background image

Page 3

HP25 PARTS ARRANGEMENT

FIGURE 1

HP25 UNIT COMPONENTS

CONTACTOR

DEFROST CONTROL

LIQUID LINE

SERVICE VALVE

VAPOR  LINE

SERVICE VALVE

COMPRESSOR

MUFFLER

DEFROST

THERMOSTAT

EXPANSION

VALVE

EXPANSION   VALVE

SENSING BULB

REVERSING VALVE

AND SOLENOID

COMPRESSOR

TERMINAL BOX

FILTER/DRIER

WITH

INTERNAL CHECK VALVE

THERMOMETER WELL

TERMINAL STRIP

DUAL CAPACITOR

(Single-Phase Units)

SERVICE LIGHT

THERMOSTAT

DISTRIBUTOR

AND GAUGE PORT

AND GAUGE PORT

SUCTION GAUGE PORT

COMPRESSOR

TEMPERATURE

SENSOR

HP25211 THRU 460 ONLY

FACTORY

CHARGE

PROCESS PORT

CHARGE

COMPENSATOR

ACCUMULATOR

HP25510 AND

-650 ONLY

HIGH PRESSURE SWITCH

FAN CAPACITOR

(Three-Phase Units)

SETTING THE UNIT

HP25 heat pump units are approved and warranted

only for installation with specially matched indoor

coils, L10 or L15 line sets, and refrigerant control de

vices as designated by Lennox. Refer to the Lennox En

gineering Handbook for approved systems.

INSTALLATION

CLEARANCES

FIGURE 2

NOTE-48"

(1219mm)

 clearance required

on top of unit.

*One side dimension

 may be 12" (305mm).

*36"

(914mm)

36"

(914mm)

*36"

(914mm)

*36"

(914mm)

Heat pump units operate under a wide range of weath
er conditions; therefore, several factors must be con
sidered when positioning the outdoor unit.

 1- Place a sound-absorbing material, such as Iso

mode, under the unit if it will be installed in a loca
tion or position that will transmit sound or vibra
tion to the living area or adjacent buildings.

 2- Mount unit high enough above ground or roof to al

low adequate drainage of defrost water and prevent
ice build-up.

 3- In heavy snow areas, do not locate unit where drift

ing will occur. The unit base should be elevated
above the depth of average snows.

NOTE-Elevation of the unit may be accomplished
by constructing a frame using suitable materials. If
a support frame is constructed, it must not block
drain holes in unit base.

 4- When installed in areas where low ambient tem

peratures exist, locate unit so winter prevailing
winds do not blow directly into outdoor coil.

 5- Locate unit away from overhanging roof lines

which would allow water or ice to drop on, or in
front of, coil or into unit.

Содержание HP-511-513

Страница 1: ...evied for non compliance INSTALLATION INSTRUCTIONS HP25 SERIES UNITS HEAT PUMP UNITS 503 302M 6 95 Supersedes 503 247M TABLE OF CONTENTS HP25 HEAT PUMP UNIT 1 SHIPPING AND PACKING LIST 1 GENERAL INFOR...

Страница 2: ...D E F G H J K L HP25 211 in 27 7 8 25 7 8 29 7 8 12 1 4 22 7 16 14 7 16 22 1 8 1 7 8 16 3 4 5 1 2 2 7 8 HP25 211 HP25 261 mm 708 657 759 311 570 367 562 48 425 140 73 HP25 311 in 30 7 8 32 1 8 34 1 16...

Страница 3: ...OTE 48 1219mm clearance required on top of unit One side dimension may be 12 305mm 36 914mm 36 914mm 36 914mm 36 914mm Heat pump units operate under a wide range of weath er conditions therefore sever...

Страница 4: ...is instruction see figure 6 and in indoor unit instructions Refer to figure 5 for thermostat designa tions Refer to unit rating plate for minimum circuit am pacity and maximum fuse size WARNING Unit m...

Страница 5: ...1 1 8 in 28 6 mm FIELD FABRICATED L15 LINE SETS L15 41 20 ft 50 ft 6 1 m 15 2 m L15 65 30 ft 50 ft 9 1 m 15 2 m FIELD FABRICATED L15 26 20 ft 50 ft 6 1 m 15 2 m NOTE To obtain maximum efficiency remov...

Страница 6: ...o produce substances that corrode copper piping and compressor parts 1 Connect manifold gauge set to the service valve ports as follows low pressure gauge to vapor line service valve high pressure gau...

Страница 7: ...and suc tions pressures do not perform normally follow the steps below to correctly phase in the unit 1 Disconnect power to the unit 2 Reverse any two field power leads to the unit 3 Reapply power to...

Страница 8: ...6 If ambient temperature is less than 60 F 15 C air flow might need to be restricted to achieve pressur es in the 200 250 psig 1379 1724 kPa range See figure 8 These higher pressures are necessary for...

Страница 9: ...ngle pole single throw which is located on the liquid line The switch shuts off the compressor when discharge pressure rises above the factory set ting The switch is normally closed and is permanently...

Страница 10: ...PS2 termi nals on the defrost board If using an additional pres sure switch remove jumper before connecting additional switch to control board If no additional switch is needed DO NOT REMOVE JUMPER U...

Страница 11: ...power supplies At the beginning of each heating or cooling season the system should be cleaned as follows Heat Pump Unit 1 Clean and inspect outdoor coil Coil may be flushed with a water hose 2 Outdo...

Страница 12: ...o City City Serial No Date State State Service Technician Amps Supply Outdoor Fan Compressor Indoor Filter Clean Indoor Blower RPM Electrical Connections Tight Supply Voltage Unit Off S P Drop Over Ev...

Отзывы: