Page 10

2 -   Approach temperature should be as indicated in 

table 3 for each stage. An approach temperature 

greater than this value indicates an undercharge. 

An approach temperature less than this value 

indicates an overcharge. 

A - Add or remove charge in increments. 
B -   Allow system to stabilize at least 5 minutes each 

time refrigerant is added or removed. 

3 -   Do not use the approach method if system pressures 

do not match pressures in table 4 except when the 

outdoor ambient temperature is below 65ºF (18ºC). 

The approach method is not valid for grossly over or 

undercharged systems.

TABLE 3. HFC-410A Approach Temperatures*

Models

Approach  

Temperature (ºF) 

(+/-1)

Approach  

Temperature (ºC) 

(+/-.05)

ELP090S4S / 

ELA090

7.0

3.9

ELP120S4S / 

ELA120

6.0

3.3

*Approach temperature method valid at full load.

TABLE 4. HFC-410A Normal Operating Pressures – Cooling Mode (Liquid 

±

10 and Suction 

±

5 psig)**

Temp*

ELP090 / ELA090

ELP120 / ELA120

Liquid 

Suction

Liquid 

Suction

65º F (18º C)

226

119

247

132

75º F (24º C)

261

125

291

136

85º F (29º C)

303

129

333

138

95º F (35º C)

349

133

370

140

105º F (41º C)

404

135

437

142

115º F (46º C)

462

137

495

144

125º F (52º C)

525

136

562

146

STD. CFM

2760

4000

*Temperature of air entering outdoor coil.

Liquid and suction pressures measured via condenser service valve ports. 

** Indoor conditions – 80° F Dry Bulb and 67° F Wet Bulb.

TABLE 5. HFC-410A Normal Operating Pressures – Heating Mode (Liquid 

±

10 and Suction 

±

5 psig)**

Temp*

ELP090 / ELA090

ELP120 / ELA120

Liquid 

Suction

Liquid 

Suction

60º F (15º C)

364

121

335

115

50º F (10º C)

343

100

322

101

40º F (4º C)

324

83

308

86

30º F (-1º C)

311

72

294

72

20º F (-6º C)

297

57

280

58

10º F (-12º C)

280

44

266

44

STD. CFM

2760

4000

*Temperature of air entering outdoor coil.

Liquid and suction pressures measured via condenser service valve ports. 

** Indoor conditions – 70° F.

Содержание ELP090S4S

Страница 1: ...tective clothing INSTALLATION INSTRUCTIONS HEAT PUMPS 7 5 AND 10 TONS 507744 01 11 2017 Elite Class ELP Series 7 5 and 10 Ton Shipping and Packing List Check the unit for shipping damage If damaged or...

Страница 2: ...HOLES For Rigging FRONT VIEW TOP VIEW FORKLIFT SLOTS Both Sides SIDE VIEW 1108 48 3 4 1238 3 1 2 89 1149 FF EE INLET AIR INLETAIR B B AA CC DD CENTER OF GRAVITY ELECTRICAL INLETS Above Refrigerant Li...

Страница 3: ...ITCH S24 CTXV SENSING BULB DEFROST SWITCH LOCATION S6 REVERSING VALVE CHECK EXPANSION VALVE CTXV ELP120S4S HIGH PRESSURE SWITCH S4 PRESSURE SWITCH S192 DEFROST SWITCH LOCATION S6 REVERSING VALVE LIQUI...

Страница 4: ...ressor Unit Control Box Components Arrangement ELP090S4S AND ELP120S4S TRANSFORMER T1 CONTACTOR K1 RUN CAPACITORS C1 C2 GROUND LUG TERMINAL STRIP TB14 DEFROST CONTROL BOARD Rigging the Unit for Liftin...

Страница 5: ...LP090 5 8 16mm 1 1 8 29mm ELP120 5 8 16mm 1 1 8 29mm Refrigerant Line Limitations You may install the unit in applications that have line set lengths of up to 50 linear feet 15 m with refrigerant line...

Страница 6: ...DELS NOTE ANY EXCESS HIGH VOLTAGE FIELD WIRING SHOULD BE TRIMMED AND SECURED AWAY FROM ANY LOW VOLTAGE FIELD WIRING ROUTE EARTH GROUND THROUGH LEFT CUTOUT AND CONNECT TO GROUND LUG 2 TYPICAL HIGH VOLT...

Страница 7: ...S C D TIGHTEN WIRE TIE TO SECURE 24VDC CONTROL WIRING NOTE FOR PROPER VOLTAGES SELECT THERMOSTAT WIRE CONTROL WIRING GAUGE PER TABLE ABOVE NOTE WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND MAI...

Страница 8: ...ISCONNECT ALL POWER BEFORE SERVICING 7 C2 C2 B5 MOTOR OUTDOOR FAN 2 CAPACITOR OUTDOOR FAN 2 1 4 K10 1 2 1 K8 1 2 8 5 K8 2 CB8 CIRCUIT BREAKER TRANS T1 S9 T1 TRANSFORMER CONTROL SWITCH DEFROST COMPRESS...

Страница 9: ...gerant is added or removed 2 Minor variations in these pressures may be expected due to differences in installations Significant differences could mean that the system is not properly charged or that...

Страница 10: ...d TABLE 4 HFC 410A Normal Operating Pressures Cooling Mode Liquid 10 and Suction 5 psig Temp ELP090 ELA090 ELP120 ELA120 Liquid Suction Liquid Suction 65 F 18 C 226 119 247 132 75 F 24 C 261 125 291 1...

Страница 11: ...30 475 6 146 579 8 38 113 6 54 152 8 69 197 3 85 254 1 100 317 2 116 396 0 131 481 6 147 586 8 39 115 8 55 155 5 70 200 6 86 258 0 101 321 8 117 401 3 132 487 8 148 593 8 40 118 0 56 158 2 71 203 9 87...

Страница 12: ...s with defrost control 100269 02 The factory de fault defrost interval is 60 minutes Units with defrost control 100269 04 or higher The fac tory default defrost interval is 90 minutes If the timing se...

Страница 13: ...rmal operation Alternating Slow Flash 5 min anti short cycle delay Fault and Lockout Codes OFF Slow Flash Loss of Charge Fault OFF ON Loss of Charge Lockout Slow Flash OFF High Pressure Fault ON OFF H...

Страница 14: ...e or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Vapor Pressure Refrigerant Lines...

Отзывы: