background image

3DJH 

The Subcooling Method
TXV Systems, < 60EF Outdoor Temp

Because the outdoor ambient temperature is below

60EF, airflow over the outdoor coil will need to be re-

duced to drive up the liquid line pressure to a range of

200 -- 250 psig. To do this block off the outdoor coil

with cardboard or a plastic sheet.

BLOCKING OUTDOOR COIL

CARDBOARD OR

PLASTIC SHEET

OUTDOOR COIL SHOULD

BE BLOCKED ONE SIDE

AT A TIME WITH CARD--

BOARD OR PLASTIC

SHEET UNTIL PROPER

TESTING PRESSURES

ARE REACHED.

FIGURE 8

1-- Remove the cap from the liquid line service valve

stem and turn the stem clockwise 1/4 to 1/2 turn.

This will open the service port. Exercise caution--

the service port is not equipped with a valve core.

2-- With the manifold gauge hose still on the liquid

service port and the unit operating, read the liquid

line pressure.

3-- If the pressure is too low, block the airflow

through the outdoor coil until the liquid line pres-

sure stabilizes in a range of 200 to 250 psig. At that

time, record the liquid line temperature and the

liquid line pressure reading.

4-- Using a temperature/pressure chart for R22, de-

termine the saturation temperature for the liquid

line pressure reading.

5-- Subtract the liquid line temperature from the sat-

uration temperature (according to the chart) to

determine Subcooling. (Liquid line temperature --

Saturation temperature = Subcooiling)

6-- Compare the Subcooling value with those in table

4. If Subcooling is greater than shown, refrigerant

must be reclaimed. If Subcooling is less than

shown, refrigerant must be added.

TABLE 4

SUBCOOLING TEMP. (EF)

MODEL

HP23--211

HP23--410

HP23--460

4 + 2

HP23--311

HP23--261

HP23--141

HP23--510

HP23--650

SUBCOOLING METHOD--TXV Systems

9 + 2

13 + 2

9 + 2
9 + 2

8 + 2

6 + 2

7 + 2

HP23--410CDN

13 + 2

The Approach Method
TXV Systems, > 60EF Outdoor Temp

+DYLQJ WDNHQ WKH RXWGRRU DPELHQW DQG OLTXLG OLQH WHPSHUD
WXUH UHDGLQJV VXEWUDFW WKH RXWGRRU DPELHQW WHPSHUDWXUH
IURP WKH OLTXLG OLQH WHPSHUDWXUH WR GHWHUPLQH WKH $S
SURDFK WHPSHUDWXUH /LTXLG OLQH E)   2XWGRRU $PELHQW
E)  $SSURDFK WHPSHUDWXUH 7KH UHVXOWLQJ GLIIHUHQFH
$SSURDFK WHPSHUDWXUH VKRXOG DJUHH ZLWK WKH YDOXHV JLY
HQ LQ WDEOH  ,I QRW DGG UHIULJHUDQW WR ORZHU WKH DSSURDFK
WHPSHUDWXUH RU UHFRYHU UHIULJHUDQW IURP WKH V\VWHP WR LQ
FUHDVH WKH DSSURDFK WHPSHUDWXUH

TABLE 5

HP23--211

HP23--410CDN

HP23--460

6

14

12

HP23--311/410

7

HP23--261

5

HP23--141

HP23--510

HP23--650

11

7

11

APPROACH METHOD

MODEL NO.

APPROACH TEMPERATURE

LIQUID LINE E F

-- OUTDOOR AMBIENT E F

Note--For best results, the same thermometer should be used to

check both outdoor ambient and liquid temperatures.

6<67(0 23(5$7,21

Compressor Oil Charge

Refer to Lennox Cooling Service Handbook for cor-
rect procedure to check and add compressor oil. Heat
pump grade mineral oil (brand and viscosity unspeci-
fied) should be used. See table 6.

&2035(6625 2,/ &+$5*(

7$%/( 

81,7 02'(/ 12

&2035(6625 2,/ &+$5*(

)OXLG 2]V

+3 

+3 

+3 

+3 

+3 

+3 

+3 

+3 



+3 &'1

Filter Drier

The filter drier is equipped with an internal check
valve for correct refrigerant flow. See figure 7. If re-
placement is necessary, order another of like design
and capacity. A strainer in the liquid line gives addi-
tional protection.

Содержание HP23-141

Страница 1: ...HFODLPLQJ PXVW EH IROORZHG LQHV DQG RU LQFDUFHUDWLRQ PD EH OHYLHG IRU QRQ FRP SOLDQFH 167 7 21 16758 7 216 3 6 5 6 81 76 7 3803 81 76 WKURXJK WRQ 0 6XSHUVHGHV 0 7 2 217 176 3 7 3803 81 7 6 33 1 1 3 1...

Страница 2: ...6WDWH 6HUYLFHPDQ PSV 6XSSO 2XWGRRU DQ RPSUHVVRU QGRRU LOWHU OHDQ QGRRU ORZHU 530 OHFWULFDO RQQHFWLRQV 7LJKW 6XSSO 9ROWDJH 8QLW 2II 6 3 URS 2YHU YDSRUDWRU U 2XWGRRU RLO QWHULQJ LU 7HPSHUDWXUH LTXLG 3U...

Страница 3: ...f a support frame is constructed it must not block drain holes in unit base 4 When installed in areas where low ambient tem peratures exist locate unit so winter prevailing winds do not blow directly...

Страница 4: ...rafts or vibra tion Do not install thermostat on an outside wall A position approximately 5 feet 1524 mm from the floor and near the center of the conditioned area is most desirable 5 Route 24VAC cont...

Страница 5: ...ne I D and O D 2 The thermometer well packaged separately and at tached to the liquid line should be installed in the liquid line close to the HP23 unit as shown in figure 5 Connect thermometer well m...

Страница 6: ...NIFOLD GAUGE CONNECTIONS OUTDOOR COIL DEFROST THERMOSTAT EXPANSION VALVE FILTER DRIER WITH INTERNAL CHECK VALVE STRAINER TO R 22 DRUM LOW PRESSURE HIGH PRESSURE COMPRESSOR REVERSING VALVE VAPOR LINE V...

Страница 7: ...nect high pres sure gauge to service port 3 Using service wrench open valve stem one turn clockwise from backseated position 4 When finished using port backseat stem with ser vice wrench Tighten firml...

Страница 8: ...n will explode on con tact with oil and could cause personal injury When using high pressure gas such as nitrogen or CO2 for this purpose be sure to use a regulator that can control the pressure down...

Страница 9: ...ifold gauge valves to release the nitrogen from the line set and indoor unit 7 Reconnect the manifold gauge to the vacuum pump turn the pump on and continue to evacuate the line set and indoor unit un...

Страница 10: ...center manifold hose to an upright bottle of R22 Close manifold gauge set valves 2 Set the room thermostat to call for heat This will create the necessary load for properly charging the system in the...

Страница 11: ...shown refrigerant must be reclaimed If Subcooling is less than shown refrigerant must be added TABLE 4 SUBCOOLING TEMP EF MODEL HP23 211 HP23 410 HP23 460 4 2 HP23 311 HP23 261 HP23 141 HP23 510 HP23...

Страница 12: ...ill not allow a de frost to last for more than 14 minutes The defrost timer can be field adjusted from a 60 minute to a 30 or 90 minute defrost interval if warranted by climatic con ditions Timed Off...

Отзывы: