox Unit Information Service Manual for proper size...

Страница 13: ...APOR LINE VALVE SUCTION SERVICE PORT TO HCFC 2 2 DRUM HIGH PRESSURE LIMIT THERMOME TER WELL ACCUMULATOR FIGURE 15 NOTE Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant l...

Страница 14: ...LVE VALVE CLOSED VALVE FRONT SEATED FIELD SIDE UNIT SIDE To Access Schrader Port 1 Remove access panel 2 Remove service port cap with an adjustable wrench 3 Connect gauge to the service port 4 When te...

Страница 15: ...uge to center port of gauge manifold With both manifold service valves open start pump and evac uate indoor coil and refrigerant lines IMPORTANT A temperature vacuum gauge mercury vacuum U tube or the...

Страница 16: ...Below 60 F 16 C NOTE It may be necessary to restrict air flow in order to reach liquid pressures in the 200 250 psig range which are required for checking charge Block equal sections of air intake pa...

Страница 17: ...ason the system should be cleaned as follows A Outdoor Unit 1 Clean and inspect outdoor coil Coil may be flushed with a water hose 2 Visually inspect all connecting lines joints and coils for evidence...

Страница 18: ...ELD WIRING DIAGRAM HP27 WITH INDOOR UNIT 1 2 3 THERMOSTAT HEAT ANTICIPATION SET TING 4 AMP ELECTRIC HEAT WHEN TWO STAGE THERMOSTAT IS USED CONNECT SECOND STAGE HEAT BULB TO TER MINAL W2 AND REMOVE JUM...

Страница 19: ...Page 19 C Diagram HP27 1 208 230 Volt 1 2 3 4 5 6 7 8...

Страница 20: ...Page 20 D Diagram HP27 6 208 230 Volt 1 2 3 4 5 6 7 8...

Страница 21: ...Page 21 E Diagram HP27 7 208 230 Volt 1 2 3 4 5 6 7 8...

Страница 22: ...Page 22 F Diagram HP27 7 208 230 Volt 1 2 3 4 5 6 7 8...

Страница 23: ...ODE 9 During heating operation when outdoor coil tempera ture drops below 35 F 2 C or 42 5 5 C see de frost system description for specific unit dash number defrost switch thermostat S6 closes 10 Defr...

Отзывы: