background image

Page 9

Refrigerant Charge 

ELP units have a factory holding charge of 2 pounds of 

HFC-410A. Additional refrigerant will need to be added 

during installation (table 2).

TABLE 2. Adding Refrigerant

Models

25 Feet

1

 

(pounds

Liquid 

Line  

Dia.  

(inches)

Vapor 

Line  

Dia.  

(inches) 

Ounces  

Adjustment  

per foot of  

line set

2

ELP090 / 

ELA090

23.25

5/8

1-1/8

1.7

ELP120 / 

ELA120

31.0

5/8

1-1/8

1.7

1

Total amount of charge necessary to accommodate 25 

feet of line set.

2

If line set length is greater than 25 feet, add this amount 

to each circuit. If line set is less than 25 feet, subtract this 

amount from each circuit. Refer to Lennox Refrigerant 

Piping Design and Fabrication Guidelines for more infor-

mation.

NOTE 

Refrigerant line sets longer than 200 feet (60 me-

ters) are not recommended. For assistance contact Len-

nox Application Department. 

To charge the system, use either of the following proce-

dures: 

CHARGE PROCEDURE – NORMAL OPERATING 

PRESSURES 

1 -  Connect a manifold gauge set to the service valves: 

A - Low pressure gauge to vapor service port. 
B -  High pressure gauge to liquid valve service port 

2 -   Operate system in cooling mode until pressures 

and temperatures stabilize (5 minutes minimum). 

3 -   

Use a thermometer to measure the outdoor 

ambient temperature. The outdoor temperature will 

determine which charging procedure to use. 

Outdoor Temp > 65ºF (18ºC) 

1 -   Apply the outdoor ambient temperature to table 

4 or 5 to determine normal operating pressures. 

Compare the normal operating pressures to the 

pressures obtained from the connected gauges. 

If discharge pressure is high, remove refrigerant 

from the system. If discharge pressure is low, add 

refrigerant to the system. 

A - Add or remove charge in increments. 
B -   Allow the system to stabilize at least 5 minutes each 

time refrigerant is added or removed 

2 -   

Minor variations in these pressures may be 

expected due to differences in installations. 

Significant differences could mean that the system 

is not properly charged or that a problem exists with 

some component in the system. 

3 - 

 Switch to heating mode to confirm normal operating 

pressures. Let the system stabilize at least 10 

minutes, then compare the pressure obtained from 

the connected gauges to the normal operating 

pressures (heating mode) in table 5.

4 -   Verify the charge, as described in the approach 

method section.

Outdoor Temp < 65ºF (18ºC) 

1 -   When the outdoor ambient temperature is below 

65F (18C) it may be necessary to restrict the air flow 

through the outdoor coil to achieve liquid pressures 

in the 325-375 psig (2240-2585 kPa) range. These 

higher pressures are necessary for checking the 

charge. Block equal sections of the outdoor coil on 

all coil sides until the liquid pressure is in the 325-

375 psig range (figure 4). 

2 -   Charge the unit using the approach method in the 

approach method section. 

3 -   Switch to heating mode and let the system stabilize 

at least 10 minutes. Then confirm that the pressures 

obtained from the connected gauges match the 

normal operating pressures (heating mode) in table 5. 

4 -   

Minor variations in these pressures may be 

expected due to differences in installations. 

Significant differences could mean that the system 

is not properly charged or that a problem exists with 

some component in the system.

CARDBOARD OR

PLASTIC SHEET

OUTDOOR COIL SHOULD BE BLOCKED ONE SIDE AT A TIME

WITH  CARDBOARD  OR  PLASTIC  SHEET  UNTIL  PROPER

TESTING PRESSURES ARE REACHED.

FIGURE 4. Blocking Outdoor Coil

CHARGE PROCEDURE – APPROACH METHOD 

Use the following approach method along with the normal 

operating pressures to confirm readings. 

1 -   

Using the same thermometer, compare liquid 

temperature at service valve to outdoor ambient 

temperature. 

Approach Temperature = Liquid temperature minus 

ambient temperature 

Содержание ELP090S4S

Страница 1: ...tective clothing INSTALLATION INSTRUCTIONS HEAT PUMPS 7 5 AND 10 TONS 507744 01 11 2017 Elite Class ELP Series 7 5 and 10 Ton Shipping and Packing List Check the unit for shipping damage If damaged or...

Страница 2: ...HOLES For Rigging FRONT VIEW TOP VIEW FORKLIFT SLOTS Both Sides SIDE VIEW 1108 48 3 4 1238 3 1 2 89 1149 FF EE INLET AIR INLETAIR B B AA CC DD CENTER OF GRAVITY ELECTRICAL INLETS Above Refrigerant Li...

Страница 3: ...ITCH S24 CTXV SENSING BULB DEFROST SWITCH LOCATION S6 REVERSING VALVE CHECK EXPANSION VALVE CTXV ELP120S4S HIGH PRESSURE SWITCH S4 PRESSURE SWITCH S192 DEFROST SWITCH LOCATION S6 REVERSING VALVE LIQUI...

Страница 4: ...ressor Unit Control Box Components Arrangement ELP090S4S AND ELP120S4S TRANSFORMER T1 CONTACTOR K1 RUN CAPACITORS C1 C2 GROUND LUG TERMINAL STRIP TB14 DEFROST CONTROL BOARD Rigging the Unit for Liftin...

Страница 5: ...LP090 5 8 16mm 1 1 8 29mm ELP120 5 8 16mm 1 1 8 29mm Refrigerant Line Limitations You may install the unit in applications that have line set lengths of up to 50 linear feet 15 m with refrigerant line...

Страница 6: ...DELS NOTE ANY EXCESS HIGH VOLTAGE FIELD WIRING SHOULD BE TRIMMED AND SECURED AWAY FROM ANY LOW VOLTAGE FIELD WIRING ROUTE EARTH GROUND THROUGH LEFT CUTOUT AND CONNECT TO GROUND LUG 2 TYPICAL HIGH VOLT...

Страница 7: ...S C D TIGHTEN WIRE TIE TO SECURE 24VDC CONTROL WIRING NOTE FOR PROPER VOLTAGES SELECT THERMOSTAT WIRE CONTROL WIRING GAUGE PER TABLE ABOVE NOTE WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND MAI...

Страница 8: ...ISCONNECT ALL POWER BEFORE SERVICING 7 C2 C2 B5 MOTOR OUTDOOR FAN 2 CAPACITOR OUTDOOR FAN 2 1 4 K10 1 2 1 K8 1 2 8 5 K8 2 CB8 CIRCUIT BREAKER TRANS T1 S9 T1 TRANSFORMER CONTROL SWITCH DEFROST COMPRESS...

Страница 9: ...gerant is added or removed 2 Minor variations in these pressures may be expected due to differences in installations Significant differences could mean that the system is not properly charged or that...

Страница 10: ...d TABLE 4 HFC 410A Normal Operating Pressures Cooling Mode Liquid 10 and Suction 5 psig Temp ELP090 ELA090 ELP120 ELA120 Liquid Suction Liquid Suction 65 F 18 C 226 119 247 132 75 F 24 C 261 125 291 1...

Страница 11: ...30 475 6 146 579 8 38 113 6 54 152 8 69 197 3 85 254 1 100 317 2 116 396 0 131 481 6 147 586 8 39 115 8 55 155 5 70 200 6 86 258 0 101 321 8 117 401 3 132 487 8 148 593 8 40 118 0 56 158 2 71 203 9 87...

Страница 12: ...s with defrost control 100269 02 The factory de fault defrost interval is 60 minutes Units with defrost control 100269 04 or higher The fac tory default defrost interval is 90 minutes If the timing se...

Страница 13: ...rmal operation Alternating Slow Flash 5 min anti short cycle delay Fault and Lockout Codes OFF Slow Flash Loss of Charge Fault OFF ON Loss of Charge Lockout Slow Flash OFF High Pressure Fault ON OFF H...

Страница 14: ...e or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Vapor Pressure Refrigerant Lines...

Отзывы: