background image

Page 45

G51MP−60C−090 PERFORMANCE (Less Filter)

External

Static

Pressure −

in. w.g.

Air Volume / Watts at Different Blower Speeds

Bottom Return Air, Side Return Air with Optional RAB
Return Air Base, Return Air from Both Sides or Return
Air from Bottom and One Side.

Single Side Return Air

 − Air volumes in bold require field

fabricated transition to accommodate 20 x 25 x 1 in. air
filter in order to maintain proper air velocity.

High

Medium−High Medium−Low

Low

High

Medium−High Medium−Low

Low

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

0.00

2840

1450

2345

1105

1895

900

1515

700

2835

1495

2340

1155

1800

895

1440

695

0.10

2765

1415

2365

1080

1950

885

1580

700

2785

1475

2345

1135

1805

865

1515

690

0.20

2695

1385

2345

1050

1985

870

1620

695

2715

1435

2275

1080

1825

845

1560

685

0.30

2605

1335

2315

1030

1990

850

1645

690

2620

1380

2260

1035

1840

825

1600

680

0.40

2530

1300

2265

990

1990

825

1665

675

2550

1350

2230

1015

1845

815

1620

670

0.50

2420

1260

2210

955

1970

800

1675

665

2450

1305

2175

990

1850

790

1615

655

0.60

2330

1220

2145

925

1930

775

1665

650

2365

1270

2130

940

1830

775

1615

640

0.70

2250

1190

2050

885

1875

745

1645

630

2240

1205

2070

915

1815

760

1595

620

0.80

2135

1140

2000

865

1810

715

1620

615

2185

1190

1965

865

1775

745

1555

605

0.90

2030

1090

1885

830

1720

685

1560

590

2015

1150

1820

820

1690

715

1440

580

G51MP−60C−110 PERFORMANCE (Less Filter)

External

Static

Pressure

in. w.g.

Air Volume / Watts at Different Blower Speeds

Bottom Return Air, Side Return Air with Optional RAB
Return Air Base, Return Air from Both Sides or Return
Air from Bottom and One Side.

Single Side Return Air

 − Air volumes in bold require field

fabricated transition to accommodate 20 x 25 x 1 in. air
filter in order to maintain proper air velocity.

High

Medium−High Medium−Low

Low

High

Medium−High Medium−Low

Low

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

0.00

2720

1385

2410

1090

2055

935

1620

710

2625

1350

2310

1080

1885

885

1515

700

0.10

2665

1355

2385

1075

2025

885

1730

735

2570

1330

2325

1060

1910

865

1575

700

0.20

2585

1315

2350

1015

2030

865

1680

690

2410

1305

2285

1035

1930

845

1620

690

0.30

2505

1275

2290

990

2025

840

1695

675

2425

1265

2230

990

1925

825

1635

675

0.40

2435

1250

2235

940

2030

830

1695

660

2335

1220

2175

950

1910

810

1640

660

0.50

2350

1205

2170

930

1975

790

1735

665

2270

1195

2120

935

1895

785

1640

640

0.60

2255

1185

2100

895

1915

765

1720

650

2170

1155

2045

885

1860

765

1630

630

0.70

2160

1150

2005

840

1865

730

1680

635

2110

1130

1950

855

1795

730

1590

610

0.80

2020

1090

1905

825

1810

710

1625

610

2035

1090

1885

820

1745

705

1540

580

0.90

1910

1050

1820

795

1705

675

1540

590

1900

1055

1760

780

1665

680

1470

565

G51MP−60D−135 PERFORMANCE (Less Filter)

External

Static

Pressure

in. w.g.

Air Volume / Watts at Different Blower Speeds

Bottom Return Air, Side Return Air with Optional RAB
Return Air Base, Return Air from Both Sides or Return
Air from Bottom and One Side.

Single Side Return Air

 − Air volumes in bold require field

fabricated transition to accommodate 20 x 25 x 1 in. air
filter in order to maintain proper air velocity.

High

Medium−High Medium−Low

Low

High

Medium−High Medium−Low

Low

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

0.00

2730

1465

2425

1125

2055

915

1560

680

2665

1440

2325

1100

1865

890

1410

690

0.10

2670

1440

2400

1100

2065

890

1590

675

2615

1405

2310

1065

1915

865

1465

685

0.20

2600

1400

2365

1070

2045

865

1620

665

2530

1370

2280

1055

1925

850

1570

675

0.30

2525

1360

2315

1045

2035

845

1615

655

2470

1330

2235

1015

1920

825

1590

670

0.40

2445

1325

2260

1015

2020

820

1615

645

2380

1290

2175

985

1910

805

1590

655

0.50

2360

1280

2195

985

1960

790

1610

635

2310

1265

2120

965

1890

790

1595

645

0.60

2290

1255

2130

965

1900

755

1600

615

2200

1230

2055

935

1835

765

1580

630

0.70

2205

1220

2035

910

1825

730

1570

600

2120

1190

1970

900

1790

740

1545

605

0.80

2110

1195

1945

880

1765

710

1540

580

2025

1160

1890

875

1720

710

1515

590

0.90

1970

1120

1835

830

1680

690

1540

545

1930

1110

1800

835

1655

685

1440

570

Содержание G51MP

Страница 1: ...n 41 Other Unit Adjustments 43 Service 46 Planned Service 48 Repair Parts List 48 Troubleshooting 49 Ignition Control Board Diagnostic Codes 52 Vent Pipe Sizing Worksheet 53 Start Up Performance Check...

Страница 2: ...he optional RAB Return Air Base NOTE 60C and 60D size units installed in upflow applica tions that require air volumes over 1800 cfm 850 L s must have one of the following 1 Single side return air wit...

Страница 3: ...lokPlusTM HEAT EXCHANGER ASSEMBLY CONDENSER COIL CONTROL BOX DOOR INTERLOCK SWITCH COLD HEADER COLLECTOR BOX COMBUSTION AIR INDUCER BLOWER ACCESS DOOR BURNER ACCESS PANEL FLUE COLLAR COMBUSTION AIR PR...

Страница 4: ...deck in the heating compartment G51MP 60D 135 units are shipped with a 3 to 2 PVC re ducing elbow Canadian Installations Only Replace the provided 2 street elbow shipped with the G51MP 48C 110 and G5...

Страница 5: ...rrangement a damper or other means to control the flow of air must adequately prevent chilled air from entering the furnace If the damper is manually oper ated it must be equipped to prevent operation...

Страница 6: ...berglass wool is known to the State of Cal ifornia to cause cancer Fiberglass wool may also cause respiratory skin and eye irritation To reduce exposure to this substance or for further information co...

Страница 7: ...a door Though an area may appear to be un confined it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration If the furnace is located i...

Страница 8: ...ng of all equipment in the enclosure See figures 4 and 5 When communicat ing with the outdoors through horizontal ducts each open ing shall have a minimum free area of 1 square inch 645 mm2 per 2 000...

Страница 9: ...one rigid leg The rigid leg is equipped with a shipping bolt and a flat white plastic wash er rather than the rubber mounting grommet used with a flexible mounting leg The bolt and washer must be re m...

Страница 10: ...her combustible materials other than wood flooring FIGURE 8 Return Air Upflow Units Return air can be brought in through the bottom or either side of the furnace installed in an upflow application If...

Страница 11: ...th RAB Return Air Base 1 Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet Minimum unit side return air opening dimensions for units re...

Страница 12: ...k 0 Sides 0 Vent 0 Floor NC Front clearance in alcove installation must be 24 in 610 mm Maintain a minimum of 24 in 610 mm for front service access Allow proper clearances to accommodate condensate tr...

Страница 13: ...rnace over the plenum 6 Ensure that the seal between the furnace and plenum is adequate G51MP UNIT SUPPLY AIR PLENUM ADDITIVE BASE PROPERLY SIZED FLOOR OPENING FIGURE 14 Installation on Cooling Cabine...

Страница 14: ...front of unit 3 If unit is installed above finished space fabricate a drain pan fitted with a 1 2 inch or 3 4 inch N P T fitting 4 Using 3 8 inch rods and support frame kit ordered separately fabricat...

Страница 15: ...n figure 18 or install the furnace on a field fabri cated raised platform as shown in figure 19 The unit must be supported at both ends and beneath the blower deck to prevent sagging Unit Heater Disch...

Страница 16: ...ed on a platform make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely Use fiberglass sealing strips caulking or equivalent seal...

Страница 17: ...r Dia X Length Outdoor Ex haust Accel erator Dia X Length 1 1 2 Concentric Kit 2 Con centric Kit 3 Con centric Kit 2 Wall Plate Kit 3 Wall Plate Kit 2 Wall Ring Kit 1 1 2 X 12 2 X 12 71M80 or 44W92 69...

Страница 18: ...cations which permit the use of several differ ent sizes of vent pipe a combination vent pipe may be used Contact Lennox Application Department for assis tance in sizing vent pipe in these application...

Страница 19: ...ION Fumes from PVC glue may ignite during system check Allow fumes to dissipate for at least 5 minutes before placing unit into operation 1 Measure and cut vent pipe to desired length 2 Debur and cham...

Страница 20: ...In upflow or downflow applications the reducing ell must be glued using transition solvent cement directly into the unit flue collar 1 Choose the appropriate side for venting in upflow or downflow pos...

Страница 21: ...e exhaust vent pipe operates under positive pres sure and must be completely sealed to prevent leak age of combustion products into the living space Intake Piping The G51MP furnace may be installed in...

Страница 22: ...on Shown 2 2 2 2 TRANSITION TRANSITION 2 2 1 2 3 OR 4 2 1 2 3 OR 4 Limit pipe length to 4 in 135 applications 2 2 24B 045 36B 045 36B 070 36C 090 48C 090 60C 090 48C 110 60C 110 60D 135 24B 045 36B 04...

Страница 23: ...arance of 3 76mm around the air intake opening The air intake opening with the protective screen should always be directed either downward or straight out Use 2 pipe and fittings only and make sure th...

Страница 24: ...n temperature is below 32 F 0 C exhaust piping should be insulated with 1 2 13mm Ar maflex or equivalent when run through unheated space Do not leave any surface area of exhaust pipe open to out side...

Страница 25: ...rance above paved sidewalk or paved driveway located on public property Clearance under veranda porch deck or balcony 12 Equal to or greater than soffit depth 3 feet 9m 12 3 feet 9m within a height 15...

Страница 26: ...ewalk or paved driveway located on public property Clearance under veranda porch deck or balcony 12 3 feet 9m 7 feet 2 1m 3 feet 9m within a height 15 feet 4 5m above the meter regulator assembly 3 fe...

Страница 27: ...3 FOAM INSULATION IN UNCONDITIONED SPACE SIZE TERMINATION PIPE PER TABLE 8 3 76 MAX 12 305 ABOVE AVERAGE SNOW ACCUMULATION 3 76 OR 2 51 PVC PROVIDE SUPPORT FOR INTAKE AND EXHAUST LINES 8 203 MIN Inche...

Страница 28: ...305 MAX for 2 51 8 203 MIN 1 2 13 FOAM INSULATION 1 2 13 FOAM INSULATION IN UNCONDITIONED SPACE PROVIDE SUPPORT FOR INTAKE AND EXHAUST LINES EVERY 36 914 OUTSIDE WALL Inches mm SIDE VIEW DIRECT VENT W...

Страница 29: ...ULATE TO FORM SEAL SHEET METAL TOP PLATE MINIMUM 12 305mm ABOVE ROOF OR AVERAGE SNOW ACCUMULATION SIZE TERMINATION PIPE PER TABLE 8 Details of Exhaust Piping Terminations for Non Direct Vent Applicati...

Страница 30: ...RMINATION PIPE PER TABLE 8 G51MP NON DIRECT VENT APPLICATION USING EXISTING CHIMNEY Condensate Piping This unit is designed for either right or left side exit of con densate piping in either upflow or...

Страница 31: ...1 8m kit no 26K68 24 ft 7 3m kit no 26K69 and 50 ft 15 2m kit no 26K70 CAUTION Do not use copper tubing or existing copper condensate lines for drain line 5 If unit will be started immediately upon co...

Страница 32: ...and field installed for gas leaks Use a leak detecting solution or other preferred means The furnace must be isolated from the gas supply system by closing its individual manual shut off valve during...

Страница 33: ...1 73 57 1 61 53 1 50 50 1 42 3 4 19 05 824 20 930 360 10 19 250 7 08 200 5 66 170 4 81 151 4 28 138 3 91 125 3 54 118 3 34 110 3 11 103 2 92 1 25 4 1 049 26 645 680 19 25 465 13 17 375 10 62 320 9 06...

Страница 34: ...can be turned off for servicing Before connecting the thermostat or the power wiring check to make sure the wires will be long enough for servicing at a later date Remove the blower access panel to c...

Страница 35: ...mostat terminal block which is lo cated on the control board Install the room thermostat according to the instruc tions provided with the thermostat See figure 51 for thermostat designations If the fu...

Страница 36: ...eating Speed 120VAC Unused Blower Not energized Continuous Low Blower Speed Accessory Terminal 120VAC Transformer 120VAC Input 120VAC Heat Only Accessory 120VAC 120 Volt Neutral Flame Sensor Heat Only...

Страница 37: ...Page 37 FIGURE 54 TYPICAL G51MP WIRING DIAGRAM...

Страница 38: ...should be primed with suffi cient water to ensure proper condensate drain opera tion BEFORE LIGHTING the unit smell all around the fur nace area for gas Be sure to smell next to the floor be cause so...

Страница 39: ...rmostat calls for heat combustion air inducer starts Combustion air pressure switch proves blower opera tion Switch is factory set and requires no adjustment After a 15 second prepurge the hot surface...

Страница 40: ...ove the threaded plug from the outlet side of the gas valve and install a field provided barbed fitting Connect test gauge connection to barbed fitting to measure manifold pressure 2 Tee into the gas...

Страница 41: ...izes 10 0 10 0 10 0 10 0 10 0 Conversion kit required for applications at altitudes above 7501 ft above sea level Conversion kit required for applications at all altitudes NOTE A natural to L P propan...

Страница 42: ...y inspect the venting system for proper size and horizontal pitch Determine there is no blockage or re striction leakage corrosion or other deficiencies which could cause an unsafe condition 3 To the...

Страница 43: ...onds See figure 53 Thermostat Heat Anticipation Set the heat anticipator setting if adjustable according to the amp draw listed on the wiring diagram that is attached to the unit Electrical 1 Check al...

Страница 44: ...965 335 860 295 0 80 1080 440 1010 360 865 310 775 270 0 90 945 400 840 320 765 275 710 245 G51MP 36C 090 PERFORMANCE Less Filter External Static Pressure in w g Air Volume Watts at Different Blower...

Страница 45: ...10 1090 2055 935 1620 710 2625 1350 2310 1080 1885 885 1515 700 0 10 2665 1355 2385 1075 2025 885 1730 735 2570 1330 2325 1060 1910 865 1575 700 0 20 2585 1315 2350 1015 2030 865 1680 690 2410 1305 22...

Страница 46: ...ger If cleaning the heat exchanger becomes necessary follow the below procedures and refer to figure 1 when disassem bling unit Use papers or protective covering in front of fur nace while removing he...

Страница 47: ...mps 35 Reinstall burner box assembly in vestibule area 36 Reconnect flame roll out switch wires 37 Reconnect sensor wire and reconnect 2 pin plug from ignitor 38 Secure burner box assembly to vestibul...

Страница 48: ...mporarily shut down the furnace until the items can be repaired or replaced Instruct the homeowners to pay attention to their furnace Situations can arise between annual furnace in spections that may...

Страница 49: ...LOUT SWITCH CLOSES GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED DS1 SLOW FLASH DS2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY DS1 OFF DS2 SLOW...

Страница 50: ...AL FOR IGNITION GAS VALVE OPENS IGNITOR ENERGIZED FOR UP TO 4 SECONDS YES FLAME STABILIZATION PERIOD GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER OFF HAS CONTROL FAILED TO SENSE FLAME FOR FIV...

Страница 51: ...ONTINUOUSLY ARE ROLLOUT SWITCHES CLOSED DS1 DS2 SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELA...

Страница 52: ...ring cooling and continuous fan SIMULTANEOUS FAST FLASH SIMULTANEOUS FAST FLASH Normal operation Signaled when heating demand initiated at thermostat SLOW FLASH ON Primary or secondary limit switch op...

Страница 53: ...ved NOTE In Direct Vent systems total the equivalent length of either the exhaust OR intake piping run depending upon which will be LONGER Intake and exhaust pipe diameter must be the same size and mu...

Страница 54: ...eight 8 feet above grade di rectly in line with the exhaust vent terminal for the hori zontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half...

Отзывы: