9 – Defrost Control CMC1

The CMC1 defrost control (figure 6) is a solid state control
manufactured by Hamilton Standard. The control
provides automatic switching from normal heating
operation to defrost mode and back. The control
provides 14 minute defrost periods at 30, 60 or 90 minute
field changeable intervals. The control monitors
thermostat demand and “holds” the timer in place
between thermostat demand. A set of diagnostic pins are
also provided for troubleshooting the unit.

The control contains a solid state timer which switches
an external defrost relay through 1/4” male spades
mounted on the control’s circuit board. When the
defrost thermostat closes (call for defrost), the defrost
timer initiates a 30, 60 or 90 minute (depending on how
the control is preset) timing sequence. If the defrost
thermostat remains closed when the timing sequence
ends, the defrost relay is energized and defrost begins.

SOLID STATE DEFROST CONTROL CMC1

Timing
Jumper

Timing Pins

Troubleshooting Pins

Control Terminals

30

60 90

FIGURE 6

A defrost period can last up to 14 minutes and can be
terminated two ways. If the defrost thermostat does
not open within 14 minutes after defrost begins, the
timer will de–energize the defrost relay and the unit
will resume normal operation. If the defrost
thermostat opens during the 14 minute defrost period,
the defrost relay is de–energized and the unit resumes
normal operation. Refer to figure 7.

ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉÉÉ

ÉÉ

ÉÉ

ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ

ÉÉÉ

ÉÉÉ

ÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉ

ÉÉÉÉ

ÉÉÉÉ

ÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉÉÉÉÉÉ

ÉÉ

ÉÉ

ÉÉ

ÉÉ

ÉÉ

ÉÉ

CLOSED, ON

OPEN, OFF

THERMOSTAT DEMAND

DEFROST THERMOSTAT

DEFROST RELAY

DEFROST THERMOSTAT

DEFROST RELAY

THERMOSTAT DEMAND

DEFROST THERMOSTAT

DEFROST RELAY

THERMOSTAT DEMAND

DEFROST THERMOSTAT

DEFROST RELAY

HP23 SERIES UNITS TYPICAL DEFROST TIMINGS

NORMAL HEATING OPERATION: DEFROST TERMINATED BY DEFROST THERMOSTAT

NORMAL HEATING OPERATION: DEFROST TERMINATED BY TIME

NORMAL HEATING OPERATION INTERRUPTED BY THERMOSTAT DEMAND: “HOLD” FUNCTION

DEFROST PERIOD INTERRUPTED BY THERMOSTAT DEMAND: “HOLD” FUNCTION

30/60/90 MINUTES

“HOLD” TIME

“HOLD” TIME

14 MIN. PLUS “HOLD” TIME

30/60/90 MINUTES

DEFROST THERMOSTATOPEN WITHIN 14 MINUTES

30/60/90 MINUTES

14 MIN.

30/60/90 MINUTES

30/60/90 MINUTES PLUS “HOLD” TIME

Note – Control begins timing at 0 when defrost thermostat closes. Defrost is terminated when defrost

relay is de–energized. Anytime defrost thermostat opens, defrost relay is immediately de–energized,

defrost timer resets and “HOLD” function stops.

DEFROST THERMOSTAT

MUST REMAIN CLOSED

FOR TIMER TO REMAIN

IN “HOLD”

DEFROST THERMOSTAT

MUST REMAIN CLOSED

FOR TIMER TO REMAIN

IN “HOLD”

FIGURE 7

ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ

THERMOSTAT DEMAND

Содержание HP23 Series

Страница 1: ...ting in the compressor The heater is temperature actuated and operates only when required A crankcase heater for HP23 141 units is optional but suction accumulator is factory installed Several models...

Страница 2: ...lectrical Code manual to determine wire fuse and disconnect size requirements NOTE Extremes of operating range are plus 10 and minus 5 of line voltage ELECTRICAL DATA Model No HP23 413 HP23 461 1 HP23...

Страница 3: ...AN MOTOR CONTROL BOX EXPANSION VALVE FIGURE 2 FAN SPIDER A Control Box Figures 3 and 4 FIGURE 3 DUAL CAPACITOR C12 START CAPACITOR C7 POTENTIAL RELAY K31 COMPRESSOR CONTACTOR K1 HP23 UNIT CONTROL BOX...

Страница 4: ...t Capacitor C7 All single phase units use a start capacitor C7 C7 is located inside the unit control box see figure 3 C7 is wired in parallel with the compressor side of the dual capacitor See table 2...

Страница 5: ...fter defrost begins the timer will de energize the defrost relay and the unit will resume normal operation If the defrost thermostat opens during the 14 minute defrost period the defrost relay is de e...

Страница 6: ...and NOTE Hold function operates between thermostat demands only when defrost thermostat is closed This is the only time that the timer is operating 5 TST Pins Each board is equipped with a set of test...

Страница 7: ...ing parts a rotor shaft eccentric roller and a blade See figure 11 The compressor rotor shaft is attached directly to the compressor motor The rotor shaft is permanently attached to an eccentric The e...

Страница 8: ...t relay ELECTRICAL DATA tables in this manual show specifications for outdoor fans used in HP23s Two different mounting arrangements are used fan up and fan motor up see figures 14 and 15 Access to th...

Страница 9: ...LIZER LINE DRIER WITH CHECK VALVE PRESSURE TAP FITTING WITH VALVE CORE DISTRIBUTOR TO OUTDOOR COIL STRAINER HP23 LIQUID LINE COMPONENTS REFRIGERANT FLOW IN COOLING MODE REFRIGERANT FLOW IN HEATING MOD...

Страница 10: ...is not pressurized The service port cap can be removed and gauge connections can be made CAUTION The service port cap is used to seal the liquid line service valve Access to service port requires back...

Страница 11: ...stem cap tighten firmly Tighten finger tight then tighten an additional 1 6 turn To Close Vapor Line Service Valve 1 Remove stem cap with an adjustable wrench 2 Using service wrench and 5 16 hex head...

Страница 12: ...ULATOR 460 510 AND 650 ONLY DEFROST SWITCH S6 FILTER DRIER W INTERNAL CHECK VALVE MUFFLER LIQUID LINE FROM INDOOR COIL TO OUTDOOR COIL DISCHARGE LINE SERVICE PORT STRAINER LIQUID LINE SERVICE PORT REV...

Страница 13: ...nitrogen pressure from the system correct any leaks and recheck CAUTION When using dry nitrogen a pressure reducing regulator must be used to prevent excessive pressure in gauge manifold connecting ho...

Страница 14: ...Warmer Than Liquid Line HP23 261 HP23 311 HP23 411 413 CAN HP23 461 463 HP23 211 HP23 141 HP23 511 513 HP23 651 653 SUBCOOLING METHOD EXPANSION VALVE SYSTEMS AMBIENT TEMPERATURE BELOW 60 F 16 C 4 2 9...

Страница 15: ...4 13 11 10 7 8 1 12 9 8 6 7 0 6 7 6 4 5 0 4 5 4 2 2 Approved matchups only HP23 410 CB CBH19 41 17 15 14 11 8 5 18 16 15 12 9 6 Condensing Temp F Warmer Than Liquid Line At Various Ambients 5 Place th...

Страница 16: ...Page 16 HP23 SINGLE PHASE OPERATING SEQUENCE 1 2 3 5 6 4 7 8 9 10 11 12 13 15 16 17 18 19 20 21 22 23 24 25 27 26 1 20...

Страница 17: ...K1 1 opens and compressor B1 and outdoor fan motor B4 are de energized and stop im mediately FIRST STAGE HEAT 11 Heating demand initiates at W1 in the ther mostat 12 24VAC energizes compressor contac...

Страница 18: ...Page 18 HP23 THREE PHASE OPERATING SEQUENCE 1 2 3 5 6 4 7 8 9 10 11 12 13 15 14 16 17 18 19 20 21 22 23 24 25 26 1...

Страница 19: ...the ther mostat 11 24VAC energizes compressor contactor K1 12 K1 1 N O closes energizing compressor and outdoor fan motor 13 Compressor B1 and outdoor fan motor B4 begin immediate operation END OF FIR...

Отзывы: