background image

Page 8

Air from Outside

If air from outside is brought in for combustion and ventila-
tion, the confined space shall be provided with two
permanent openings. One opening shall be within 12"
(305mm) of the top of the enclosure and one within 12"
(305mm) of the bottom. These openings must communi-
cate directly or by ducts with the outdoors or spaces (crawl
or attic) that freely communicate with the outdoors or indi-
rectly through vertical ducts. Each opening shall have a
minimum free area of 1 square inch per 4,000 Btu
(645mm

2

 per 1.17kW) per hour of total input rating of all

equipment in the enclosure. When communicating with
the outdoors through horizontal ducts, each opening shall
have a minimum free area of 1 square inch per 2,000 Btu
(645mm

2

 per .59kW) per total input rating of all equipment

in the enclosure (See figure 4).

FIGURE 4

EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE

(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)

NOTE

−The inlet and outlet air openings shall each have a free area

of at least one square inch per 4,000 Btu (645mm

per 1.17kW) per

hour of the total input rating of all equipment in the enclosure.

OUTLET

AIR

INLET

AIR

VENTILATION

LOUVERS

(For unheated

crawl space)

G51MP

ROOF TERMINATED 

EXHAUST PIPE

VENTILATION LOUVERS

(Each end of attic)

SIDE WALL

 TERMINATED

EXHAUST PIPE

(ALTERNATE

LOCATION)

If air from outside is brought in for combustion and ventila-
tion, the confined space must have two permanent open-
ings. One opening shall be within 12 inches (305 mm) of
the top of the enclosure and one opening within 12 inches
(305 mm) of the bottom. These openings must communi-
cate directly or by ducts with the outdoors or spaces (crawl
or attic) that freely communicate with the outdoors or indi-
rectly through vertical ducts. Each opening shall have a
minimum free area of 1 square inch (645 mm

2

) per 4,000

Btu (1.17 kW) per hour of total input rating of all equipment
in the enclosure. See figures 4 and 5. When communicat-
ing with the outdoors through horizontal ducts, each open-
ing shall have a minimum free area of 1 square inch (645
mm

2

) per 2,000 Btu (.56 kW) per total input rating of all

equipment in the enclosure. See

 

figure  6.

When ducts are used, they shall be of the same cross−sec-
tional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3 inches (75 mm). In calculating free
area, the blocking effect of louvers, grilles, or screens
must be considered. If the design and free area of protec-
tive covering is not known for calculating the size opening
required, it may be assumed that wood louvers will have
20 to 25 percent free area and metal louvers and grilles
will have 60 to 75 percent free area. Louvers and grilles
must be fixed in the open position or interlocked with the
equipment so that they are opened automatically during
equipment operation.

FIGURE 5

EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE

(All Air Through Ventilated Attic)

NOTE

−The inlet and outlet air openings shall each have a free area of

at least one square inch per 4,000 Btu (645mm

per 1.17kW) per hour

of the total input rating of all equipment in the enclosure.

OUTLET

AIR

VENTILATION LOUVERS

(Each end of attic)

INLET AIR

(Ends 12" above

bottom)

G51MP

ROOF TERMINATED 

EXHAUST PIPE

SIDE WALL

 TERMINATED

EXHAUST PIPE

(ALTERNATE

LOCATION)

FIGURE 6

G51MP

EQUIPMENT IN CONFINED SPACE − 

ALL AIR FROM OUTSIDE

OUTLET AIR

INLET AIR

NOTE

−Each air duct opening shall have a free area of at least one

square inch per 2,000 Btu (645mm

per .59kW) per hour of the total

input rating of all equipment in the enclosure. If the equipment room
is located against an outside wall and the air openings communi-
cate directly with the outdoors, each opening shall have a free area
of at least 1 square inch per 4,000 Btu (645mm

per 1.17kW) per

hour of the total input rating of all other equipment in the enclosure.

ROOF TERMINATED 

EXHAUST PIPE

SIDE WALL

 TERMINATED

EXHAUST PIPE

(ALTERNATE

LOCATION)

Содержание G51MP

Страница 1: ...n 41 Other Unit Adjustments 43 Service 46 Planned Service 48 Repair Parts List 48 Troubleshooting 49 Ignition Control Board Diagnostic Codes 52 Vent Pipe Sizing Worksheet 53 Start Up Performance Check...

Страница 2: ...he optional RAB Return Air Base NOTE 60C and 60D size units installed in upflow applica tions that require air volumes over 1800 cfm 850 L s must have one of the following 1 Single side return air wit...

Страница 3: ...lokPlusTM HEAT EXCHANGER ASSEMBLY CONDENSER COIL CONTROL BOX DOOR INTERLOCK SWITCH COLD HEADER COLLECTOR BOX COMBUSTION AIR INDUCER BLOWER ACCESS DOOR BURNER ACCESS PANEL FLUE COLLAR COMBUSTION AIR PR...

Страница 4: ...deck in the heating compartment G51MP 60D 135 units are shipped with a 3 to 2 PVC re ducing elbow Canadian Installations Only Replace the provided 2 street elbow shipped with the G51MP 48C 110 and G5...

Страница 5: ...rrangement a damper or other means to control the flow of air must adequately prevent chilled air from entering the furnace If the damper is manually oper ated it must be equipped to prevent operation...

Страница 6: ...berglass wool is known to the State of Cal ifornia to cause cancer Fiberglass wool may also cause respiratory skin and eye irritation To reduce exposure to this substance or for further information co...

Страница 7: ...a door Though an area may appear to be un confined it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration If the furnace is located i...

Страница 8: ...ng of all equipment in the enclosure See figures 4 and 5 When communicat ing with the outdoors through horizontal ducts each open ing shall have a minimum free area of 1 square inch 645 mm2 per 2 000...

Страница 9: ...one rigid leg The rigid leg is equipped with a shipping bolt and a flat white plastic wash er rather than the rubber mounting grommet used with a flexible mounting leg The bolt and washer must be re m...

Страница 10: ...her combustible materials other than wood flooring FIGURE 8 Return Air Upflow Units Return air can be brought in through the bottom or either side of the furnace installed in an upflow application If...

Страница 11: ...th RAB Return Air Base 1 Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet Minimum unit side return air opening dimensions for units re...

Страница 12: ...k 0 Sides 0 Vent 0 Floor NC Front clearance in alcove installation must be 24 in 610 mm Maintain a minimum of 24 in 610 mm for front service access Allow proper clearances to accommodate condensate tr...

Страница 13: ...rnace over the plenum 6 Ensure that the seal between the furnace and plenum is adequate G51MP UNIT SUPPLY AIR PLENUM ADDITIVE BASE PROPERLY SIZED FLOOR OPENING FIGURE 14 Installation on Cooling Cabine...

Страница 14: ...front of unit 3 If unit is installed above finished space fabricate a drain pan fitted with a 1 2 inch or 3 4 inch N P T fitting 4 Using 3 8 inch rods and support frame kit ordered separately fabricat...

Страница 15: ...n figure 18 or install the furnace on a field fabri cated raised platform as shown in figure 19 The unit must be supported at both ends and beneath the blower deck to prevent sagging Unit Heater Disch...

Страница 16: ...ed on a platform make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely Use fiberglass sealing strips caulking or equivalent seal...

Страница 17: ...r Dia X Length Outdoor Ex haust Accel erator Dia X Length 1 1 2 Concentric Kit 2 Con centric Kit 3 Con centric Kit 2 Wall Plate Kit 3 Wall Plate Kit 2 Wall Ring Kit 1 1 2 X 12 2 X 12 71M80 or 44W92 69...

Страница 18: ...cations which permit the use of several differ ent sizes of vent pipe a combination vent pipe may be used Contact Lennox Application Department for assis tance in sizing vent pipe in these application...

Страница 19: ...ION Fumes from PVC glue may ignite during system check Allow fumes to dissipate for at least 5 minutes before placing unit into operation 1 Measure and cut vent pipe to desired length 2 Debur and cham...

Страница 20: ...In upflow or downflow applications the reducing ell must be glued using transition solvent cement directly into the unit flue collar 1 Choose the appropriate side for venting in upflow or downflow pos...

Страница 21: ...e exhaust vent pipe operates under positive pres sure and must be completely sealed to prevent leak age of combustion products into the living space Intake Piping The G51MP furnace may be installed in...

Страница 22: ...on Shown 2 2 2 2 TRANSITION TRANSITION 2 2 1 2 3 OR 4 2 1 2 3 OR 4 Limit pipe length to 4 in 135 applications 2 2 24B 045 36B 045 36B 070 36C 090 48C 090 60C 090 48C 110 60C 110 60D 135 24B 045 36B 04...

Страница 23: ...arance of 3 76mm around the air intake opening The air intake opening with the protective screen should always be directed either downward or straight out Use 2 pipe and fittings only and make sure th...

Страница 24: ...n temperature is below 32 F 0 C exhaust piping should be insulated with 1 2 13mm Ar maflex or equivalent when run through unheated space Do not leave any surface area of exhaust pipe open to out side...

Страница 25: ...rance above paved sidewalk or paved driveway located on public property Clearance under veranda porch deck or balcony 12 Equal to or greater than soffit depth 3 feet 9m 12 3 feet 9m within a height 15...

Страница 26: ...ewalk or paved driveway located on public property Clearance under veranda porch deck or balcony 12 3 feet 9m 7 feet 2 1m 3 feet 9m within a height 15 feet 4 5m above the meter regulator assembly 3 fe...

Страница 27: ...3 FOAM INSULATION IN UNCONDITIONED SPACE SIZE TERMINATION PIPE PER TABLE 8 3 76 MAX 12 305 ABOVE AVERAGE SNOW ACCUMULATION 3 76 OR 2 51 PVC PROVIDE SUPPORT FOR INTAKE AND EXHAUST LINES 8 203 MIN Inche...

Страница 28: ...305 MAX for 2 51 8 203 MIN 1 2 13 FOAM INSULATION 1 2 13 FOAM INSULATION IN UNCONDITIONED SPACE PROVIDE SUPPORT FOR INTAKE AND EXHAUST LINES EVERY 36 914 OUTSIDE WALL Inches mm SIDE VIEW DIRECT VENT W...

Страница 29: ...ULATE TO FORM SEAL SHEET METAL TOP PLATE MINIMUM 12 305mm ABOVE ROOF OR AVERAGE SNOW ACCUMULATION SIZE TERMINATION PIPE PER TABLE 8 Details of Exhaust Piping Terminations for Non Direct Vent Applicati...

Страница 30: ...RMINATION PIPE PER TABLE 8 G51MP NON DIRECT VENT APPLICATION USING EXISTING CHIMNEY Condensate Piping This unit is designed for either right or left side exit of con densate piping in either upflow or...

Страница 31: ...1 8m kit no 26K68 24 ft 7 3m kit no 26K69 and 50 ft 15 2m kit no 26K70 CAUTION Do not use copper tubing or existing copper condensate lines for drain line 5 If unit will be started immediately upon co...

Страница 32: ...and field installed for gas leaks Use a leak detecting solution or other preferred means The furnace must be isolated from the gas supply system by closing its individual manual shut off valve during...

Страница 33: ...1 73 57 1 61 53 1 50 50 1 42 3 4 19 05 824 20 930 360 10 19 250 7 08 200 5 66 170 4 81 151 4 28 138 3 91 125 3 54 118 3 34 110 3 11 103 2 92 1 25 4 1 049 26 645 680 19 25 465 13 17 375 10 62 320 9 06...

Страница 34: ...can be turned off for servicing Before connecting the thermostat or the power wiring check to make sure the wires will be long enough for servicing at a later date Remove the blower access panel to c...

Страница 35: ...mostat terminal block which is lo cated on the control board Install the room thermostat according to the instruc tions provided with the thermostat See figure 51 for thermostat designations If the fu...

Страница 36: ...eating Speed 120VAC Unused Blower Not energized Continuous Low Blower Speed Accessory Terminal 120VAC Transformer 120VAC Input 120VAC Heat Only Accessory 120VAC 120 Volt Neutral Flame Sensor Heat Only...

Страница 37: ...Page 37 FIGURE 54 TYPICAL G51MP WIRING DIAGRAM...

Страница 38: ...should be primed with suffi cient water to ensure proper condensate drain opera tion BEFORE LIGHTING the unit smell all around the fur nace area for gas Be sure to smell next to the floor be cause so...

Страница 39: ...rmostat calls for heat combustion air inducer starts Combustion air pressure switch proves blower opera tion Switch is factory set and requires no adjustment After a 15 second prepurge the hot surface...

Страница 40: ...ove the threaded plug from the outlet side of the gas valve and install a field provided barbed fitting Connect test gauge connection to barbed fitting to measure manifold pressure 2 Tee into the gas...

Страница 41: ...izes 10 0 10 0 10 0 10 0 10 0 Conversion kit required for applications at altitudes above 7501 ft above sea level Conversion kit required for applications at all altitudes NOTE A natural to L P propan...

Страница 42: ...y inspect the venting system for proper size and horizontal pitch Determine there is no blockage or re striction leakage corrosion or other deficiencies which could cause an unsafe condition 3 To the...

Страница 43: ...onds See figure 53 Thermostat Heat Anticipation Set the heat anticipator setting if adjustable according to the amp draw listed on the wiring diagram that is attached to the unit Electrical 1 Check al...

Страница 44: ...965 335 860 295 0 80 1080 440 1010 360 865 310 775 270 0 90 945 400 840 320 765 275 710 245 G51MP 36C 090 PERFORMANCE Less Filter External Static Pressure in w g Air Volume Watts at Different Blower...

Страница 45: ...10 1090 2055 935 1620 710 2625 1350 2310 1080 1885 885 1515 700 0 10 2665 1355 2385 1075 2025 885 1730 735 2570 1330 2325 1060 1910 865 1575 700 0 20 2585 1315 2350 1015 2030 865 1680 690 2410 1305 22...

Страница 46: ...ger If cleaning the heat exchanger becomes necessary follow the below procedures and refer to figure 1 when disassem bling unit Use papers or protective covering in front of fur nace while removing he...

Страница 47: ...mps 35 Reinstall burner box assembly in vestibule area 36 Reconnect flame roll out switch wires 37 Reconnect sensor wire and reconnect 2 pin plug from ignitor 38 Secure burner box assembly to vestibul...

Страница 48: ...mporarily shut down the furnace until the items can be repaired or replaced Instruct the homeowners to pay attention to their furnace Situations can arise between annual furnace in spections that may...

Страница 49: ...LOUT SWITCH CLOSES GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED DS1 SLOW FLASH DS2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY DS1 OFF DS2 SLOW...

Страница 50: ...AL FOR IGNITION GAS VALVE OPENS IGNITOR ENERGIZED FOR UP TO 4 SECONDS YES FLAME STABILIZATION PERIOD GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER OFF HAS CONTROL FAILED TO SENSE FLAME FOR FIV...

Страница 51: ...ONTINUOUSLY ARE ROLLOUT SWITCHES CLOSED DS1 DS2 SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELA...

Страница 52: ...ring cooling and continuous fan SIMULTANEOUS FAST FLASH SIMULTANEOUS FAST FLASH Normal operation Signaled when heating demand initiated at thermostat SLOW FLASH ON Primary or secondary limit switch op...

Страница 53: ...ved NOTE In Direct Vent systems total the equivalent length of either the exhaust OR intake piping run depending upon which will be LONGER Intake and exhaust pipe diameter must be the same size and mu...

Страница 54: ...eight 8 feet above grade di rectly in line with the exhaust vent terminal for the hori zontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half...

Отзывы: