![Lennox G32 SERIES Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/lennox/g32-series/g32-series_unit-information_1877490038.webp)
Page 38
G32−2 &−3
HEATING SEQUENCE OF OPERATION
NORMAL HEATING MODE
ABNORMAL HEATING MODE
CONTROL SELF−CHECK OKAY?
BURNER OFF?
(CONTINUOUS FLAME CHECK)
NORMAL OPERATION:
LED #1 −− SIMULTANEOUS SLOW FLASH
LED #2 −− SIMULTANEOUS SLOW FLASH
YES
YES
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER DELAY OFF.
LED #1 ON
LED #2 ON
(RESET CONTROL BY TURNING MAIN POWER OFF.)
NO
NO
POLARITY REVERSED.
LED #1 −− FAST FLASH
LED #2 −− SLOW FLASH
NO
POWER ON
COMBUSTION AIR BLOWER ON FOR 1 SECOND.
POLARITY OKAY?
ROLLOUT SWITCH CLOSED?
THERMOSTAT CALLS FOR HEAT:
LED #1 −− FAST FLASH
LED #2 −− FAST FLASH
PRIMARY LIMIT SWITCH CLOSED?
PRESSURE SWITCH CONTACTS OPEN?
(HIGH AND LOW HEAT)
TWO−STAGE MODE
CALL FOR 1ST STAGE HEAT
W2 TIMED MODE
SINGLE STAGE T’STAT
SINGLE−STAGE MODE
HIGH HEAT ONLY
COMBUSTION AIR BLOWER
ON LOW SPEED (
t
2.5 MINUTES)
LOW−HEAT PRESSURE
SWITCH CLOSED?
PREPURGE
15 SECONDS
COMBUSTION AIR BLOWER
ON HIGH SPEED (
t
2.5 MINUTES)
HIGH−HEAT PRESSURE
SWITCH CLOSED?
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF DELAY.
LED #1 −− ON
LED #2 −− SLOW FLASH
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
LED #1 −− SLOW FLASH
LED #2 −− OFF
GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF DELAY.
LED #1 OFF
LED #2 SLOW FLASH
(Sequence holds until pressure switch
closes or thermostat resets control.)
PRESSURE SWITCH WATCHGUARD
(5 MINUTES)
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
LED #1 OFF
LED #2 SLOW FLASH
NO
NO
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER ON.
LED #1 −− SLOW FLASH
LED #2 −− ON
NO
NO
YES
YES
NO
YES
YES
YES
ENERGIZE COMBUSTION AIR BLOWER.
ENERGIZE HTG ACC. TERM.
IS UNIT PROPERLY GROUNDED?
IS LINE VOLTAGE ABOVE 75 VOLTS?
YES
YES
NO
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
LED #1 −− ALTERNATING FAST FLASHES
LED #2 −− ALTERNATING FAST FLASHES
WATCHGUARD
60MINUTE DELAY
(SIGNAL LIMIT OR IGNITION FAILURE)
GAS VALVE OFF. COMBUSTION AIR
AND INDOOR BLOWER OFF.
LED #1 AND LED #2
ALTERNATING SLOW FLASHES
CONTINUED ON NEXT PAGE
LED#1 AND #2
ALTERNATING FAST
FLASH. SIGNAL
HOLDS UNTIL UNIT IS
PROPERLY GROUND.
IS THERE A
PROPER GROUND?
IS VOLTAGE
ABOVE 75 VOLTS?
LED #1 AND #2 ALTERNATING FAST FLASH.
SIGNAL HOLDS UNTIL VOLTAGE RISES
ABOVE 75 VOLTS.
NO
YES
NO
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON. LED #1 AND #2
ALTERNATING FAST FLASH. CHECK FOR
BROKEN IGNITOR OR OPEN IGNITOR CIRCUIT.