background image

3DJH 

PLUMBING

Field refrigerant piping consists of liquid and vapor

lines from the heat pump (sweat connections) to the

indoor evaporator coil (typically flare connections).

Use Lennox L10 series line sets as shown in table 1 or

use field--fabricated refrigerant lines. Refer to unit in-

formation manual piping section for proper size, type

and application of field--fabricated lines.
If refrigerant tubes are routed through a wall, seal and

isolate the opening so vibration is not transmitted to

the building.
NOTE-Line length should be no greater than 50 feet
(15.2 m). Select line set diameters from table 1 to en-
sure oil return to compressor.

UNIT

LIQUID

LINE

VAPOR

LINE

L10

LINE SETS

HP23--311

HP23--411/413

HP23--461/463

HP23--511/513

3/8 in.

(10mm)

3/4 in.

(19mm)

7/8 in.

(22mm)

HP23--211

HP23--261

5/16 in.

(8mm)

5/8 in.

(16mm)

L10--21

20 ft. -- 50 ft.

(3m -- 15.2m)

TABLE 1

REFRIGERANT LINE SET KITS

1/4 in.

(6mm)

HP23--141

1/2 in.

(12mm)

Field Fabricated

L10--41

20 ft. -- 50 ft.

(6.1m -- 15.2m)

3/8 in.

(10mm)

L10--65

30 ft. -- 50 ft.

(9.1m -- 15.2m)

HP23--651/653

1--1/8 in.

(29mm)

3/8 in.

(10mm)

Field Fabricated

NOTE-To obtain maximum efficiency, remove the
3/4” reduction from the L10-65 series line sets and the
flare fitting from the indoor coil. Then, make a sweat
connection using a 7/8” X 1-1/8” reducer bushing.

Sweat Connection Procedure

1-- End of refrigerant line must be cut square, free

from nicks or dents, deburred. Pipe must remain

round, do not pinch end of line. (I.D. and O.D.)

2-- The thermometer well (packaged separately and at-

tached to the liquid line) should be installed in the

liquid line close to the HP23 unit as shown in figure

5. Connect thermometer well male end to female

end of liquid valve. Take care to install thermometer

well so that the thermometer can be inserted and

read easily. Wrap a wet cloth around the liquid line

valve body and copper tube stub to protect from

heat damage during brazing. Wrap another wet

cloth underneath the liquid valve to protect the base

paint.

FIGURE 5

THERMOMETER WELL

(Field Installed)

PROTECT LIQUID LINE

VALVE WITH WET RAG

DURING BRAZING

THERMOMETER WELL

INSTALL THERMOMETER WELL SO THAT THERMOMETER

CAN BE INSERTED AND READ EASILY

LIQUID

LINE

VALVE

THERMOMETER WELL--MALE

LIQUID LINE--FEMALE

CONNECTION

3-- Quench the joint with water or a wet cloth to pre-

vent possible heat damage to valve core and open-
ing port.

REFRIGERANT METERING DEVICE

+3 XQLWV DUH DSSOLFDEOH WR HLWKHU 5)& RU DQ H[SDQVLRQ
YDOYH V\VWHP 6HH LQGRRU FRLO LQVWDOODWLRQ LQVWUXFWLRQV DQG
WKH /HQQR[ HQJLQHHULQJ KDQGERRN IRU DSSURYHG 5)&
DQG 7;9 PDWFK XSV DQG DSSOLFDWLRQ LQIRUPDWLRQ

RFC Systems

+3 XQLWV DUH VKLSSHG ZLWK HLWKHU DQ 5)& PHWHULQJ GH
YLFH 5)& EXOOHW LV LQVWDOOHG DV VKRZQ LQ ILJXUH  7DNH
FDUH QRW WR WZLVW FDS WXEHV ZKHQ ORRVHQLQJ VHDO QXW IURP
RULILFH ERG\ ,Q FDVHV RI QRQ WUDGLWLRQDO DSSOLFDWLRQV
5)& EXOOHW VKLSSHG PD\ QRW EH DSSURSULDWH 5HIHU WR WKH
LQGRRU FRLO LQVWDOODWLRQ LQVWUXFWLRQV DQG WKH HQJLQHHU
LQJ KDQGERRN IRU VSHFLILF RULILFH LQIRUPDWLRQ

RFC INSTALLATION

DISTRIBUTOR

“BULLET”

ORIFICE

ORIFICE

BODY

SEAL

NUT

FIGURE 6

SWEAT

CONNECTION

Содержание HP23-141

Страница 1: ...HFODLPLQJ PXVW EH IROORZHG LQHV DQG RU LQFDUFHUDWLRQ PD EH OHYLHG IRU QRQ FRP SOLDQFH 167 7 21 16758 7 216 3 6 5 6 81 76 7 3803 81 76 WKURXJK WRQ 0 6XSHUVHGHV 0 7 2 217 176 3 7 3803 81 7 6 33 1 1 3 1...

Страница 2: ...6WDWH 6HUYLFHPDQ PSV 6XSSO 2XWGRRU DQ RPSUHVVRU QGRRU LOWHU OHDQ QGRRU ORZHU 530 OHFWULFDO RQQHFWLRQV 7LJKW 6XSSO 9ROWDJH 8QLW 2II 6 3 URS 2YHU YDSRUDWRU U 2XWGRRU RLO QWHULQJ LU 7HPSHUDWXUH LTXLG 3U...

Страница 3: ...f a support frame is constructed it must not block drain holes in unit base 4 When installed in areas where low ambient tem peratures exist locate unit so winter prevailing winds do not blow directly...

Страница 4: ...rafts or vibra tion Do not install thermostat on an outside wall A position approximately 5 feet 1524 mm from the floor and near the center of the conditioned area is most desirable 5 Route 24VAC cont...

Страница 5: ...ne I D and O D 2 The thermometer well packaged separately and at tached to the liquid line should be installed in the liquid line close to the HP23 unit as shown in figure 5 Connect thermometer well m...

Страница 6: ...NIFOLD GAUGE CONNECTIONS OUTDOOR COIL DEFROST THERMOSTAT EXPANSION VALVE FILTER DRIER WITH INTERNAL CHECK VALVE STRAINER TO R 22 DRUM LOW PRESSURE HIGH PRESSURE COMPRESSOR REVERSING VALVE VAPOR LINE V...

Страница 7: ...nect high pres sure gauge to service port 3 Using service wrench open valve stem one turn clockwise from backseated position 4 When finished using port backseat stem with ser vice wrench Tighten firml...

Страница 8: ...n will explode on con tact with oil and could cause personal injury When using high pressure gas such as nitrogen or CO2 for this purpose be sure to use a regulator that can control the pressure down...

Страница 9: ...ifold gauge valves to release the nitrogen from the line set and indoor unit 7 Reconnect the manifold gauge to the vacuum pump turn the pump on and continue to evacuate the line set and indoor unit un...

Страница 10: ...center manifold hose to an upright bottle of R22 Close manifold gauge set valves 2 Set the room thermostat to call for heat This will create the necessary load for properly charging the system in the...

Страница 11: ...shown refrigerant must be reclaimed If Subcooling is less than shown refrigerant must be added TABLE 4 SUBCOOLING TEMP EF MODEL HP23 211 HP23 410 HP23 460 4 2 HP23 311 HP23 261 HP23 141 HP23 510 HP23...

Страница 12: ...ill not allow a de frost to last for more than 14 minutes The defrost timer can be field adjusted from a 60 minute to a 30 or 90 minute defrost interval if warranted by climatic con ditions Timed Off...

Отзывы: