The TEST mode may be started at anytime. If the jumper
is in the TEST position at power-up or for longer than
five minutes, the control will ignore the TEST selection
and will default to a 90 minute interval.

Time-Delay

The timed-off delay is five minutes long. The delay fea
ture is provided to help protect the compressor in
cased of an interruption in power to the unit or when a
pressure switch resets.

Pressure Switch Safety Circuits

The defrost control incorporates a pressure switch safe
ty circuit that allows the application of an additional
pressure switch; high pressure switch (S4) is factory-
wired to this circuit. See figure 9. PS1 and PS2 terminals
are wired in series with a jumper internal to the control
board. This feature is available on all units.

During one demand cycle, the defrost control will lock
out the unit on the third instance that the unit goes off
on any auto-reset pressure switch wired to this circuit.
The diagnostic LEDs will display a pattern for a locked

out pressure switch on the third open pressure switch
occurrence. See table 7. The unit will remain locked out
until power is broken then remade to the control.
For HP25-211/461 units, the PS2 safety circuit termi
nals are connected to the compressor thermostat. An
optional loss of charge switch may be field-installed by
connecting it in series with the other switches. See unit
wiring diagram.
HP25-511/651 units are equipped with a factory-
installed jumper over the two safety circuit PS2 termi
nals on the defrost board. If using an additional pres
sure switch, remove jumper before connecting
additional switch to control board. If no additional
switch is needed, 

DO NOT REMOVE JUMPER

. Unit will

not operate without jumper in place in this case.
For three-phase units, the factory-installed high pres
sure switch is connected to the two outside terminals
of the pressure switch connections. If adding another
pressure switch, remove lead from outer PS2 terminal
and connect it to inside terminal of PS1. Connect addi
tional pressure switch leads to PS2 set of safety circuit
terminals. See figure 9.

DEFROST CONTROL BOARD

FIGURE 9

24V TERMINAL

STRIP

CONNECTIONS

DIAGNOSTIC

LEDs

PRESSURE

SWITCH

SAFETY CIRCUIT

CONNECTIONS

S4

S5

S4

FACTORY CONNECTION FOR

THREE-PHASE UNITS ONLY

FACTORY CONNECTIONS FOR

HP25-211/461 UNITS ONLY

DEFROST

INTERVAL

TIMING PINS

FACTORY-INSTALLED

JUMPER

HP25-511/651 ONLY.

(Remove to add

pressure switch)

AMBIENT

THERMISTOR

CONNECTION

High Pressure

Compressor

Thermostat

S4

FACTORY CONNECTIONS FOR

HP25-511/651 UNITS ONLY

High Pressure

To add additional pressure switch, remove jumper and

connect optional switch leads to PS2 terminals. If no

other pressure switch is added, jumper must stay in

place for proper unit operation.

To add additional pressure switch, remove lead from

outer PS2 terminal and connect to inside PS1 terminal.

Connect optional switch leads to PS2 terminals.

NOTE- There is an internal jumper between inside PS1 and PS2 terminals.

High Pressure

SERVICE LIGHT

CONNECTION

To add additional pressure switch, such as loss of

charge switch, wire it in series with the two factory-

installed switches. See unit wiring diagram for details.

Содержание HP-511-513

Страница 1: ...evied for non compliance INSTALLATION INSTRUCTIONS HP25 SERIES UNITS HEAT PUMP UNITS 503 302M 6 95 Supersedes 503 247M TABLE OF CONTENTS HP25 HEAT PUMP UNIT 1 SHIPPING AND PACKING LIST 1 GENERAL INFOR...

Страница 2: ...D E F G H J K L HP25 211 in 27 7 8 25 7 8 29 7 8 12 1 4 22 7 16 14 7 16 22 1 8 1 7 8 16 3 4 5 1 2 2 7 8 HP25 211 HP25 261 mm 708 657 759 311 570 367 562 48 425 140 73 HP25 311 in 30 7 8 32 1 8 34 1 16...

Страница 3: ...OTE 48 1219mm clearance required on top of unit One side dimension may be 12 305mm 36 914mm 36 914mm 36 914mm 36 914mm Heat pump units operate under a wide range of weath er conditions therefore sever...

Страница 4: ...is instruction see figure 6 and in indoor unit instructions Refer to figure 5 for thermostat designa tions Refer to unit rating plate for minimum circuit am pacity and maximum fuse size WARNING Unit m...

Страница 5: ...1 1 8 in 28 6 mm FIELD FABRICATED L15 LINE SETS L15 41 20 ft 50 ft 6 1 m 15 2 m L15 65 30 ft 50 ft 9 1 m 15 2 m FIELD FABRICATED L15 26 20 ft 50 ft 6 1 m 15 2 m NOTE To obtain maximum efficiency remov...

Страница 6: ...o produce substances that corrode copper piping and compressor parts 1 Connect manifold gauge set to the service valve ports as follows low pressure gauge to vapor line service valve high pressure gau...

Страница 7: ...and suc tions pressures do not perform normally follow the steps below to correctly phase in the unit 1 Disconnect power to the unit 2 Reverse any two field power leads to the unit 3 Reapply power to...

Страница 8: ...6 If ambient temperature is less than 60 F 15 C air flow might need to be restricted to achieve pressur es in the 200 250 psig 1379 1724 kPa range See figure 8 These higher pressures are necessary for...

Страница 9: ...ngle pole single throw which is located on the liquid line The switch shuts off the compressor when discharge pressure rises above the factory set ting The switch is normally closed and is permanently...

Страница 10: ...PS2 termi nals on the defrost board If using an additional pres sure switch remove jumper before connecting additional switch to control board If no additional switch is needed DO NOT REMOVE JUMPER U...

Страница 11: ...power supplies At the beginning of each heating or cooling season the system should be cleaned as follows Heat Pump Unit 1 Clean and inspect outdoor coil Coil may be flushed with a water hose 2 Outdo...

Страница 12: ...o City City Serial No Date State State Service Technician Amps Supply Outdoor Fan Compressor Indoor Filter Clean Indoor Blower RPM Electrical Connections Tight Supply Voltage Unit Off S P Drop Over Ev...

Отзывы: